SUPPLY FROM ESMSB

4 WAYS TP&N MCCB/ELCB (EDB-B1) LOCATION AT 1ST BASEMENT FLOOR


* ELCB / MSSB / ONE UNIT
LOAD IN WATT
DIB CIR.
MCB
SIZE OF WIRE
NO.
AMP.
R
Y
B
300
500

500
500
200

400

5A
5A
5A
5A
5A
5A

3x1.5mm2
3x1.5mm2
3x1.5mm2
3x1.5mm2
3x1.5mm2
3x1.5mm2

20A

4x4mm2+1x4mm2

2000
3

2000

EX.FAN AT 2ND BASEMENT

2000
10A
5A
10A

4
TOTAL
2800
2700
TOTAL CONNECTED LOAD (KW)
MAXIMUM DEMAND LOAD (KW)
25 A TP ISOLATOR

SPARE
SPARE
SPARE

2900
8.4
6.72

DESCRIPTION

3 Nos. LIGHTS AT PARKING


3 Nos. LIGHTS, 1 Nos. EX.FAN , 1 Nos. FRESH FAN AT GENERATOR , ELEC ROOM
5 Nos. LIGHTS AT RAMP
5 Nos. LIGHTS AT RAMP
1 Nos. LIGHT, 1 Nos. EX.FAN AT ELEC ROOM
4 Nos. LIGHTS AT RAMP

SUPPLY FROM ESMSB


4 WAYS TP&N MCCB/ELCB (EDB-B2) LOCATION AT 2ND BASEMENT FLOOR
* ELCB / MSSB / ONE UNIT
LOAD IN WATT
DIB CIR.
MCB
SIZE OF WIRE
NO.
AMP.
R
Y
B
300
500

500
1600
1200

5A
5A
5A
15A
10A
5A

3x1.5mm2
3x1.5mm2
3x1.5mm2
3x4mm2
3x4mm2

20A

4x4mm2+1x4mm2

1800
3

1800
1800

4
TOTAL
3700
3500
TOTAL CONNECTED LOAD (KW)
MAXIMUM DEMAND LOAD (KW)
25 A TP ISOLATOR

2300
9.5
7.60

DESCRIPTION

3 Nos. LIGHTS AT PARKING


3 Nos. LIGHTS , 1 Nos. EX.FAN, 1 Nos. FRESH FAN AT FIRE PUMP, ELEC ROOM AND PUMP ROOM
5 Nos. LIGHTS AT RAMP
11 Nos. LIGHTS and 5 Nos. EMERGENCY EXIT AT STAIR CASE
11 Nos. LIGHTS AND 1 Nos. EMERGENCY EXIT AT LIFT LOBBY
SPARE
EX.FAN AT 2ND BASEMENT

SUPPLY FROM ESMSB


10 WAYS TP&N MCCB/ELCB (DB-OOREDOO) LOCATION AT GROUND FLOOR
* ELCB / MSSB / ONE UNIT
LOAD IN WATT
DIB CIR.
MCB
SIZE OF WIRE
NO.
AMP.
R
Y
B
100
1500

1500
4160

5A
20A*
20A*
40A

3x1.5mm2
3x4mm2
3x4mm2
3x10mm2

10
TOTAL
4260
1500
TOTAL CONNECTED LOAD (KW)
MAXIMUM DEMAND LOAD (KW)
125 A TP ISOLATOR

1500
7.26
5.81

DESCRIPTION

2 Nos. LIGHTS AT OOREDOO ROOM


POWER SOCKET AT OOREDOO ROOM
POWER SOCKET AT OOREDOO ROOM
AC UNIT AT OOREDOO ROOM
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE

SUPPLY FROM ESMSB


6 WAYS TP&N MCCB/ELCB (EDB-R) LOCATION AT ROOF FLOOR
* ELCB / MSSB / ONE UNIT
LOAD IN WATT
DIB CIR.
MCB
SIZE OF WIRE
NO.
AMP.
R
Y
B
600
100

600
100
1500

DESCRIPTION

10A
5A
30A*
20A
20A
20A

3x2.5mm2
3x1.5mm2
4x4mm2+2x2.5mm2
3x4mm2
3x4mm2

6 Nos. LIGHTS AT ROOF


1 Nos. LIGHT AT ROOF
6Nos. RING MAIN SOCKETS AT ROOF
EX.FAN AT ROOF
EX.FAN AT ROOF
SPARE

40A

4x10mm2+1x10mm2 STAIR PRESSURIZATION FAN

4334
4334

4334
620
4

620

20A

4x4mm2+1x4mm2

BOOSTER PUMP

620
5

10A
20A
20A

SPARE
SPARE
SPARE

20A

SPACE

TOTAL
5654
6554
TOTAL CONNECTED LOAD (KW)
MAXIMUM DEMAND LOAD (KW)
50 A TP ISOLATOR

5554
17.762
14.21