ECG Engineering Consultants Group

PROJECT: NOZHA CITY CENTER


DATE : MAY 2007

SUBJECT : ESTIMATE COOLING LOAD CALCULATIONS FOR FIRST FLOOR

AREA
SERIAL

HEIGH

NO. OF

F.A PER TOTAL F.A

COOLING

TOTAL

WATER

ZONE NAME

REV.

M2

PERSONS

PERSON

CFM

CAPACITY T.R.

GPM

CFM
F.A %

T.R./M2

design data effected

ONE A/C

CFM

NOTES
PER T.R Lighting W/F2 EQ.KW EQ.W/F2

L1-00

70

5.6

14

11

147

3.2

5.3

22.1

1634

231

516

4.5

0.4

0.5

TREATED F/A

L1-105

52

5.6

10

11

109

2.4

3.9

22.1

1214

171

516

4.5

0.3

0.5

TREATED F/A

L1-106

70

5.6

14

11

147

3.2

5.3

22.1

1634

231

516

4.5

0.4

0.5

TREATED F/A

L1-107

47

5.6

11

99

2.1

3.6

22.1

1097

155

516

4.5

0.2

0.5

TREATED F/A

L1-108

47

5.6

11

99

2.1

3.6

22.1

1097

155

516

4.5

0.2

0.5

TREATED F/A

L1-109

70

5.6

14

11

147

3.2

5.3

22.1

1634

231

516

4.5

0.4

0.5

TREATED F/A

L1-110

52

5.6

10

11

109

2.4

3.9

22.1

1214

171

516

4.5

0.3

0.5

TREATED F/A

L1-118

146

5.6

29

11

307

6.7

11.1

21.9

3440

481

516

4.5

0.7

0.5

TREATED F/A

L1-119

133

5.6

27

11

279

6.1

10.1

21.9

3134

438

516

4.5

0.7

0.5

TREATED F/A

10

L1-120

67

5.6

13

11

141

3.1

5.1

21.9

1579

221

516

4.5

0.3

0.5

TREATED F/A

11

L1-121

118

5.6

24

11

248

5.4

9.0

21.9

2780

389

516

4.5

0.6

0.5

TREATED F/A

12

L1-122

114

5.6

23

11

239

5.2

8.7

21.9

2686

376

516

4.5

0.6

0.5

TREATED F/A

13

L1-123

112

5.6

22

11

235

5.1

8.5

21.9

2639

369

516

4.5

0.6

0.5

TREATED F/A

14

L1-124

113

5.6

23

11

237

5.2

8.6

21.9

2662

372

516

4.5

0.6

0.5

TREATED F/A

15

L1-125

100

5.6

20

11

210

4.6

7.6

21.9

2356

329

516

4.5

0.5

0.5

TREATED F/A

16

L1-126

124

5.6

25

11

260

5.7

9.5

21.9

2922

408

516

4.5

0.6

0.5

TREATED F/A

17

L1-127

74

5.6

15

11

155

3.5

5.9

21.0

1818

244

516

4.5

0.4

0.5

TREATED F/A

18

L1-128

145

5.6

29

11

305

6.9

11.5

21.0

3563

478

516

4.5

0.7

0.5

TREATED F/A

19

L1-129

160

5.6

32

11

336

7.6

12.7

21.0

3931

527

516

4.5

0.8

0.5

TREATED F/A

20

L1-130

177

5.6

35

11

372

8.4

14.1

21.0

4349

583

516

4.5

0.9

0.5

TREATED F/A

21

L1-131

73

5.6

15

11

153

3.2

5.3

23.0

1638

240

516

4.5

0.4

0.5

TREATED F/A

22

L1-132

102

5.6

20

11

214

4.4

7.4

23.0

2288

336

516

4.5

0.5

0.5

TREATED F/A

23

L1-133

164

5.6

33

11

344

7.5

12.4

22.0

3869

540

519

4.5

0.8

0.5

TREATED F/A

24

L1-134

148

5.6

30

11

311

6.4

10.7

23.0

3320

488

516

4.5

0.7

0.5

TREATED F/A

25

L1-135

60

5.6

12

11

126

2.7

4.6

22.0

1396

198

512

4.5

0.3

0.5

TREATED F/A

26

L1-136

112

5.6

22

11

235

5.1

8.5

22.0

2607

369

512

4.5

0.6

0.5

TREATED F/A

ECG Engineering Consultants Group


PROJECT: NOZHA CITY CENTER
DATE : MAY 2007

SUBJECT : ESTIMATE COOLING LOAD CALCULATIONS FOR FIRST FLOOR

AREA
SERIAL

HEIGH

NO. OF

F.A PER TOTAL F.A

COOLING

TOTAL

WATER

ZONE NAME

REV.

M2

PERSONS

PERSON

CFM

CAPACITY T.R.

GPM

CFM
F.A %

T.R./M2

design data effected

ONE A/C

CFM

NOTES
PER T.R Lighting W/F2 EQ.KW EQ.W/F2

27

L1-137

164

5.6

33

11

344

7.5

12.5

21.9

3893

540

519

4.5

0.8

0.5

TREATED F/A

28

L1-138

164

5.6

33

11

344

7.5

12.5

21.9

3887

540

519

4.5

0.8

0.5

TREATED F/A

29

L1-139

164

5.6

33

11

344

7.5

12.5

21.9

3887

540

519

4.5

0.8

0.5

TREATED F/A

30

L1-140

164

5.6

33

11

344

7.5

12.5

21.9

3887

540

519

4.5

0.8

0.5

TREATED F/A

31

L1-141

126

5.6

25

11

265

5.8

9.6

21.9

2986

415

519

4.5

0.6

0.5

TREATED F/A

32

L1-142

70

5.6

14

11

147

3.2

5.3

21.9

1659

231

519

4.5

0.4

0.5

TREATED F/A

33

L1-143

164

5.6

33

11

344

7.5

12.5

21.9

3887

540

519

4.5

0.8

0.5

TREATED F/A

34

L1-144

164

5.6

33

11

344

7.5

12.5

21.9

3887

540

519

4.5

0.8

0.5

TREATED F/A

35

L1-145

164

5.6

33

11

344

7.5

12.5

21.9

3887

540

519

4.5

0.8

0.5

TREATED F/A

36

L1-146

100

5.6

20

11

210

4.6

7.6

21.9

2370

329

519

4.5

0.5

0.5

TREATED F/A

37

L1-147

100

5.6

20

11

210

4.6

7.6

21.9

2370

329

519

4.5

0.5

0.5

TREATED F/A

38

L1-148

100

5.6

20

11

210

4.6

7.6

21.9

2370

329

519

4.5

0.5

0.5

TREATED F/A

39

L1-149

33

5.6

11

69

1.5

2.5

21.9

782

109

519

4.5

0.2

0.5

TREATED F/A

40

L1-150

86

5.6

17

11

181

3.9

6.6

21.9

2038

283

519

4.5

0.4

0.5

TREATED F/A

41

L1-151

142

5.6

28

11

298

6.5

10.8

21.9

3365

468

519

4.5

0.7

0.5

TREATED F/A

42

L1-152

149

5.6

30

11

313

6.8

11.4

21.9

3531

491

519

4.5

0.7

0.5

TREATED F/A

43

L1-153

153

5.6

31

11

321

7.0

11.7

21.9

3626

504

519

4.5

0.8

0.5

TREATED F/A

44

L1-154

106

5.6

21

11

223

4.8

8.1

21.9

2512

349

519

4.5

0.5

0.5

TREATED F/A

45

L1-154A

135

5.6

27

11

284

6.2

10.3

21.9

3199

445

519

4.5

0.7

0.5

TREATED F/A

46

L1-155

149

5.6

30

11

313

6.8

11.4

21.9

3531

491

519

4.5

0.7

0.5

TREATED F/A

47

L1-156

142

5.6

28

11

298

6.5

10.8

21.9

3365

468

519

4.5

0.7

0.5

TREATED F/A

48

L1-157

132

5.6

26

11

277

6.0

10.1

21.9

3128

435

519

4.5

0.7

0.5

TREATED F/A

49

L1-158

120

5.6

24

11

252

5.5

9.2

21.9

2844

395

519

4.5

0.6

0.5

TREATED F/A

50

L1-160

100

5.6

20

11

210

4.6

7.6

21.9

2370

329

519

4.5

0.5

0.5

TREATED F/A

51

L1-161

100

5.6

20

11

210

4.6

7.6

21.9

2370

329

519

4.5

0.5

0.5

TREATED F/A

52

L1-162

100

5.6

20

11

210

4.6

7.6

21.9

2370

329

519

4.5

0.5

0.5

TREATED F/A

ECG Engineering Consultants Group


PROJECT: NOZHA CITY CENTER
DATE : MAY 2007

SUBJECT : ESTIMATE COOLING LOAD CALCULATIONS FOR FIRST FLOOR

AREA
SERIAL

HEIGH

NO. OF

F.A PER TOTAL F.A

COOLING

TOTAL

WATER

ZONE NAME

REV.

M2

PERSONS

PERSON

CFM

CAPACITY T.R.

GPM

CFM
F.A %

T.R./M2

design data effected

ONE A/C

CFM

NOTES
PER T.R Lighting W/F2 EQ.KW EQ.W/F2

53

CS-002

56.25

5.6

40

20

804

7.9

13.3

7.1

1790

45

185

225

4.5

1.1

2.0

TREATED F/A

54

CS-003

56.25

5.6

40

20

804

7.9

13.3

7.1

1790

45

185

225

4.5

1.1

2.0

TREATED F/A

55

FC-01

65.5

5.6

22

20

437

3.5

5.9

18.5

1926

23

216

544

3.0

3.3

5.0

TREATED F/A

56

FC-02

65.5

5.6

22

20

437

3.5

5.9

18.5

1926

23

216

544

3.0

3.3

5.0

TREATED F/A

57

FC-03

71

5.6

24

20

473

3.8

6.4

18.5

2088

23

234

544

3.0

3.6

5.0

TREATED F/A

58

FC-04

34

5.6

11

20

227

1.8

3.1

18.5

1000

23

112

544

3.0

1.7

5.0

TREATED F/A

59

FC-05

34

5.6

11

20

227

1.8

3.1

18.5

1000

23

112

544

3.0

1.7

5.0

TREATED F/A

60

FC-06

34

5.6

11

20

227

1.8

3.1

18.5

1000

23

112

544

3.0

1.7

5.0

TREATED F/A

61

FC-07

34.5

5.6

12

20

230

1.9

3.1

18.5

1014

23

114

544

3.0

1.7

5.0

TREATED F/A

62

FC-08

105

5.6

35

20

700

5.7

9.5

18.5

3088

23

346

544

3.0

5.3

5.0

TREATED F/A

63

FC-09

67

5.6

22

20

447

3.6

6.0

18.5

1970

23

221

544

3.0

3.4

5.0

TREATED F/A

64

FC-10

69

5.6

23

20

460

3.7

6.2

18.5

2029

23

227

544

3.0

3.5

5.0

TREATED F/A

65

FC-11

34.5

5.6

12

20

230

1.9

3.1

18.5

1014

23

114

544

3.0

1.7

5.0

TREATED F/A

66

FC-12

34.5

5.6

12

20

230

1.9

3.1

18.5

1014

23

114

544

3.0

1.7

5.0

TREATED F/A

67

FC-13

34.5

5.6

12

20

230

1.9

3.1

18.5

1014

23

114

544

3.0

1.7

5.0

TREATED F/A

68

FC-14

34.5

5.6

12

20

230

1.9

3.1

18.5

1014

23

114

544

3.0

1.7

5.0

TREATED F/A

69

FC-15

68.5

5.6

23

20

457

3.7

6.2

18.5

2014

23

226

544

3.0

3.4

5.0

TREATED F/A

70

FC-16

65.5

5.6

22

20

437

3.5

5.9

18.5

1926

23

216

544

3.0

3.3

5.0

TREATED F/A

71

FC-17

65.5

5.6

22

20

437

3.5

5.9

18.5

1926

23

216

544

3.0

3.3

5.0

TREATED F/A

20197

336.9

562.6

20.7

6970.5

ECG Engineering Consultants Group


PROJECT: NOZHA CITY CENTER
DATE : MAY 2007

SUBJECT : ESTIMATE COOLING LOAD CALCULATIONS FOR FIRST FLOOR

AREA
SERIAL

HEIGH

NO. OF

F.A PER TOTAL F.A

COOLING

TOTAL

WATER

ZONE NAME

REV.

M2

PERSONS

PERSON

CFM

CAPACITY T.R.

GPM

CFM
F.A %

T.R./M2

design data effected

ONE A/C

CFM

NOTES
PER T.R Lighting W/F2 EQ.KW EQ.W/F2

72

M1-01

1404

5.6

281

11

3021

63.0

105.2

22.3

24285

12

4625

385

4.5

7.0

0.5

NORMAL F/A

73

M1-02

1174

5.6

235

11

2658

58.0

96.8

20.3

22795

12

3867

393

4.5

5.9

0.5

NORMAL F/A

74

M1-03

915

5.6

183

11

2034

46.3

77.4

19.7

18580

11

3014

401

4.5

4.6

0.5

NORMAL F/A

75

R1-01

137

5.6

69

20

1370

14.3

23.8

9.6

3454

40

451

242

3.0

1.4

1.0

NORMAL F/A

76

R1-02

127

5.6

64

20

1270

13.2

22.1

9.6

3188

40

418

241

3.0

1.3

1.0

NORMAL F/A

77

R1-03

316

5.6

158

20

3160

32.9

55.0

9.6

8065

39

1041

245

3.0

3.2

1.0

NORMAL F/A

78

R1-04

119

5.6

60

20

1190

12.4

20.7

9.6

3000

40

392

242

3.0

1.2

1.0

NORMAL F/A

79

R1

108

5.6

54

20

1080

11.6

19.4

9.3

2787

39

356

240

3.0

1.1

1.0

NORMAL F/A

80

R1

99

5.6

50

20

990

10.6

17.8

9.3

2502

40

326

235

3.0

1.0

1.0

NORMAL F/A

81

PRAY AREA

272

5.6

272

20

5440

50.8

84.9

5.4

8355

65

896

164

3.0

1.0

0.4

NORMAL F/A

82

LAND MARK

4483

5.6

897

11

9925

199.0

332.3

22.5

75575

13

14768

380

4.5

11.2

0.3

NORMAL F/A

83

MAGIC LAND

1584

5.6

396

25

9925

118.0

197.1

13.4

47900

21

5218

406

10.0

NORMAL F/A

84

FOOD COURT

1330

5.6

665

20

13300

100.6

167.9

13.2

19950

67

4381

198

3.0

1.3

0.1

NORMAL F/A

85

FIRST CORRIDOR

4756

5.6

476

12

5707

134.0

223.8

35.5

54395

10

15667

406

3.0

1.2

0.0

NORMAL F/A

86

SETTING AREA

938

5.6

670

12

8040

85.4

142.6

11.0

18840

43

3090

221

3.0

1.1

0.1

NORMAL F/A

87

ALL CORRIDORES

699

5.6

70

12

839

18.0

30.1

38.8

9000

2303

500

3.0

1.0

0.2

NORMAL F/A

88

ELEC

40

5.6

12

24

2.2

3.7

18.0

1133

132

510

2.0

0.8

2.0

TREATED F/A

89

LC

18

5.6

12

24

1.0

1.7

18.0

510

59

510

2.0

0.4

2.0

TREATED F/A

110390

1308.3

25489.5

TOTAL FRESH AIR ENTRING THE BUILDING =


TOTAL TREATED FRESH AIR FOR THE BUILDING CFM =
TOTAL LOAD TREATED FRESH AIR FOR THE FIRST FLOOR =

110390 CFM
20245 CFM
135 TR

TOTAL LOAD OF THE BUILDING WITH OUT F/A =

1308 TR

TOTAL LOAD OF THE FIRST FLOOR =

1443 TR