device.

Alternatively, logical blocks


and function modules can be used
for the implementation.
Some sources recommend a delay of
up to a few minutes after a trip of
the network protection during a fault
on the network before reclosing.
Therefore, a release signal according to Figure 6 for reclosing, is necessary and
specified for power plants connected to the medium voltage network
The reclosure is enabled if:

A specified time has passed after the trip


The network frequency is within a given range
The three line to line voltages of the network are above 95% of their nominal
value