DESIGN OF RINGWALL
GEOMETRICAL CONSIDERATIONS:
1. Thickness - (i) Minimum thick of ring wall shall not be lesss than
300mm as per API650.
(ii) The centreline diameter of the ringwall should be equal to
nominal diameter of the tank or PCD line of the tank.
ANALYTICAL CONSIDERATIONS:
2. Minimum height rise of the tank above FFL/FGl shall not be less
than 300 mm.
(ii) Shear and moment at base of the tank due to Wind & Seismic loads
- from mechanincal vendor.
(iii) Percentage of tank load acting on the ringwall and on enclosed soil
are calculated based on the ratio of area it bears the tank.
DESIGN :
Reinforcement for hoop tension:
(i) hoop tension / yeild stress of steel = Ast .
(ii) Area of steel require due to hoop tension is horizontal bars of
ringwall.
(iii) Total hoop steel area required shall not be less than the area of
steel required for temperature changes & shrinkages ie., 0.025 times the
vertical cross-sectional area of the ringwall.
Vertical Reinforcement:
(i) One meter width strip wall considered and it has to be designed for
bending moments due to : Given Moment (EQ/WL) , moment from
shear due to EQ or WL and earth pressure.
(ii) Minimum Vertical reinforcement required for temperature &
shrinkage is 0.0015 times the horizontal cross-sectional area of the
ringwall.