Académique Documents
Professionnel Documents
Culture Documents
MDB-1(Existing Modified)
FEED FROM: METER 1
CIRCUIT
FEEDER
DB. NO
PVC
SWA
XLPE
CABLE SIZE
2/4X1C 2/4X2C
SQ.MM SQ.MM
BY DEWA
MCCB
DUTY
KA
TP
400 N/A
50
DB-GR-1
TP
32
25
4c x 10 sqmm (XLPE)
DB-GR-2
TP
40
25
4c x 10 sqmm (XLPE)
DB SHED
PUMP-3
PUMP-4
PUMP-5
PUMP-6
TP
TP
TP
TP
TP
TP
TP
32
20
20
20
20
25
25
25
25
25
35
35
4c x 10 sqmm (XLPE)
4c x 6 sqmm (XLPE)
4c x 6 sqmm (XLPE)
4c x 6 sqmm (XLPE)
4c x 6 sqmm (XLPE)
4c x 185sqmm (XLPE)
INCOMER
SP TP
ISO ACB
ECC
SIZE
SQ.MM
2x1cx150
CONNCETED LOAD
KWHR METER
RPH
YPH
BPH
RYB
64.37
65.87
64.56
3.50
3.50
3.50
10.50
4.00
4.00
4.00
12.00
3.00
1.50
1.50
1.50
1.50
3.00
1.50
1.50
1.50
1.50
3.00
1.50
1.50
1.50
1.50
37.87
39.37
38.06
10.00
10.00
10.00
9.00
4.50
4.50
4.50
4.50
115.30
30.00
REMARKS
3 CT
FULL LOAD
AMP/PH
OUTGOING
SMDB-1
SPARE
225
63
10
10
10
4
4
4
4
95
EXISTING
EXISTING
EXISTING
40A,30ma ELCB (Existing)
40A,30ma ELCB (Existing)
40A,30ma ELCB (Existing)
40A,30ma ELCB (Existing)
PROPOSED
PROPOSED
1
194.80
165.58
KW
MDB-2
FEED FROM: METER 1
CIRCUIT
FEEDER
DB. NO
INCOMER
RATING IN AMPS
SP
TP
TP
ISO
ACB
MCCB
FAULT
DUTY
KA
400 N/A
50
PVC
SWA
XLPE
CABLE SIZE
2/4X1C
SQ.MM
2/4X2C
SQ.MM
ECC
CONNCETED LOAD
KWHR METER
SIZE
SQ.MM
RPH
YPH
BPH
BY DEWA
2x1cx150
72.95
72.45
70.50
16
25
16
25
10
25
12.95
14.30
15.62
14.42
11.90
13.98
RYB
12.05
39.30
14.42
44.46
11.25
11.55
34.70
13.98
13.98
41.94
3.50
3.50
3.50
10.50
15.00
15.00
15.00
45.00
39,000
44,460
34,700
41,940
10,500
45,000
72.45
70.50
REMARKS
CT
FULL LOAD
AMP/PH
OUTGOING
DB-GF
TP
80
35
4c x 25 sqmm (XLPE)
DB-AC-1
TP
100
35
4c x 35 sqmm (XLPE)
DB-FF
TP
80
35
4c x 25 sqmm (XLPE)
DB-AC 2
TP
100
35
4c x 35 sqmm (XLPE)
Lift
TP
40
35
4c x 10 sqmm (XLPE)
SWIMMING POOL
TP
100
35
4c x 35 sqmm (XLPE)
72.95
215.90
183.52
40A,300ma ELCB
100A,100ma ELCB
KW
PROVIDE CT METER ABOVE MAX DEMAND
SMDB-1
FEED FROM: MDB-1
CIRCUIT
FEEDER
DB. NO
RATING IN AMPS
ECC
SIZE
SQ.MM
50
CABLE SIZE
PVC
SWA
2/4X1C
2/4X2C
XLPE
SQ.MM
SQ.MM
4c x 185 sqmm (XLPE)
100
35
4c x 35 sqmm (XLPE)
80
35
4c x 25 sqmm (XLPE)
TP
63
35
4c x 35 sqmm (XLPE)
TP
TP
20
20
25
25
4c x 4 sqmm (XLPE)
4c x 4 sqmm (XLPE)
MCCB
FAULT
DUTY
KA
TP
225 N/A
DB service
TP
DB Majlis
TP
DB FARMERS ROOM
PUMP-1
PUMP-2
INCOMER
SP TP
ISO
ACB
CONNCETED LOAD
KWHR METER
RYB
REMARKS
RPH
YPH
BPH
CT
95
37.87
39.37
38.06
25
16
16.47
16.82
15.72
49.00
11.40
12.55
12.35
36.30
25
4
4
7.00
7.00
7.00
21.00
PROPOSED
PROPOSED
EXISTING
1.50
1.50
1.50
1.50
1.50
1.50
4.50
4.50
FULL LOAD
AMP/PH
OUTGOING
37.87
39.37 38.06
115.30
98.00
KW