Automation systems (PLC, DCS) maintenance plan and reliability 

By Carlo Lebrun (Ecisgroup Spa) 

Some definitions first 
Maintenance could be defined as:  

“All actions performed with the objective to keep an item in its full functional state.”  

In general maintenance can be further defined according to the following types: 

1. Breakdown maintenance: An item gets repaired when it breaks or fails. 

2. Preventive maintenance: regular activity (cleaning, lubricating, replacing, etc.) is performed in 
order to keep the functional condition. It can be further split into periodic maintenance (based on 
absolute time ) and predictive maintenance (based on working conditions, e.g. 2000 hrs running at 
90% of load). 

3. Corrective maintenance: It improves equipment with design issues. Weak design requires 
improvement to keep or to improve functionality. Note: the term is often but improperly used 
instead of “breakdown maintenance”. 

4. Maintenance prevention: design actions are performed to reduce maintenance requirements, 
based on the analysis of past experience with similar equipment (lesson learned). 

And to keep our installed equipment in good shape we should perform at least the first two: 

‐ restore the full functionality every time a certain type of  failure is detected by the system itself 

‐ regularly inspect the system, and re‐establish the full functionality in case the inspection shows 
some performance decrease 

Today we often tend to Reliability Centered Maintenance (RCM). This is meant as the optimal balance 
between lower activity cost and higher equipment reliability. 

The technical standard SAE  JA 1011 “Evaluation Criteria for RCM Processes” sets the criteria to implement 
Reliability Centered Maintenance. It is based on the questions here below, to be answered in the given 
sequence: 

1. What is the item supposed to do and its associated performance standards? 

2. In what ways can it fail to provide the required functions? 

3. What are the events that cause each failure? 

4. What happens when each failure occurs? 

5. In what way does each failure matter? 
6. What systematic task can be performed proactively to prevent, or to decrease the consequences of 
the failure? 

7. What should be done if a suitable proactive task cannot be found? 

Maintenance improves Reliability  
Automation systems like PLC , DCS, ESD, HIPPS logic solvers, etc. require maintenance just as any other 
equipment. Regular preventive maintenance helps to keep the desired functionality and minimize the risk 
of failures. 

Although they are apparently static and reliable devices they are subject to changes of their working 
conditions which may affect or breach their functionality. 

When the automation equipment is also in charge of a protective function (like an HIPPS logic solver, and 
we call it Safety Instrument System: SIS) we then fall in the field of functional safety (portion of safety that 
depends on the correct functionality of an equipment). 

As a consequence if we deal with functional safety requirements (often defined as SIL classification) we are 
then obliged to respect and document a precise maintenance plan, together with a periodic total or partial 
verification of the equipment functionality, the “proof test interval”. 

The declared reliability of a PLC (or other “logic solver”) is not an intrinsic and stable feature. It is a dynamic 
condition, which can change due to several causes, including the correct actuation of the planned 
maintenance. The usual metric is the Probability of Failure on Demand (PFD). PFD is normally considered as 
increasing with time. A 100% proof test of functionality would make the PFD restart from the lowest level. 
And SIL classification  is based on the Average PFD during the Safety system lifecycle. 

Maintenance will ensure that any known possible degradation of functionality is prevented or detected on 
time. 

The value of declared failure rates 
We often hear that electronic equipment has its own failure rate. It is not always easy to understand if a 
failure of an electronic module  is due to an intrinsic feature or to some external cause. But indeed we have 
to admit that we are not really able to track all possible causes. So let’s accept there is an intrinsic failure 
rate for each equipment.  

When we read a manufacturer IEC61508 certification for a component, we should read the declared data 
as the intrinsic failure rates, assuming perfect design, installation, environmental conditions, etc. 

And if the manufacturer declares only the SIL or the PFD values that’s even worst: these should be taken as 
the most optimistic data, assuming some hidden proof test time interval, some hidden percentage of 
common cause of failures, etc. 

We should carefully evaluate the applicability of all these assumptions. 
Do you know any PLC/DCS manufacturer who declared their equipment failure rates instead of just the PFD 
values in their IEC61508 certification? I don’t. 

Do you know any PLC/DCS manufacturer who declared their assumptions in their IEC61508 certification? I 
don’t. 

Negative answers, but it doesn’t really matter too much: their evaluation are usually based on theoretical 
calculations based on the detail list of electronic subcomponents, each of them with a specific failure rate.  

Can you believe the result? I don’t. But you can use it as a starting value …  

Therefore the IEC61508 manufacturer declaration should allow us to estimate the “ideal” failure rate of the 
equipment in use. 

As an alternative we can use a failure rates  database issued by  some organization or authority working 
with functional safety (Exida, OREDA, OLF, etc.). At least these guys declare clearly their assumptions. 

Here is a table A.3 portion from APPLICATION OF IEC 61508 AND IEC 61511 IN THE NORWEGIAN 
PETROLEUM INDUSTRY Rev. 2 by OLF (also called “OLF‐070 guidelines”, see  www.itk.ntnu.no/sil ) 

Possible causes of failures 
As we said the declared failure rates mostly assume that everything is perfect out of the boundaries of our 
component, which is not always true. 

But several other causes may affect the frequency of failures.  

We recall here several possible issues that we are aware of (there are surely other!): 
‐ Ambient (and/or cabinets) temperature  above tolerated limits: overheating can degrade 
components, and even cause fires. Normally different conditions are specified for operation and for 
storage. 

‐ Ambient (and/or cabinets) temperature  oscillations: thermal expansion could materials 
degradation or repeated movement up to loss of electrical contact       

‐ Moisture / humidity above tolerated limits: Humidity can provoke short circuits, and facilitate 
corrosion or materials degradation. 

‐ Dust: deposits can limit the thermal exchange and promote overheating. If we consider that our 
equipment is normally installed in ventilated cabinet dust can also plug the filters and reduce the 
ventilation effect. In some cases dust can be conductive (from metals or from coal) and can 
provoke short circuits.  

‐ Corrosion: exposure to corrosive environments can cause materials degradation. Corrosion maybe 
often caused or enhanced by dust and by humidity(even when below the tolerated limits!)   

‐ Electromagnetic interference: radio waves can affect electrical equipment. Nowadays the 
technology improvements have significantly reduced the importance of this issue. 

‐ Power Supply stability: fluctuations beyond the specified limits can affect PLC/DCS functionality. 
The use of separate power supplies for separate functions is mostly recommended. Avoid to use 
automation equipment power supply for other purposes like e.g. soldering, welding or brewing 
coffee. 

‐ Vibration: vibration could provoke physical breaks and components or cables disconnection, with 
loss of electrical contact. Vibration could be caused by earthquakes, but also by machinery in 
operation and by human activities during construction. 

‐ Age: it may degrade some materials like e.g. condensers and transformers filling and 
isolation(dielectric materials). This effect is normally defeated by regular replacement of some 
components (typically power supply units) every specific time interval.         

‐ Grounding / Earthing: bad grounding can cause power supply instability and also network 
communication problems. Complete isolation from rest of the plant is essential. Neutral to ground 
voltage to be less than 1 V. All metal parts of the cabinet and in the cabinet  shall be connected to 
ground.  

‐ Induced currents: incorrect routing of power cables close to automation system cables (e.g. I/O 
wirings) can cause induced currents which may lead to signal spikes or even I/O modules failure. 
Shielded and grounded cables for power and control circuits are usually recommended.     

‐ Do not allow the welding or any high current drawing activity near the cabinet or power from the 
cabinet.        

‐ I/O short circuits: I/O cards should be isolated from external shorts         

‐ Wildlife: ants, rats, squirrels, bats can damage equipment and gnaw cables. Sometimes they do not 
cause a direct damage but they can hinder maintenance (wasps, etc.)         
‐ Design problems: let’s not forget they can exist. 

‐ Maintenance: mistakes, distractions, underestimated impact on other equipment,  missing or 
wrong documentation, etc. can also cause actions on the wrong piece of equipment. 

‐ Human unauthorized access: voluntary sabotage or involuntary damage action should also be 
considered in the development of access procedures to control rooms and cabinets security. 

‐ Housekeeping: beware of external objects ,wastes, and swarf in the cabinets, or around, or above, 
etc. Some could have different environmental conditions tolerance compared with the real 
equipment. Some materials could be ignited by heating. Some could obstruct ventilation. Some 
could be conductive and provoke short circuits. Take also care of correct doors opening and 
housekeeping of working spaces around the cabinets. 

If the frequency of failures in our plant is clearly higher than the theoretical failure rate it is worth to 
investigate further on the listed topics. 

Do you suffer too many DCS failures? A shortcut assessment 
A standard industrial PLC is considered to have a failure rate 5 failures / 10e6 hours (as per the table 
included above). This number is given for a complete system composed of  1 CPU + 2 I/O cards.  

This gives 5/3  failures / 10e6 hours per each card, which makes 0.0146 failures/year per each hardware 
module card. If your complete system is composed of 100 modules you should then expect about 1.5 
failures/year. 

Too rough? It is. But you should consider the result purely qualitatively, and look at the order of magnitude 
only. 

If you experience 5 failure/year you are still in the same order of magnitude. 

If you experience e.g. 1 failure/month you should then investigate for some external failure cause. 

Planning preventive PLC / DCS maintenance 
For an optimal planning of PLC and DCS preventive maintenance we should also balance the value of any 
check and inspection with the risk associated with it. In fact some tests can require to temporarily force the 
system to a degraded functionality, and this may be not acceptable: e.g. we do not expect you test the CPU 
backup switch over during plant in operation. 

We could split our preventive maintenance activities like this, assuming we already completed FAT, SAT and 
commissioning: 

‐ Periodical maintenance during plant operation: it will include all checks that can be safely done 
during plant operation, and all checks which MUST be done only during operation. 

‐ Periodical maintenance during  plant  shut down 
‐ Periodical Proof test: it is normally required for SIS protective equipment, with a specific minimum 
frequency (with interval T1) to maintain the desired reliability target. It can be perfect (test of 100% 
of functionality) or non‐perfect (test of less than 100% of functionality). In both cases it is a key 
parameter in the average PFD estimation during the system lifecycle. The Proof Test procedure 
should clearly define the associated plant conditions: in operation or shut‐down. 

Here is a suggested preventive maintenance plan for a BPCS (basic process control system), without need of 
SIL certification: 

  Plant in Operation  Shut‐Down Plant  Proof Test at T1 interval 

Visual inspection of cabinet  Every 6 months  At every planned Shut‐Down  Not applicable 


external and internal 
conditions (housekeeping, 
signs of deterioration, correct 
opening and access space, 
etc.) 

Visual Inspection of system  Every 6 months  At every planned Shut‐Down  Not applicable  


composition and  layout 
(compared to specs) 

Verify environmental  AT LEAST Every 6 months or  At every planned Shut‐Down  Not applicable 


conditions   continuously by data logging   or continuously by data 
logging 

Cleaning of mechanical  Every 6 months (actual period  At every planned Shut‐Down  Not applicable 


devices (peripherals, fans,  can be “tuned” based on past 
filters, etc.)  experience and control room 
cleaness) 

Check of power supply backup  NO, unless strictly necessary  At every planned Shut‐Down  Not applicable 


swap   (*) 

Check quality of power supply  Every 6 months  At every planned Shut‐Down  Not applicable 


and grounding (tension, 
oscillations, backup batteries, 
etc.) 

Periodical replacement of  NO, unless strictly necessary  According to manufacturer  Not applicable 


power supply transformer etc.  (*)   schedule 

Check redundancy and swap  NO, unless strictly necessary  At every planned Shut‐Down if  Not applicable 


of CPU, I/O, communication  (*)  Proof Test is not planned 
cards, etc. 

Backup copy of application  At every modification (for SIS)  NO  Not applicable 


software  or as per backup schedule 
(DCS, etc) 

Firmware upgrade  NO, unless strictly necessary  If required  Not applicable 


(*) 

Application software and  At every modification   At every modification  Not applicable 


hardware documentation 
update 
  Plant in Operation  Shut‐Down Plant  Proof Test at T1 interval 

Maintenance activity log   At every action, planned or  At every action  Not applicable 


exceptional 
 

Verify functionality of the  NO, unless strictly necessary  At every Plant Shutdown  Not applicable 


engineering station  (*) 

Verify electrical components   NO, unless strictly necessary  According to manufacturer  Not applicable 


(fuses, relays, terminals, etc.)  (*)  schedule 

Other checks and  In case system or conditions  Planned plant shutdown are a  Not applicable 


improvements analysis  changes are promoted or  good opportunity for changes 
detected, and possibly before  and improvements 
every planned plant 
shutdown. 

Review of maintenance and  AT LEAST in case of accident  Planned plant shutdown are a  Not applicable 


security procedures  good opportunity for changes 
and improvements 

SW / HW Functionality of  NO, unless strictly necessary  Allowed. Not essential.  Not applicable 


applications   (*) 

SW / HW Functionality of HMI  NO, unless strictly necessary  Allowed. Not essential.  Not applicable 


(keyboards, push buttons,  (*). An exception: the lamps 
graphic displays, etc.)  test is normally allowed and 
harmless. 

System Performances (CPU  Some feature are accessible  Some feature are accessible  Not applicable 


load, system memory, etc.)  only during plant operation.  only during plant shutdown 
Log if possible. 

Note (*): actions which are not recommended as preventive action during plant operation could be anyway 
required in case of breakdown maintenance. 

Here is the equivalent list of preventive maintenance plan for a SIL‐rated PLC protection system (HIPPS, 
ESD, etc.): 

  Plant in Operation  Shut‐Down Plant  Proof Test at T1 interval 

Visual inspection of cabinet  Every 6 months  At every planned Shut‐Down  Yes (**) 


external and internal 
conditions (housekeeping, 
signs of deterioration, correct 
opening and access space, 
etc.) 
  Plant in Operation  Shut‐Down Plant  Proof Test at T1 interval 

Visual Inspection of system  Every 6 months  At every planned Shut‐Down  Yes (**) 


composition and  layout 
(compared to specs) 

Verify environmental  AT LEAST Every 6 months or  At every planned Shut‐Down  Yes 


conditions   continuously by data logging   or continuously by data 
logging 

Cleaning of mechanical  Every 6 months (actual period  At every planned Shut‐Down  Yes 


devices (peripherals, fans,  can be “tuned” based on past 
filters, etc.)  experience and control room 
cleaness) 

Check of power supply backup  NO, unless strictly necessary  At every planned Shut‐Down  Yes (**) 


swap   (*) 

Check quality of power supply  Every 6 months  At every planned Shut‐Down  Yes 


and grounding (tension, 
oscillations, backup batteries, 
etc.) 

Periodical replacement of  NO, unless strictly necessary  According to manufacturer  Yes 


power supply transformer etc.  (*)   schedule 

Check redundancy and swap  NO, unless strictly necessary  At every planned Shut‐Down if  Yes (**) 


of CPU, I/O, communication  (*)  Proof Test is not planned 
cards, etc. 

Backup copy of application  At every modification (for SIS)   NO  Not essential. Changes should 


software  be managed properly 
(reviewing SIL impact). 

Firmware upgrade  NO, unless strictly necessary  If required  Not essential. Changes should 


(*)  be managed properly 
(reviewing SIL impact). 

Application software and  At every modification   At every modification  Yes. Changes should be 


hardware documentation  managed properly (reviewing 
update  SIL impact). 

Maintenance activity log   At every action, planned or  At every action  Yes. For SIL certified system 


exceptional  this is mandatory. 
 

Verify functionality of the  NO, unless strictly necessary  Allowed  Not essential. Changes should 


engineering station  (*)  be managed properly 
(reviewing SIL impact). 

Verify electrical components   NO, unless strictly necessary  According to manufacturer  Yes (**) 


(fuses, relays, terminals, etc.)  (*)  schedule 

Other checks and  In case system or conditions  Planned plant shutdown are a  AT LEAST in case of accident. 


changes are promoted or  good opportunity for changes  Changes should be managed 
  Plant in Operation  Shut‐Down Plant  Proof Test at T1 interval 

improvements analysis  detected, and possibly before  and improvements  properly (reviewing SIL 


every planned plant  impact). 
shutdown. 

Review of maintenance and  AT LEAST in case of accident  Planned plant shutdown are a  AT LEAST in case of accident 


security procedures  good opportunity for changes 
and improvements 

SW / HW Functionality of  NO, unless strictly necessary  Allowed  Yes (**) 


applications   (*) 

SW / HW Functionality of HMI  NO, unless strictly necessary  Allowed.   Yes (**) 


(keyboards, push buttons,  (*). An exception: the lamps 
graphic displays, etc.)  test is normally allowed and 
harmless. 

System Performances (CPU  Some feature are accessible  Some feature are accessible  Yes (**) 


load, system memory, etc.)  only during plant operation.  only during plant shutdown 
Log if possible. 

Note (*): actions which are not recommended as preventive action during plant operation could be anyway 
required in case of breakdown maintenance. 

Note (**): detail procedures can be referred (or even totally match) Factory Acceptance / Site Acceptance 
Tests procedures. These should in fact considered as the correct procedures to test functionality at 100%. 
Proof test can be also deliberately shortcut some test procedures and target less than 100% (a socalled 
non‐perfect proof test).  

 
 

Picture 1: US Navy Construction Electrician checks dirty and corroded wires and circuit breakers from a 
generator damaged by water during the Tsunami that hit Indonesia in Dec. 26, 2004 (Public Domain photo 
by United States Navy , ID 050125‐N‐9712C‐001). 

Picture 2: A clean cabinet filter (left) against a dirty cabinet filter (right). (photo Ecisgroup SpA) 