Académique Documents
Professionnel Documents
Culture Documents
In this lab, student had doing test setting for relay. The minimum current to check relay pick start
function with test setting is 1.01A. Then, they do timing checks with test setting. Graph 1 show
the data taken from the test based on table timing checks with test setting. For perfect result all
the value should be equal to 1A follow the final setting of the relay. However, the reading taken
was just nice since all the values were within range of 5% of 1A.
1.02
1.02
E/F (s)
1.01
1.01
1
E/F (S)
1
0.99
0.99
0.98
1.3A
2.0A
3.0A
4.0A
5.0A
Introduction
Earth-fault relay is used to protect feeder against faults involving ground. Typically, earth
faults are single line to ground and double line to ground faults. For the purpose of setting and
coordination, only single line to ground faults is considered. In generally, earth fault relay is used
to operate the leakage current to the earth. There are two types of configuration:
grounding enables electrical systems to continue running when one of the phases is faulted. This
prevents interruptions to the power supply. This kind of earthing system provides time to
identify and isolate the fault.