SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

1 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

project no.:

41131107/00

FINAL SETTING TEST REPORT

132/33kV SABYA NORTH S/S

132kV FINAL SETTING TEST RESULT


OF
NUMERICAL BUSBAR PROTECTION
MICOM P740
[MICOM P741 (CU) & p743 (PU)]

Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

2 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

project no.:

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

41131107/00

FINAL SETTING TEST REPORT


1. PURPOSE OF TESTS:
The purpose of the tests is to check the full functionality of the protection relay and
the complete scheme related.
2. REFERENCE DOCUMENTS:
DOCUMENT

DOCUMENT
REFERENCE

VERSION/
DATE

REMARKS

Protection Line Diagram


Technical Manual

SA - 039405
P740/EN--/H65

04
NA

OK
OK

3. TERMINOLOGY:
Code ( ANSI)
87BB

Terminology
Low Impedance Busbar Protection

4. TEST EQUIPMENT USED:


Sl No

Description

Make

Equipment
Sl. No.

Calibration
date

Calibration
due date

1.

Secondary
Injection Kit

FREJA 300

3500910

11-July-2014

10-July-2015

2.

Multimeter

FLUKE 289

84490082

10-Mar-2014

9-Mar-2015

3.

Laptop

Dell Latitude

NA

5. TEST PROCEDURES:
Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

3 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

project no.:

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

41131107/00

FINAL SETTING TEST REPORT


The following procedures are written for demonstrating the main protection functions of
the P740 relay using an Omicron test set or similar. This document is to be referred to
when performing commissioning tests in association with the commissioning section of
the service manual.
5.1.
ID>1 threshold (circuitry fault current):
The ID>1 threshold is a CUs parameter, this setting is:
ID>1

= 0.10 A ( Primary I = 200 A )

tID>1

= 2.00 Seconds.

K ID>1 = 10.00 %
For the search of the current threshold the ID>1 alarm timer is set at the minimum value (100 ms).With
the Freja 300, applied a current on I1 of each PU and increase the current by step of 0.01 A until appear
the circuitry fault alarm. (Output relay of CU circuitry fault)
Repeat this sequence for the phase I2 and I3.
The ID>1 alarm timer is checked for each PU after the measurement of the current threshold, the setting
of the ID>1 alarm timer is set at the original value. (2 Sec)
The time delay is measured for a differential current upper than ID>1, the start of the clock is when the
current is applied and the stop of the clock is when the circuitry fault alarm appeared.
5.2.

ID>2 threshold (tripping current):

The ID>2 threshold is a CUs parameter, this setting is:


ID>2 = 1.00 A (Primary I = 2000 A )

IDCZ>2 = 1.00 A (Primary I = 2000 A )

K2

KCZ

= 65.00 %

= 30.00 %

The tripping time is less of one cycle ( <20 ms with Fn = 60 Hz)

Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

4 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

project no.:

41131107/00

FINAL SETTING TEST REPORT


With the FREJA 300, applied a current on I1 of each PU and increase the current by step of 0.01 A
until the trip of the PU (output relay No. 1, 2 or 3). The FREJA 300 is programmed to stop when the
tripping relay switch on. Repeat this sequence for the phase I2 and I3.
5.3. Slope Test :

Methodology of 2 current on bus:


With Freja kit put: I1 => on phase I1 of one PU, I2 => on phase I1 of another PU
1. Fixed a bias current > Ibias0
2. Increase the differential current until the busbar trip, by 2 opposite ramps of current on I1 and I2 with
the same speed so that the bias current is always constant.

Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

5 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

project no.:

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

41131107/00

FINAL SETTING TEST REPORT


Then

I Bias = I1 + I2,

I Diff = I2 - I1

Tripping characteristic is I Diff> K2 * I Bias


So ,

I2 I1 >= K2 * I1 + I2

Tripping should come when


I2 >= {(1 + K2)/(1 K2)} * I1

5.4 Breaker Failure Protection Test:


Breaker failure protection can be initiated either by internal initiation through diff, o/c or
E/F protection element or by external initiation through binary input
Energize the b/I for BF external initiation and inject the current more than I< setting
value. When relay trip freja will stop and it gives the trip time for stage1
For stage2 trip time, give the output contact for stage2 trip of the relay to input of freja to
stop the kit.

6. BB PROTECTION DETAILS
6.1.

Central Unit: Quantity-1

Model Number

Serial Number

Address

Soft Issue

P74135NA6M0510K

32477226/03/13

E2.4_A

6.2.

Peripheral Unit: Quantity-13

Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

6 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

project no.:

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

41131107/00

FINAL SETTING TEST REPORT


Model Number

Serial Number

PU
Addres
s

P74331NA6M0510K

32473875/03/13

E2.4_A

132KV B/S W605-1A

P74331NA6M0510K

32477231/03/13

E2.4_A

132KV B/S W605-1B

P74331NA6M0510K

32473868/03/13

E2.4_A

132KV B/C W606-1B

P74331NA6M0510K

32473867/03/13

10

E2.4_A

132KV B/C W606-2B

P74331NA6M0510K

32473871/03/13

11

E2.4_A

132KV OHL FDR-1 W603

P74331NA6M0510K

32473873/03/13

12

E2.4_A

132/33KV TR-T601 W604

P74331NA6M0510K

32477232/03/13

13

E2.4_A

132/33KV TR-T602 W607

P74331NA6M0510K

32477230/03/13

14

E2.4_A

132KV OHL FDR-2 W608

P74331NA6M0510K

32473876/03/13

15

E2.4_A

SPARE W609

P74331NA6M0510K

32473870/03/13

16

E2.4_A

FUTURE W610

P74331NA6M0510K

32473869/03/13

17

E2.4_A

FUTURE W611

P74331NA6M0510K

32473874/03/13

18

E2.4_A

FUTURE W601

P74331NA6M0510K

32473872/03/13

19

E2.4_A

FUTURE W602

Soft
Issue

Feeder/Bay Unit

7. CENTRAL UNIT LED / BINARY INPUT / BINARY OUTPUT CONFIGURATION:


7.1.
Central Unit Fixed LED Test :
Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

7 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

project no.:

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

FINAL SETTING TEST REPORT


LED Label

Color

Result

Trip

Red

ok

Alarm

Yellow

ok

Out of Service

Yellow

ok

Healthy

Green

ok

7.2

Central Unit Configured LED Test :

LED No.

Description

Result

LED1

87BB FAULT PHASE R

ok

LED2

87BB FAULT PHASE Y

ok

LED3

87BB FAULT PHASE B

ok

LED4

LED5

LED6

LED7
LED8
Function Key LED1

ZONE 1A
Red
:87BB- BB DIFF Trip
Green :50BF- CBF Back Trip
Yellow:87BB&50BF Trip
ZONE 1B
Red
:87BB- BB DIFF Trip
Green :50BF- CBF Back Trip
Yellow:87BB&50BF Trip
ZONE 2A
Red
:87BB- BB DIFF Trip
Green :50BF- CBF Back Trip
Yellow:87BB&50BF Trip
ZONE 2B
Red
:87BB- BB DIFF Trip
Green :50BF- CBF Back Trip
Yellow:87BB&50BF Trip
Communication Failure
ZONE OR CHECK ZONE

ok

ok

ok

ok
ok
ok

Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

41131107/00

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

8 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

project no.:

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

FINAL SETTING TEST REPORT


Red
:Block
Yellow :Alarm
Green :No Alarm
Red
:PU Error
Yellow :Alarm
Green :No Alarm
BB Protn. Out Of Service
ZONE 1A
Red
:Out Of Service
Green :Service
ZONE 2A
Red
:Out Of Service
Green :Service
ZONE 1B
Red
:Out Of Service
Green :Service
ZONE 2B
Red
:Out Of Service
Green :Service
Red
:Zone 1A Blocked
Yellow :Zone 1B Blocked
Red
:Zone 2A Blocked
Yellow :Zone 2B Blocked
Reset Indication
CU+PU

Function Key LED2


Function Key LED3
Function Key LED4

Function Key LED5

Function Key LED6

Function Key LED7


Function Key LED8
Function Key LED9
Function Key LED10

ok
ok
ok

ok

ok

ok
ok
ok
ok

7.3 Central Unit Opto Inputs Test :


Input
No.

Terminal No.
(+)

(-)

L1

K2

L2
L3

Function Assigned

Result

K1

Zone-1A BB Protn. Out Of Service

ok

K4

K3

Zone-2A BB Protn. Out Of Service

ok

K6

K5

Zone-1B BB Protn. Out Of Service

ok

Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

41131107/00

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

9 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

project no.:

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

41131107/00

FINAL SETTING TEST REPORT


L4

K8

K7

Zone-2B BB Protn. Out Of Service

ok

L5

K10

K9

Spare

ok

L6

K12

K11

Spare

ok

L7

K14

K13

BB Protn. Out Of Service

ok

L8

K16

K15

BB Protn. in Service

ok

7.4 Central Unit Output Relay Test :


Output No.

Terminal No.

Type

Function Assigned

Result

RL1

J1 J2

NO

Zone-1A Trip To FR

ok

RL2

J3 J4

NO

Zone-2A Trip To FR

ok

RL3

J5 J6

NO

Zone-1B Trip To FR

ok

RL4

J7 J8

NO

Zone-2B Trip To FR

ok

RL5

J9 J10

NO

Check Zone Optd.

ok

RL6

J11 J12

NO

Spare

ok

J13 J15

NC

Spare

ok

J14 J15

NO

Spare

ok

J16 J18

NC

Spare

ok

J17 J18

NO

Spare

ok

L11 L12

NC

CU Faulty

ok

L13 L14

NO

Spare

ok

RL7
RL8
WD

Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

10 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

project no.:

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

41131107/00

FINAL SETTING TEST REPORT


8. BAY UNIT LED / BINARY INPUT / BINARY OUTPUT CONFIGURATION:
9.1 TRANSFORMER BAY UNITS : 87PU12(W604) & 87PU13(W607)
9.1.1 Bay Units Fixed LED Test :
Results of BUs

LED Label

Color

Trip

Red

ok

Alarm

Yellow

ok

Out of Service

Yellow

ok

Healthy

Green

ok

9.1.2

BU12 & 13

Bay Units Configured LED Test :

LED No.

Results of BUs
BU12 & 13

Description

LED4

ISO(QB1) : Red Closed


Green Open
Yellow Disc.
ISO(QB2) : Red Closed
Green Open
Yellow Disc.
CB(Q0) : Red Closed
Green Open
Yellow Disc.
87BB BB Diff. Trip

LED5

CBF Stage-1 Trip

ok

LED6

CBF Stage-2 Trip

ok

LED7

Spare

ok

LED8

Communication Failure

ok

Function Key LED1

Reset Indications

ok

LED1

LED2

LED3

ok

ok

ok
ok

Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

11 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

project no.:

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

41131107/00

FINAL SETTING TEST REPORT


Function Key LED3

Red
- CB Defective
Green - CB Healthy
Bay Out Of Service

Function Key LED4

CBF Protn. Disabled

ok

Function Key LED5

ok

Function Key LED6

BB Protn. Disabled
Spare

Function Key LED7

Spare

ok

Function Key LED8

Spare

ok

Function Key LED9

Spare

ok

Function Key LED10

Spare

ok

Function Key LED2

9.1.3

ok
ok

ok

Bay Units Opto Inputs Test :

Input
No.

Terminal No.
(+)

(-)

L1

B2

L2

Function Assigned

Results of BUs
BU12 & 13

B1

CB Q0 OPEN

ok

B4

B3

CB Q0 CLOSED

ok

L3

B6

B5

DISC QB1 OPEN

ok

L4

B8

B7

DISC QB1 CLOSED

ok

L5

B10

B9

DISC QB2 OPEN

ok

L6

B12

B11

DISC QB2 CLOSED

ok

L7

B14

B13

CB DEFECTIVE

ok

L8

B16

B15

EXT.CBF INITIATE

ok

L9

C2

C1

BBP BLOCKED

ok

L10

C4

C3

BAY OUT

ok

L11

C6

C5

BAY IN

ok

Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

12 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

project no.:

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

41131107/00

FINAL SETTING TEST REPORT


L12

C8

C7

50BF BLOCKED

ok

L13

C10

C9

SPARE

ok

L14

C12

C11

SPARE

ok

L15

C14

C13

SPARE

ok

L16

C16

C15

SPARE

ok

L17

D2

D1

SPARE

ok

L18

D4

D3

SPARE

ok

L19

D6

D5

SPARE

ok

L20

D8

D7

SPARE

ok

L21

D10

D9

SPARE

ok

L22

D12

D11

SPARE

ok

L23

D14

D13

SPARE

ok

L24

D16

D15

SPARE

ok

9.1.4

Bay Units Output Relay Test :

Output No.

Terminal No.

Type

Function Assigned

Results of
BU12 & 13

RL1

F1 F2

NO

BBP PROTN OPTD-FR

ok

RL2

F3 F4

NO

50BF STG-1 OPTD-SAS

ok

RL3

F5 F6

NO

50BF STG-2 OPTD-SAS

ok

RL4

F7 F8

NO

50BF STG-2 OPTD-86BF

ok

RL5

F9 F10

NO

Spare

ok

RL6

F11 F12

NO

Spare

ok

F13 F15

NC

Spare

ok

F14 F15
F16 F18

NO
NC

BBP PROTN OPTD-86B


Spare

ok
ok

RL7
RL8

Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

13 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

project no.:

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

41131107/00

FINAL SETTING TEST REPORT


F17 F18

NO

50BF STG-2 OPTD-94BF

ok

RL9

E1 F2

NO

Spare

ok

RL10

E3 F4

NO

Spare

ok

RL11

E5 F6

NO

Spare

ok

RL12

E7 F8

NO

Spare

ok

RL13

E9 F10

NO

Spare

ok

RL14

E11 F12

NO

Spare

ok

E13 F15

NC

Spare

ok

E14 F15

NO

Spare

ok

E16 F18

NC

Spare

ok

E17 F18

NO

Spare

ok

G11 G12

NC

PU Faulty

ok

G13 G14

NO

Spare

ok

RL15
RL16
WD

9.2 OHL BAY UNITS : 87PU11(W603) & 87PU14(W608)


9.2.1 Bay Units Fixed LED Test :
LED Label

Color

Results of BUs
BU11 & 14

Trip

Red

ok

Alarm

Yellow

ok

Out of Service

Yellow

ok

Healthy

Green

ok

9.2.2

Bay Units Configured LED Test :

LED No.

Description

Results of BUs

Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

14 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

project no.:

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

41131107/00

FINAL SETTING TEST REPORT


BU11 & 14
ISO(QB1) : Red Closed
Green Open
Yellow Disc.
ISO(QB2) : Red Closed
Green Open
Yellow Disc.
CB(Q0) : Red Closed
Green Open
Yellow Disc.

LED1

LED2

LED3

ok

ok

ok

LED4

87BB BB Diff. Trip

ok

LED5

CBF Stage-1 Trip

ok

LED6

CBF Stage-2 Trip

ok

LED7

Dead Zone Trip (End Fault)

ok

LED8

Communication Failure

ok

Function Key LED1

ok

Function Key LED3

Reset Indications
Red
- CB Defective
Green - CB Healthy
Bay Out Of Service

Function Key LED4

CBF Protn. Disabled

ok

Function Key LED5

BB Protn. Disabled

ok

Function Key LED6

Spare

ok

Function Key LED7

Spare

ok

Function Key LED8

Spare

ok

Function Key LED9

Spare

ok

Function Key LED10

Spare

ok

Function Key LED2

9.2.3
Input No.

ok
ok

Bay Units Opto Inputs Test :

Terminal No.

Function Assigned

Results of BUs

Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

15 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

project no.:

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

41131107/00

FINAL SETTING TEST REPORT


BU11 & 14

(+)

(-)

L1

B2

B1

CB Q0 OPEN

ok

L2

B4

B3

CB Q0 CLOSED

ok

L3

B6

B5

DISC QB1 OPEN

ok

L4

B8

B7

DISC QB1 CLOSED

ok

L5

B10

B9

DISC QB2 OPEN

ok

L6

B12

B11

DISC QB2 CLOSED

ok

L7

B14

B13

CB DEFECTIVE

ok

L8

B16

B15

EXT.CBF INITIATE

ok

L9

C2

C1

BBP BLOCKED

ok

L10

C4

C3

BAY OUT

ok

L11

C6

C5

BAY IN

ok

L12

C8

C7

50BF BLOCKED

ok

L13

C10

C9

SPARE

ok

L14

C12

C11

SPARE

ok

L15

C14

C13

SPARE

ok

L16

C16

C15

SPARE

ok

L17

D2

D1

SPARE

ok

L18

D4

D3

SPARE

ok

L19

D6

D5

SPARE

ok

L20

D8

D7

SPARE

ok

L21

D10

D9

SPARE

ok

L22

D12

D11

SPARE

ok

L23

D14

D13

SPARE

ok

L24

D16

D15

SPARE

ok

Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

16 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

project no.:

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

41131107/00

FINAL SETTING TEST REPORT


9.2.4

Bay Units Output Relay Test :

Output No.

Terminal No.

Type

Function Assigned

Results of
BU11 & 14

RL1

F1 F2

NO

BBP PROTN OPTD-FR

ok

RL2

F3 F4

NO

50BF STG-1 OPTD-SAS

ok

RL3

F5 F6

NO

50BF STG-2 OPTD-SAS

ok

RL4

F7 F8

NO

50BF STG-2 OPTD-86BF

ok

RL5

F9 F10

NO

REMOTE INTERTRIP

ok

RL6

F11 F12

NO

Spare

ok

F13 F15

NC

Spare

ok

F14 F15

NO

BBP PROTN OPTD-86B

ok

F16 F18

NC

Spare

ok

F17 F18

NO

50BF STG-2 OPTD-94BF

ok

RL9

E1 F2

NO

Spare

ok

RL10

E3 F4

NO

Spare

ok

RL11

E5 F6

NO

Spare

ok

RL12

E7 F8

NO

Spare

ok

RL13

E9 F10

NO

Spare

ok

RL14

E11 F12

NO

Spare

ok

E13 F15

NC

Spare

ok

E14 F15

NO

Spare

ok

E16 F18

NC

Spare

ok

E17 F18

NO

Spare

ok

G11 G12

NC

PU Faulty

ok

G13 G14

NO

Spare

ok

RL7
RL8

RL15
RL16
WD

Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

17 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

project no.:

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

41131107/00

FINAL SETTING TEST REPORT


9.3 BUS SECTION BAY UNIT : 87PU7-A (W605)
9.3.1 Bay Unit 87PU7-W605A Fixed LED Test :
LED Label

Color

Results

Trip

Red

ok

Alarm

Yellow

ok

Out of Service

Yellow

ok

Healthy

Green

ok

9.3.2

Bay Unit 87PU7-W605A Configured LED Test :

LED No.

Description

Results

LED1

ISO(QB19) : RED
CLOSED
GREEN OPEN
YELLOW DISC.

ok

LED2

SPARE

ok

LED4

CB(Q0) : RED
CLOSED
GREEN OPEN
YELLOW DISC.
87BB BB DIFF. TRIP

LED5

CBF STAGE-1 TRIP

ok

LED6

CBF STAGE-2 TRIP

ok

LED7

SPARE

ok

LED8

COMMUNICATION FAILURE

ok

Function Key LED1

RESET INDICATIONS
RED - CB DEFECTIVE
GREEN - CB HEALTHY

ok

LED3

Function Key LED2

Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

ok
ok

ok

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

18 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

project no.:

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

41131107/00

FINAL SETTING TEST REPORT


Function Key LED3

BAY OUT OF SERVICE

ok

Function Key LED4

CBF PROTN. DISABLED

ok

Function Key LED5

BB PROTN. DISABLED

ok

Function Key LED6

SPARE

ok

Function Key LED7

SPARE

ok

Function Key LED8

SPARE

ok

Function Key LED9

SPARE

ok

Function Key LED10

SPARE

ok

9.3.3
Input No.

Bay Unit 87PU7-W605A Opto Inputs Test :


Terminal No.

Function Assigned

Results

CB Q0 OPEN

ok

B3

CB Q0 CLOSED

ok

B6

B5

DISC QB19 OPEN

ok

L4

B8

B7

DISC QB19 CLOSED

ok

L5

B10

B9

SPARE

ok

L6

B12

B11

SPARE

ok

L7

B14

B13

CB DEFECTIVE

ok

L8

B16

B15

EXT.CBF INITIATE

ok

L9

C2

C1

BBP BLOCKED

ok

L10

C4

C3

BAY OUT

ok

L11

C6

C5

BAY IN

ok

L12

C8

C7

50BF BLOCKED

ok

L13

C10

C9

SPARE

ok

L14

C12

C11

SPARE

ok

L15

C14

C13

SPARE

ok

L1

(+)
B2

(-)
B1

L2

B4

L3

Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

19 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

project no.:

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

41131107/00

FINAL SETTING TEST REPORT


L16

C16

C15

SPARE

ok

L17

D2

D1

SPARE

ok

L18

D4

D3

SPARE

ok

L19

D6

D5

SPARE

ok

L20

D8

D7

SPARE

ok

L21

D10

D9

SPARE

ok

L22

D12

D11

SPARE

ok

L23

D14

D13

SPARE

ok

L24

D16

D15

SPARE

ok

9.3.4

Bay Unit 87PU7-W605A Output Relay Test :

Output No.

Terminal No.

Type

Function Assigned

Result

RL1

F1 F2

NO

BBP PROTN OPTD-FR

ok

RL2

F3 F4

NO

50BF STG-1 OPTD-SAS

ok

RL3

F5 F6

NO

50BF STG-2 OPTD-SAS

ok

RL4

F7 F8

NO

50BF STG-2 OPTD-86BF

ok

RL5

F9 F10

NO

SPARE

ok

RL6

F11 F12

NO

SPARE

ok

F13 F15

NC

SPARE

ok

F14 F15

NO

BBP PROTN OPTD-86B

ok

F16 F18

NC

SPARE

ok

F17 F18

NO

50BF STG-2 OPTD-94BF

ok

RL9

E1 F2

NO

SPARE

ok

RL10

E3 F4

NO

SPARE

ok

RL11

E5 F6

NO

SPARE

ok

RL7
RL8

Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

20 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

project no.:

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

41131107/00

FINAL SETTING TEST REPORT


RL12

E7 F8

NO

SPARE

ok

RL13

E9 F10

NO

SPARE

ok

RL14

E11 F12

NO

SPARE

ok

E13 F15

NC

SPARE

ok

E14 F15

NO

SPARE

ok

E16 F18

NC

SPARE

ok

E17 F18

NO

SPARE

ok

G11 G12

NC

PU FAULTY

ok

G13 G14

NO

SPARE

ok

RL15
RL16
WD

9.4 BUS SECTION BAY UNIT : 87PU8-B (W605)


9.4.1 Bay Unit 87PU8-W605B Fixed LED Test :
LED Label

Color

Results

Trip

Red

ok

Alarm

Yellow

ok

Out of Service

Yellow

ok

Healthy

Green

ok

9.4.2

Bay Unit 87PU8-W605B Configured LED Test :

LED No.

Description

Results

LED1

ISO(QB20) : Red Closed


Green Open
Yellow Disc.

ok

Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

21 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

project no.:

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

41131107/00

FINAL SETTING TEST REPORT

LED4

ISO(QB23) : Red Closed


Green Open
Yellow Disc.
CB(Q0) : Red Closed
Green Open
Yellow Disc.
87BB BB Diff. Trip

LED5

CBF Stage-1 Trip

ok

LED6

CBF Stage-2 Trip

ok

LED7

Spare

ok

LED8

Communication Failure

ok

Function Key LED1

ok

Function Key LED3

Reset Indications
Red
- CB Defective
Green - CB Healthy
Bay Out Of Service

Function Key LED4

CBF Protn. Disabled

ok

Function Key LED5

BB Protn. Disabled

ok

Function Key LED6

Spare

ok

Function Key LED7

Spare

ok

Function Key LED8

Spare

ok

Function Key LED9

Spare

ok

Function Key LED10

Spare

ok

LED2

LED3

Function Key LED2

9.4.3
Input No.

ok

ok
ok

ok
ok

Bay Unit 87PU8-W605B Opto Inputs Test :

Terminal No.

Function Assigned

Results

B1

CB Q0 OPEN

ok

B3

CB Q0 CLOSED

ok

(+)

(-)

L1

B2

L2

B4

Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

22 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

project no.:

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

41131107/00

FINAL SETTING TEST REPORT


L3

B6

B5

DISC QB20 OPEN

ok

L4

B8

B7

DISC QB20 CLOSED

ok

L5

B10

B9

DISC QB23 OPEN

ok

L6

B12

B11

DISC QB23 CLOSED

ok

L7

B14

B13

CB DEFECTIVE

ok

L8

B16

B15

EXT.CBF INITIATE

ok

L9

C2

C1

SPARE

ok

L10

C4

C3

SPARE

ok

L11

C6

C5

SPARE

ok

L12

C8

C7

SPARE

ok

L13

C10

C9

BBP BLOCKED

ok

L14

C12

C11

BAY OUT

ok

L15

C14

C13

BAY IN

ok

L16

C16

C15

50BF BLOCKED

ok

L17

D2

D1

SPARE

ok

L18

D4

D3

SPARE

ok

L19

D6

D5

SPARE

ok

L20

D8

D7

SPARE

ok

L21

D10

D9

SPARE

ok

L22

D12

D11

SPARE

ok

L23

D14

D13

SPARE

ok

L24

D16

D15

SPARE

ok

9.4.4

Bay Unit 87PU8-W605B Output Relay Test :

Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

23 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

project no.:

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

41131107/00

FINAL SETTING TEST REPORT


Output No.

Terminal No.

Type

Function Assigned

Result

RL1

F1 F2

NO

BBP PROTN OPTD-FR

ok

RL2

F3 F4

NO

50BF STG-1 OPTD-SAS

ok

RL3

F5 F6

NO

50BF STG-2 OPTD-SAS

ok

RL4

F7 F8

NO

50BF STG-2 OPTD-86BF

ok

RL5

F9 F10

NO

SPARE

ok

RL6

F11 F12

NO

SPARE

ok

F13 F15

NC

SPARE

ok

F14 F15

NO

BBP PROTN OPTD-86B

ok

F16 F18

NC

SPARE

ok

F17 F18

NO

50BF STG-2 OPTD-94BF

ok

RL9

E1 F2

NO

SPARE

ok

RL10

E3 F4

NO

SPARE

ok

RL11

E5 F6

NO

SPARE

ok

RL12

E7 F8

NO

SPARE

ok

RL13

E9 F10

NO

SPARE

ok

RL14

E11 F12

NO

SPARE

ok

E13 F15

NC

SPARE

ok

E14 F15

NO

SPARE

ok

E16 F18

NC

SPARE

ok

E17 F18

NO

SPARE

ok

G11 G12

NC

PU FAULTY

ok

G13 G14

NO

SPARE

ok

RL7
RL8

RL15
RL16
WD

9.5 BUS COUPLER BAY UNIT : 87PU9-A (W606)

Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

24 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

project no.:

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

41131107/00

FINAL SETTING TEST REPORT


9.5.1

Bay Unit 87PU9-W606A Fixed LED Test :

LED Label

Color

Results

Trip

Red

ok

Alarm

Yellow

ok

Out of Service

Yellow

ok

Healthy

Green

ok

9.5.2

Bay Unit 87PU9-W606A Configured LED Test :

LED No.

Description

Results

LED4

ISO(QB21) : RED
CLOSED
GREEN OPEN
YELLOW DISC.
SPARE
CB(Q0) : RED
CLOSED
GREEN OPEN
YELLOW DISC.
87BB BB DIFF. TRIP

LED5

CBF STAGE-1 TRIP

ok

LED6

CBF STAGE-2 TRIP

ok

LED7

SPARE

ok

LED8

COMMUNICATION FAILURE

ok

Function Key LED1

ok

Function Key LED3

RESET INDICATIONS
RED - CB DEFECTIVE
GREEN - CB HEALTHY
BAY OUT OF SERVICE

Function Key LED4

CBF PROTN. DISABLED

ok

LED1
LED2
LED3

Function Key LED2

Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

ok
ok
ok
ok

ok
ok

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

25 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

project no.:

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

41131107/00

FINAL SETTING TEST REPORT


Function Key LED5

BB PROTN. DISABLED

ok

Function Key LED6

SPARE

ok

Function Key LED7

SPARE

ok

Function Key LED8

SPARE

ok

Function Key LED9

SPARE

ok

Function Key LED10

SPARE

ok

9.5.3

Bay Unit 87PU9-W606A Opto Inputs Test :

Input No.

Terminal No.
(+)
(-)

Function Assigned

Results

L1

B2

B1

CB Q0 OPEN

ok

L2

B4

B3

CB Q0 CLOSED

ok

L3

B6

B5

DISC QB21 OPEN

ok

L4

B8

B7

DISC QB21 CLOSED

ok

L5

B10

B9

SPARE

ok

L6

B12

B11

SPARE

ok

L7

B14

B13

CB DEFECTIVE

ok

L8

B16

B15

EXT.CBF INITIATE

ok

L9

C2

C1

BBP BLOCKED

ok

L10

C4

C3

BAY OUT

ok

L11

C6

C5

BAY IN

ok

L12

C8

C7

50BF BLOCKED

ok

L13

C10

C9

SPARE

ok

L14

C12

C11

SPARE

ok

L15

C14

C13

SPARE

ok

L16

C16

C15

SPARE

ok

L17

D2

D1

SPARE

ok

Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

26 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

project no.:

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

41131107/00

FINAL SETTING TEST REPORT


L18

D4

D3

SPARE

ok

L19

D6

D5

SPARE

ok

L20

D8

D7

SPARE

ok

L21

D10

D9

SPARE

ok

L22

D12

D11

SPARE

ok

L23

D14

D13

SPARE

ok

L24

D16

D15

SPARE

ok

9.5.4

Bay Unit 87BU9-W606A Output Relay Test :

Output No.

Terminal No.

Type

Function Assigned

Result

RL1

F1 F2

NO

BBP PROTN OPTD-FR

ok

RL2

F3 F4

NO

50BF STG-1 OPTD-SAS

ok

RL3

F5 F6

NO

50BF STG-2 OPTD-SAS

ok

RL4

F7 F8

NO

50BF STG-2 OPTD-86BF

ok

RL5

F9 F10

NO

SPARE

ok

RL6

F11 F12

NO

SPARE

ok

F13 F15

NC

SPARE

ok

F14 F15

NO

BBP PROTN OPTD-86B

ok

F16 F18

NC

SPARE

ok

F17 F18

NO

50BF STG-2 OPTD-94BF

ok

RL9

E1 F2

NO

SPARE

ok

RL10

E3 F4

NO

SPARE

ok

RL11

E5 F6

NO

SPARE

ok

RL12

E7 F8

NO

SPARE

ok

RL13

E9 F10

NO

SPARE

ok

RL7
RL8

Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

27 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

project no.:

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

41131107/00

FINAL SETTING TEST REPORT


RL14
RL15
RL16
WD

E11 F12

NO

SPARE

ok

E13 F15

NC

SPARE

ok

E14 F15

NO

SPARE

ok

E16 F18

NC

SPARE

ok

E17 F18

NO

SPARE

ok

G11 G12

NC

PU FAULTY

ok

G13 G14

NO

SPARE

ok

9.6 BUS COUPLER BAY UNIT : 87PU10-B (W606)


9.6.1 Bay Unit 87PU10-W606B Fixed LED Test :
LED Label

Color

Results

Trip

Red

ok

Alarm

Yellow

ok

Out of Service

Yellow

ok

Healthy

Green

ok

9.6.2

Bay Unit 87PU10-W606B Configured LED Test :

LED No.
LED1

LED2
LED3

Description
ISO(QB22) : Red Closed
Green Open
Yellow Disc.
ISO(QB18) : Red Closed
Green Open
Yellow Disc.
ISO(QB24) : Red Closed
Green Open

Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

Results
ok

ok
ok

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

28 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

project no.:

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

41131107/00

FINAL SETTING TEST REPORT

ok

LED5

Yellow Disc.
CB(Q0) : Red Closed
Green Open
Yellow Disc.
87BB BB Diff. Trip

LED6

CBF Stage-1 Trip

ok

LED7

CBF Stage-2 Trip

ok

LED8

Communication Failure

ok

Function Key LED1

ok

Function Key LED3

Reset Indications
Red
- CB Defective
Green - CB Healthy
Bay Out Of Service

Function Key LED4

CBF Protn. Disabled

ok

Function Key LED5

BB Protn. Disabled

ok

Function Key LED6

Spare

ok

Function Key LED7

Spare

ok

Function Key LED8

Spare

ok

Function Key LED9

Spare

ok

Function Key LED10

Spare

ok

LED4

Function Key LED2

9.6.3
Input No.

ok

ok
ok

Bay Unit 87PU10-W606B Opto Inputs Test :

Terminal No.

Function Assigned

Results

B1

DISC QB22 OPEN

ok

B4

B3

DISC QB22 CLOSED

ok

L3

B6

B5

DISC QB24 OPEN

ok

L4

B8

B7

DISC QB24 CLOSED

ok

(+)

(-)

L1

B2

L2

Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

29 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

project no.:

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

41131107/00

FINAL SETTING TEST REPORT


L5

B10

B9

DISC QB18 OPEN

ok

L6

B12

B11

DISC QB18 CLOSED

ok

L7

B14

B13

CB Q06 OPEN

ok

L8

B16

B15

CB Q06 CLOSED

ok

L9

C2

C1

CB DEFECTIVE

ok

L10

C4

C3

EXT.CBF INITIATE

ok

L11

C6

C5

SPARE

ok

L12

C8

C7

SPARE

ok

L13

C10

C9

BBP BLOCKED

ok

L14

C12

C11

BAY OUT

ok

L15

C14

C13

BAY IN

ok

L16

C16

C15

50BF BLOCKED

ok

L17

D2

D1

SPARE

ok

L18

D4

D3

SPARE

ok

L19

D6

D5

SPARE

ok

L20

D8

D7

SPARE

ok

L21

D10

D9

SPARE

ok

L22

D12

D11

SPARE

ok

L23

D14

D13

SPARE

ok

L24

D16

D15

SPARE

ok

9.6.4

Bay Unit 87PU10-W606B Output Relay Test :

Output No.

Terminal No.

Type

Function Assigned

Result

RL1

F1 F2

NO

BBP PROTN OPTD-FR

ok

RL2

F3 F4

NO

50BF STG-1 OPTD-SAS

ok

Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

30 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

project no.:

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

41131107/00

FINAL SETTING TEST REPORT


RL3

F5 F6

NO

50BF STG-2 OPTD-SAS

ok

RL4

F7 F8

NO

50BF STG-2 OPTD-86BF

ok

RL5

F9 F10

NO

SPARE

ok

RL6

F11 F12

NO

SPARE

ok

F13 F15

NC

SPARE

ok

F14 F15

NO

BBP PROTN OPTD-86B

ok

F16 F18

NC

SPARE

ok

F17 F18

NO

50BF STG-2 OPTD-94BF

ok

RL9

E1 F2

NO

SPARE

ok

RL10

E3 F4

NO

SPARE

ok

RL11

E5 F6

NO

SPARE

ok

RL12

E7 F8

NO

SPARE

ok

RL13

E9 F10

NO

SPARE

ok

RL14

E11 F12

NO

SPARE

ok

E13 F15

NC

SPARE

ok

E14 F15

NO

SPARE

ok

E16 F18

NC

SPARE

ok

E17 F18

NO

SPARE

ok

G11 G12

NC

PU FAULTY

ok

G13 G14

NO

SPARE

ok

RL7
RL8

RL15
RL16
WD

9. MEASUREMENTS OF PUS :
CT RATIO = 2000 / 1 A
PUS

PHASE

MEASURED CURRENT ( A )
@

0.25A

0.50A

@ 1.00A

% ERROR
@ 0.25A

@ 0.50A

Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

@ 1.00A

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

31 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

project no.:

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

41131107/00

FINAL SETTING TEST REPORT


7
( 87BU5-A )

8
( 87BU5-B )

9
(87BU6-A)

10
(87BU6-B)

11
(87BU3)

12
(87BU4)
13

0.248

0.496

0.998

0.8

0.8

0.2

0.248

0.500

0.998

0.8

0.2

0.250

0.502

1.008

0.4

0.8

0.250

0.500

0.998

0.2

0.252

0.502

0.998

0.8

0.4

0.2

0.254

0.506

1.012

1.6

1.2

1.2

0.250

0.498

0.994

0.4

0.6

0.252

0.500

0.998

0.8

0.2

0.252

0.504

1.01

0.8

0.8

0.250

0.502

0.994

0.4

0.6

0.250

0.500

1.00

0.254

0.506

1.01

1.6

1.2

0.248

0.498

0.994

0.8

0.4

0.6

0.252

0.502

1.01

0.8

0.4

0.252

0.504

1.002

0.8

0.8

0.2

0.248

0.498

0.993

0.8

0.4

0.7

0.252

0.502

1.004

0.8

0.4

0.4

0.254

0.506

1.006

1.6

1.2

0.6

0.250

0.498

0.998

0.4

0.2

Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

32 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

project no.:

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

41131107/00

FINAL SETTING TEST REPORT


( 87BU7)

14
( 87BU8)

15
( 87BU9)

16
( 87BU10)

17
( 87BU11)

18
( 87BU2)
19
( 87BU1)

0.252

0.502

1.004

0.8

0.4

0.4

0.252

0.504

1.01

0.8

0.8

0.250

0.500

0.998

0.2

0.252

0.502

1.00

0.8

0.4

0.252

0.504

1.01

0.8

0.8

0.250

0.494

0.992

1.2

0.8

0.250

0.500

0.998

0.2

0.252

0.502

1.008

0.8

0.4

0.8

0.250

0.498

0.998

0.4

0.2

0.250

0.500

1.004

0.4

0.252

0.504

1.01

0.8

0.8

0.248

0.496

0.990

0.8

0.8

0.248

0.498

0.996

0.8

0.4

0.4

0.252

0.502

1.006

0.8

0.4

0.6

0.248

0.498

0.996

0.8

0.4

0.4

0.250

0.501

1.004

0.2

0.4

0.254

0.504

1.01

1.6

0.8

0.250

0.498

0.993

0.4

0.7

0.252

0.500

0.998

0.8

0.2

Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

33 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

project no.:

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

41131107/00

FINAL SETTING TEST REPORT


B

0.252

0.503

1.008

0.8

0.6

0.8

10. BUSBAR PROTECTION TEST:


CU SETTINGS:
Differential Phase Fault: Activated
KCZ

30

IDCZ>2

2400

K2

65

ID>2

2400

K1

10

ID>1

450

ID>1 TIMER

2.0

Seconds

10.1.

ID>1 Threshold Check (Circuitry Fault Current):


SET ID>1 : 0.225 A (Secondary), 450 A ( Primary ), TIME : 5.0 Seconds
MEASURED PICKUP CURRENT(IN AMPS)

PUs
7
( 87BU5-A )
8
(87BU5-B)
9
(87BU6-A)
10
(87BU6-B)

R-PH

Y-PH

B-PH

Pick up (A)

Time ( S )

Pick up (A)

Time ( S )

Pick up (A)

Time ( S )

0.226

5.04

0.227

5.04

0.225

5.04

0.224

5.03

0.224

5.04

0.224

5.04

0.226

5.03

0.225

5.04

0.224

5.04

0.225

5.04

0.225

5.04

0.225

5.04

Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

34 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

project no.:

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

41131107/00

FINAL SETTING TEST REPORT


11
(87BU3)
12
(87BU4)
13
( 87BU7)
14
( 87BU8)
15
( 87BU9)
16
( 87BU10)
17
( 87BU11)
18
( 87BU2)
19
( 87BU1)

0.227

5.04

0.226

5.04

0.224

5.04

0.225

5.04

0.226

5.04

0.225

5.04

0.226

5.04

0.226

5.03

0.224

5.04

0.225

5.04

0.227

5.04

0.224

5.04

0.226

5.03

0.225

5.04

0.224

5.04

0.226

5.04

0.226

5.04

0.224

5.04

0.226

5.04

0.226

5.04

0.225

5.04

0.224

5.04

0.226

5.04

0.224

5.04

0.227

5.04

0.226

5.04

0.226

5.04

11.2 Slope Test (Circuitry Fault Current):


BAY UNITS: 87BU1-87BU2
Set
Slope
K1

0.1

Set
ID>1
(A)

0.225

Calculated Slope

Description

Injected
87BU1(A)
Injected
87BU2(A)

Current

1.227

1.836

2.451

1.473

2.207

2.694

1.715

2.452

3.062

1.0

1.5

2.0

1.2

1.8

2.2

1.4

2.5

Restrain Current ( A )

4.471

6.701

8.923

5.352

8.049

9.776

6.245

8.949

11.13

Differential
(A)

0.459

0.676

0.900

0.536

0.805

0.985

0.641

0.900

1.113

9.73

10.08

9.91

9.97

10.42

10.15

9.58

9.77

9.66

Current

Current
K1

Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

35 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

project no.:

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

41131107/00

FINAL SETTING TEST REPORT


Slope Calculation:
K1
K1
K1

=
=
=

( Y2 - Y1 ) / ( X2 - X1 )
( 0.213 0.107 ) / ( 2.213 1.107 )
0.10

BAY UNITS: 87BU2-87BU1


Set
Slope
K1

0.1

Set
ID>1
( A)

0.225

Description

Injected
87BU2(A)
Injected
87BU1(A)

Current

1.223

1.832

2.444

1.465

2.198

2.682

1.707

2.442

3.049

1.0

1.5

2.0

1.2

1.8

2.2

1.4

2.5

Restrain Current ( A )

4.427

6.686

8.927

5.364

8.009

9.794

6.253

8.894

11.18

Differential
( A)

0.456

0.672

0.900

0.551

0.819

0.988

0.639

0.896

1.131

9.56

10.17

9.87

10.13

9.47

9.86

9.73

10.28

9.99

Calculated Slope

Current

Current
K1

BAY UNITS: 87BU3-87BU4


Set
Slope
K1

0.1

Set
ID>1
( A)

0.225

Calculated Slope

Description

Injected
87BU3(A)
Injected
87BU4(A)

Current

1.223

1.833

2.445

1.466

2.200

2.685

1.708

2.441

3.049

1.0

1.5

2.0

1.2

1.8

2.2

1.4

2.5

Restrain Current ( A )

4.46

6.679

8.909

5.367

8.053

9.816

6.253

8.942

11.18

Differential
( A)

0.463

0.676

0.896

0.551

0.816

0.985

0.628

0.900

1.12

9.6

9.87

9.73

9.87

9.59

9.76

10.12

9.83

9.99

Current

Current
K1

Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

36 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

project no.:

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

41131107/00

FINAL SETTING TEST REPORT


BAY UNITS: 87BU4-87BU3
Set
Slope
K1

0.1

Set
ID>1
( A)

0.225

Description

Injected
87BU4(A)
Injected
87BU3(A)

Current

1.226

1.835

2.448

1.468

2.204

2.690

1.714

2.449

3.061

1.0

1.5

2.0

1.2

1.8

2.2

1.4

2.5

Restrain Current ( A )

4.449

6.653

8.949

5.364

8.071

9.809

6.267

8.923

11.20

Differential
( A)

0.456

0.672

0.900

0.540

0.816

0.974

0.625

0.911

1.135

9.80

9.93

9.87

10.20

9.09

9.76

10.77

9.84

10.34

Calculated Slope

Current

Current
K1

BAY UNITS: 87BU7-87BU8


Set
Slope
K1

0.1

Set
ID>1
( A)

0.225

Calculated Slope

Description

Injected
87BU7(A)
Injected
87BU8(A)

Current

1.225

1.834

2.446

1.468

2.208

2.696

1.716

2.452

3.064

1.0

1.5

2.0

1.2

1.8

2.2

1.4

2.5

Restrain Current ( A )

4.478

6.693

8.960

5.382

8.049

9.831

6.223

8.989

11.23

Differential
( A)

0.463

0.672

0.896

0.551

0.808

0.985

0.628

0.900

1.120

9.44

9.88

9.66

9.64

9.93

9.76

9.83

9.82

9.83

Current

Current
K1

Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

37 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

project no.:

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

41131107/00

FINAL SETTING TEST REPORT


BAY UNITS: 87BU8-87BU7
Set
Slope
K1

0.1

Set
ID>1
( A)

0.225

Description

Injected
87BU8(A)
Injected
87BU7(A)

Current

1.225

1.835

2.448

1.471

2.208

2.698

1.717

2.455

3.065

1.0

1.5

2.0

1.2

1.8

2.2

1.4

2.5

Restrain Current ( A )

4.474

6.741

8.978

5.371

8.078

9.878

6.260

8.956

11.21

Differential
( A)

0.463

0.687

0.904

0.544

0.827

0.999

0.639

0.907

1.131

9.88

9.70

9.79

10.45

9.56

10.10

9.94

9.94

9.94

Calculated Slope

Current

Current
K1

BAY UNITS: 87BU9-87BU10


Set
Slope
K1

0.1

Set
ID>1
( A)

0.225

Calculated Slope

Description

Injected
87BU9(A)
Injected
87BU10(A)

Current

1.227

1.839

2.454

1.471

2.210

2.696

1.718

2.455

3.066

1.0

1.5

2.0

1.2

1.8

2.2

1.4

2.5

Restrain Current ( A )

4.438

6.715

8.953

5.345

8.075

9.831

6.267

8.975

11.21

Differential
( A)

0.445

0.680

0.896

0.544

0.819

0.985

0.647

0.915

1.124

10.32

9.65

9.99

10.07

9.45

9.83

9.90

9.35

9.65

Current

Current
K1

Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

38 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

project no.:

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

41131107/00

FINAL SETTING TEST REPORT


BAY UNITS: 87BU10-87BU11
Set
Slope
K1

0.1

Set
ID>1
( A)

0.225

Description

Injected
87BU10(A)
Injected
87BU11(A)

Current

1.221

1.826

2.438

1.461

2.192

2.678

1.703

2.435

3.042

1.0

1.5

2.0

1.2

1.8

2.2

1.4

2.5

Restrain Current ( A )

4.441

6.686

8.927

5.327

8.012

9.812

6.234

8.887

11.12

Differential
( A)

0.448

0.683

0.900

0.544

0.816

0.988

0.636

0.900

1.124

10.47

9.68

10.08

10.13

9.56

9.90

9.95

10.03

9.99

Calculated Slope

Current

Current
K1

BAY UNITS: 87BU11-87BU9


Set
Slope
K1

0.1

Set
ID>1
( A)

0.225

Calculated Slope

Description

Injected
87BU11(A)
Injected
87BU9(A)

Current

1.224

1.833

2.447

1.469

2.205

2.692

1.715

2.452

3.059

1.0

1.5

2.0

1.2

1.8

2.2

1.4

2.5

Restrain Current ( A )

4.441

6.682

8.923

5.308

8.049

9.765

6.242

8.890

11.14

Differential
( A)

0.452

0.683

0.904

0.540

0.812

0.981

0.643

0.896

1.128

10.31

9.86

10.08

9.92

9.85

9.89

9.55

10.31

9.90

Current

Current
K1

11.3 ID>2 Threshold Check :


SET ID>2: 1.2 A,
K2: 65 %
Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

39 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

project no.:

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

41131107/00

FINAL SETTING TEST REPORT


MEASURED PICKUP CURRENT(IN AMPS)
R-PH

PUs

Y-PH

B-PH

Pick up
(A)

Time
( mSec )

Pick up
(A)

Time
( mSec )

Pick up
(A)

Time
( mSec )

18
( 87BU1)

1.189

16.5

1.189

16.5

1.192

17.7

19
( 87BU2)

1.189

17.0

1.189

17.2

1.189

16.5

11
(87BU3)

1.190

16.8

1.189

17.1

1.188

17.1

12
(87BU4)

1.191

17.0

1.188

16.8

1.188

16.8

13
( 87BU7)

1.186

16.9

1.186

16.5

1.186

17.1

14
( 87BU8)

1.188

16.8

1.188

16.7

1.190

17.4

15
( 87BU9)

1.193

16.7

1.192

17.1

1.193

16.9

16
( 87BU10)

1.186

17.8

1.188

16.4

1.187

17.0

17
( 87BU11)

1.189

16.4

1.190

17.1

1.192

16.6

11.4 Slope Test : Discriminating Zones


BAY UNITS: 87BU1-87BU2
Set
Slope
K2

Set
ID>1
( A)
1.2

0.65

Description
Injected
87BU1(A)
Injected
87BU2(A)

A
Current
Current

1.862

2.805

3.755

1.859

2.804

3.752

1.856

2.804

3.745

0.4

0.6

0.8

0.4

0.6

0.8

0.4

0.6

0.8

Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

40 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

project no.:

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

41131107/00

FINAL SETTING TEST REPORT


Restrain Current ( A )

4.548

6.822

9.151

4.522

6.837

9.158

4.522

6.840

9.085

Differential
( A)

2.954

4.423

5.948

2.928

4.441

5.948

2.932

4.441

5.896

64.6

65.48

65.04

65.36

64.93

65.14

65.10

64.81

64.96

Calculated Slope

Current
K2

Slope Calculation:
K2
K2
K2

=
=
=

( Y2 - Y1 ) / ( X2 - X1 )
( 4.423 2.954 ) / ( 6.822 4.548 )
0.646

BAY UNITS: 87BU2-87BU1


Set
Slope
K2

0.65

Set
ID>1
( A)

1.2

Description
Injected
87BU2(A)
Injected
87BU1(A)

A
Current

1.860

2.803

3.755

1.853

2.802

3.750

1.856

2.780

3.740

0.4

0.6

0.8

0.4

0.6

0.8

0.4

0.6

0.8

Restrain Current ( A )

4.504

6.829

9.118

4.526

6.807

9.151

4.526

6.774

9.151

Differential
( A)

2.928

4.419

5.915

2.921

4.419

5.940

2.939

4.386

5.944

64.13

65.36

64.74

65.67

64.89

65.28

64.37

65.54

64.97

Calculated Slope

Current

Current
K2

BAY UNITS: 87BU3-87BU4


Set
Slope
K2

Set
ID>1
( A)

Description

Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

41 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

project no.:

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

41131107/00

FINAL SETTING TEST REPORT

0.65

1.2

Injected
87BU3(A)
Injected
87BU4(A)

Current

1.854

2.803

3.743

1.854

2.800

3.739

1.855

2.796

3.742

0.4

0.6

0.8

0.4

0.6

0.8

0.4

0.6

0.8

Restrain Current ( A )

4.526

6.826

9.114

4.504

6.837

9.133

4.522

6.855

9.155

Differential
( A)

2.943

4.430

5.922

2.924

4.425

5.929

2.936

4.438

5.937

64.65

65.21

64.93

64.34

65.51

64.92

64.38

65.17

64.77

Calculated Slope

Current

Current
K2

BAY UNITS: 87BU4-87BU3


Set
Slope
K2

0.65

Set
ID>1
( A)

1.2

Description
Injected
87BU4(A)
Injected
87BU3(A)

A
Current

1.850

2.797

3.744

1.859

2.806

3.749

1.859

2.812

3.754

0.4

0.6

0.8

0.4

0.6

0.8

0.4

0.6

0.8

Restrain Current ( A )

4.522

6.828

9.133

4.541

6.818

9.107

4.526

6.866

9.114

Differential
( A)

2.921

4.428

5.922

2.946

4.438

5.911

2.932

4.463

5.926

65.35

64.82

65.08

65.52

64.35

64.94

65.43

65.08

65.26

Calculated Slope

Current

Current
K2

BAY UNITS: 87BU7-87BU8


Set
Slope
K2

Set
ID>1
( A)

Description

Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

42 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

project no.:

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

41131107/00

FINAL SETTING TEST REPORT

0.65

1.2

Injected
87BU7(A)
Injected
87BU8(A)

Current

1.858

2.798

3.747

1.844

2.786

3.727

1.848

2.788

3.736

0.4

0.6

0.8

0.4

0.6

0.8

0.4

0.6

0.8

Restrain Current ( A )

4.541

6.822

9.173

4.50

6.811

9.136

4.533

6.778

9.151

Differential
( A)

2.943

4.430

5.962

2.913

4.423

5.929

2.946

4.412

5.959

65.19

65.16

65.18

65.34

64.77

65.06

65.30

65.19

65.24

Calculated Slope

Current

Current
K2

BAY UNITS: 87BU8-87BU7


Set
Slope
K2

0.65

Set
ID>1
( A)

1.2

Description
Injected
87BU8(A)
Injected
87BU7(A)

A
Current

1.858

2.808

3.749

1.849

2.807

3.757

1.860

2.809

3.752

0.4

0.6

0.8

0.4

0.6

0.8

0.4

0.6

0.8

Restrain Current ( A )

4.537

6.859

9.188

4.515

6.862

9.155

4.541

6.866

9.147

Differential
( A)

2.946

4.456

5.970

2.932

4.456

5.951

2.950

4.456

5.929

65.03

65.01

65.02

64.93

65.20

65.06

64.77

64.58

64.68

Calculated Slope

Current

Current
K2

BAY UNITS: 87BU9-87BU10


Set
Slope
K2

Set
ID>1
( A)

Description

Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

43 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

project no.:

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

41131107/00

FINAL SETTING TEST REPORT

0.65

1.2

Injected
87BU9(A)
Injected
87BU10(A)

Current

1.858

2.805

3.758

1.857

2.804

3.752

1.860

2.802

3.756

0.4

0.6

0.8

0.4

0.6

0.8

0.4

0.6

0.8

Restrain Current ( A )

4.530

6.826

9.136

4.526

6.804

9.103

4.537

6.837

9.122

Differential
( A)

2.928

4.430

5.940

2.943

4.423

5.915

2.946

4.438

5.926

65.42

65.37

65.39

64.97

64.90

64.93

64.87

65.12

64.99

Calculated Slope

Current

Current
K2

BAY UNITS: 87BU10-87BU11


Set
Slope
K2

0.65

Set
ID>1
( A)

1.2

Description
Injected
87BU10(A)
Injected
87BU11(A)

A
Current

1.848

2.791

3.729

1.852

2.782

3.732

1.843

2.785

3.723

0.4

0.6

0.8

0.4

0.6

0.8

0.4

0.6

0.8

Restrain Current ( A )

4.522

6.778

9.114

4.526

6.778

9.100

4.504

6.815

9.114

Differential
( A)

2.932

4.408

5.926

2.946

4.398

5.911

2.919

4.430

5.929

65.43

64.98

65.20

64.48

65.16

64.82

65.38

65.20

65.29

2.805

3.750

Calculated Slope

Current

Current
K2

BAY UNITS: 87BU11-87BU9


Set
Slope
K2

Set
ID>1
( A)
1.2

0.65

Description
Injected
87BU11(A)

A
Current

1.856

B
2.802

3.744

1.859

C
2.804

3.752

1.856

Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

44 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

project no.:

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

41131107/00

FINAL SETTING TEST REPORT


Injected
87BU9(A)

0.4

0.6

0.8

0.4

0.6

0.8

0.4

0.6

0.8

Restrain Current ( A )

4.504

6.822

9.133

4.486

6.789

9.103

4.486

6.833

9.081

Differential
( A)

2.936

4.427

5.926

2.913

4.419

5.920

2.921

4.434

5.893

64.32

64.86

64.59

65.39

64.87

65.13

64.47

64.90

64.68

Calculated Slope

11.5

Set
Slope
KCZ

0.30

Current

Current
K2

Slope Test :Check Zone


SET IDCZ>2: 1.2 A,
KCZ: 30 %
11.5.1. WITH BUS SECTION AND COUPLER OPEN
BAY UNITS: 87BU1-87BU2

Set
IDCZ>2
(A)

Description

1.2

Injected Current
In BUS 2A (A)
Injected Current
In BUS 1A (A)
Restrain Current
( A)
Differential
Current (A)

Calculated Slope

KCZ

2.599

3.158

3.714

2.597

3.158

3.716

2.601

3.158

3.718

1.4

1.7

1.4

1.7

1.4

1.7

7.994

9.713

11.42

8.005

9.765

11.49

8.023

9.739

11.53

2.395

2.921

3.424

2.403

2.942

3.450

2.417

2.932

3.461

30.60

29.47

30.04

30.63

29.45

30.04

30.01

29.54

29.77

BAY UNITS: 87BU2-87BU1


Set
Slope
KCZ

Set
IDCZ>2
(A)

Description

Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

45 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

project no.:

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

41131107/00

FINAL SETTING TEST REPORT

0.30

1.2

Injected Current
In BUS 1A (A)
Injected Current
In BUS 2A (A)
Restrain Current
( A)
Differential
Current (A)

Calculated Slope

KCZ

2.587

3.146

3.701

2.587

3.146

3.698

2.586

3.139

3.697

1.4

1.7

1.4

1.7

1.4

1.7

8.009

9.761

11.47

8.012

9.738

11.44

7.994

9.746

11.47

2.417

2.935

3.450

2.414

2.916

3.439

2.399

2.921

3.435

29.57

30.13

29.85

29.08

30.73

29.90

29.79

29.81

29.80

BAY UNITS: 87BU3-87BU4


Set
Slope
KCZ

0.30

Set
IDCZ>2
(A)

Description

1.2

Injected Current
87BU3 In
BUS 1A (A)
Injected Current
87BU4 In
BUS 2A (A)
Restrain Current
( A)
Differential
Current (A)

Calculated Slope

KCZ

2.594

3.147

3.702

2.587

3.149

3.703

2.592

3.144

3.702

1.4

1.7

1.4

1.7

1.4

1.7

8.027

9.687

11.48

7.998

9.724

11.44

8.049

9.761

11.48

2.406

2.906

3.446

2.388

2.913

3.424

2.417

2.921

3.442

30.12

30.12

30.12

30.42

29.78

30.10

29.44

30.31

29.87

BAY UNITS: 87BU4-87BU3


Set
Slope
KCZ

Set
IDCZ>2
(A)

Description

Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

46 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

project no.:

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

41131107/00

FINAL SETTING TEST REPORT

0.30

Injected Current
87BU4 In
BUS 2A (A)
Injected Current
87BU3 In
BUS 1A (A)
Restrain Current
( A)
Differential
Current (A)

1.2

Calculated Slope

KCZ

2.598

3.153

3.707

2.594

3.154

3.712

2.596

3.155

3.706

1.4

1.7

1.4

1.7

1.4

1.7

8.031

9.761

11.49

8.034

9.765

11.48

8.020

9.742

11.49

2.410

2.935

3.446

2.406

2.936

3.450

2.410

2.913

3.442

30.35

29.55

29.95

30.62

29.97

30.30

29.21

30.26

29.74

11.5.1. WITH BUS COUPLER OPEN


BAY UNITS: 87BU7-87BU8
Set
Slope
KCZ

0.30

Set
IDCZ>2
(A)

Description

1.2

Injected Current
87BU7 In
BUS 1B (A)
Injected Current
87BU8 In
BUS 2B (A)
Restrain Current
( A)
Differential
Current (A)

Calculated Slope

KCZ

2.594

3.148

3.704

2.587

3.142

3.696

2.584

3.135

3.699

1.4

1.7

1.4

1.7

1.4

1.7

8.027

9.768

11.52

8.042

9.776

11.52

8.031

9.746

11.48

2.414

2.924

3.461

2.417

2.935

3.450

2.403

2.906

3.439

29.29

30.65

29.97

29.87

29.53

29.70

29.33

30.74

30.04

BAY UNITS: 87BU8-87BU7

Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

47 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

project no.:

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

41131107/00

FINAL SETTING TEST REPORT


Set
Slope
KCZ

0.30

Set
IDCZ>2
(A)

Description

1.2

Injected Current
87BU8 In
BUS 2B (A)
Injected Current
87BU7 In
BUS 1B (A)
Restrain Current
( A)
Differential
Current (A)

Calculated Slope

KCZ

2.584

3.139

3.690

2.857

3.140

3.694

2.585

3.140

3.700

1.4

1.7

1.4

1.7

1.4

1.7

8.012

9.706

11.45

8.027

9.717

11.39

7.994

9.706

11.41

2.425

2.915

3.439

2.403

2.917

3.416

2.403

2.910

3.442

28.93

30.05

29.49

30.41

29.83

30.12

29.61

31.22

30.42

BAY UNITS: 87BU9-87BU10


Set
Slope
KCZ

0.30

Set
IDCZ>2
(A)

Description

1.2

Injected Current
87BU9 In
BUS 2B (A)
Injected Current
87BU10 In
BUS 1B (A)
Restrain Current
( A)
Differential
Current (A)

Calculated Slope

KCZ

2.599

3.158

3.715

2.594

3.149

3.702

2.588

3.145

3.700

1.4

1.7

1.4

1.7

1.4

1.7

8.053

9.765

11.50

8.012

9.757

11.49

8.005

9.720

11.49

2.414

2.917

3.451

2.406

2.924

3.428

2.381

2.906

3.446

29.38

30.78

30.08

29.68

29.08

29.38

30.61

30.51

30.56

BAY UNITS: 87BU10-87BU9

Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

48 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

project no.:

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

41131107/00

FINAL SETTING TEST REPORT


Set
Slope
KCZ

0.30

Set
IDCZ>2
(A)

Description

1.2

Injected Current
87BU10 In
BUS 1B (A)
Injected Current
87BU9 In
BUS 2B (A)
Restrain Current
( A)
Differential
Current (A)

Calculated Slope

KCZ

2.579

3.140

3.694

2.585

3.139

3.689

2.582

3.134

3.690

1.4

1.7

1.4

1.7

1.4

1.7

8.009

9.709

11.40

8.012

9.732

11.43

8.001

9.731

11.43

2.399

2.917

3.420

2.428

2.923

3.416

2.403

2.913

3.424

30.47

29.75

30.11

28.78

29.03

28.91

29.48

30.08

29.78

BAY UNITS: 87BU11-87BU10


Set
Slope
KCZ

0.30

Set
IDCZ>2
(A)

Description

1.2

Injected Current
87BU11 In
BUS 2B (A)
Injected Current
87BU10 In
BUS 1B (A)
Restrain Current
( A)
Differential
Current (A)

Calculated Slope

KCZ

2.605

3.163

3.725

2.605

3.164

3.727

2.608

3.169

3.731

1.4

1.7

1.4

1.7

1.4

1.7

8.045

9.761

11.52

8.023

9.724

11.44

8.042

9.790

11.48

2.410

2.939

3.457

2.403

2.929

3.435

2.425

2.936

3.450

30.83

29.45

30.13

30.92

29.49

30.20

29.23

30.41

29.81

11. BREAKER FAILURE PROTECTION TEST (Setting P743):


CB FAIL (For Feeders, BC's and BS)

Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

49 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

project no.:

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

41131107/00

FINAL SETTING TEST REPORT


Address 45.01: control by

: I<.

Address 45.02: I< current set

: 100 mA ( Secondary ), 200 A ( Primary )

Address 45.03: I> current set

: Disabled

CB FAIL (For Transformers )


Address 45.01: control by

: 52a.

Internal Trip:
Address 45.07: CB fail timer 1 (stg. - 1)

: 120 m sec

Address 45.08: CB fail timer 2 (Stag. - 2)

: 240 m sec

External Trip:
Address 45.0A: CB fail timer 3 (stg. - 1)
Address 45.0B: CB fail timer 4 (Stag. - 2)

: 120 m sec
: 240 m sec

Test procedure: Config. , B/I Ext. 3PH trip, Led CBF trip,
B/O- CBF rep. trip 3P (stg. - 1)
B/O- Int./Ext. (stg. - 2)

FOR OHL FEEDERS, BUS SECTION, BUS COUPLER AND FUTURE BAYS
Circuit Breaker Failure
Internal Initiation
8Bay
No.

87BU1

Phase

P/U
(A)

Circuit Breaker Failure


External Initiation

Stg. 1
(m sec)

Stg. 2
(m sec)

Stg. 1
(m sec)

Stg. 2
(m sec)

Setting 120
ms

Setting 240
ms

Setting 120
ms

Setting 240
ms

Relay
LEDs

Remarks

L1-N

99

136

255

129

249

ok

ok

L2-N

98

137

256

129

248

ok

ok

L3-N

100

135

255

129

249

ok

ok

Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

50 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

project no.:

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

41131107/00

FINAL SETTING TEST REPORT


87BU2

87BU3

87BU5A

8
7BU5-B

87BU6A

87BU6B

87BU8

87BU9

L1-N

98

138

255

130

249

ok

ok

L2-N

99

137

254

129

249

ok

ok

L3-N

99

136

254

129

248

ok

ok

L1-N

100

138

255

130

249

ok

ok

L2-N

98

137

255

130

249

ok

ok

L3-N

100

137

255

130

249

ok

ok

L1-N

98

136

255

130

248

ok

ok

L2-N

101

136

255

129

249

ok

ok

L3-N

99

136

256

129

249

ok

ok

L1-N

98

136

256

129

248

ok

ok

L2-N

98

137

255

127

248

ok

ok

L3-N

99

137

255

129

249

ok

ok

L1-N

100

135

255

129

248

ok

ok

L2-N

98

136

255

129

249

ok

ok

L3-N

99

135

255

130

248

ok

ok

L1-N

98

136

255

129

248

ok

ok

L2-N

97

137

255

128

246

ok

ok

L3-N

99

137

254

129

248

ok

ok

L1-N

99

135

254

129

249

ok

ok

L2-N

99

136

256

130

249

ok

ok

L3-N

98

137

256

130

248

ok

ok

L1-N

99

137

254

131

250

ok

ok

Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

51 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

project no.:

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

41131107/00

FINAL SETTING TEST REPORT

87BU10

87BU11

L2-N

98

136

254

130

250

ok

ok

L3-N

99

136

255

131

251

ok

ok

L1-N

100

136

255

131

251

ok

ok

L2-N

98

135

256

131

250

ok

ok

L3-N

99

138

255

130

251

ok

ok

L1-N

100

136

256

131

250

ok

ok

L2-N

99

135

255

131

250

ok

ok

L3-N

99

137

257

131

251

ok

ok

FOR TRANSFORMERS
Circuit Breaker Failure
Measured Time With Internal Trip
Initiation

Circuit Breaker Failure


Measured Time With External Trip
Initiation

Stg 1 ( m secc )

Stg 2 ( m secc )

Stg 1 ( m secc )

Stg 2 (m sec )

Setting 120 m
sec.

Setting 240 m
sec.

Setting 120 m
sec.

Setting 240 m
sec.

87BU4

136

254

131

87BU7

137

256

132

Bay No.

Relay
LEDs

Remarks

250

ok

ok

250

ok

ok

12. DEAD ZONE PROTECTION :


SET I>DZ
= 0.150 A Secondary
= 300A Primary
I>DZ Time Delay
= 5.0 Sec.
Bay No.

Phase

Pick Up
Current ( A )

Timing ( Sec )

Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

52 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

project no.:

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

FINAL SETTING TEST REPORT


87BU1

87BU2

87BU3

87BU4

87BU5-A

87BU5-B

87BU6-A

0.148

5.028

0.149

5.028

0.148

5.028

0.147

5.029

0.148

5.028

0.148

5.029

0.148

5.028

0.149

5.027

0.148

5.029

0.148

5.029

0.149

5.029

0.148

5.028

0.148

5.027

0.147

5.027

0.149

5.026

0.147

5.026

0.148

5.026

0.148

5.027

0.148

5.027

0.146

5.026

Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

41131107/00

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

53 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

project no.:

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

FINAL SETTING TEST REPORT

87BU6-B

87BU7

87BU8

87BU9

87BU10

87BU11

0.148

5.027

0.148

5.026

0.148

5.026

0.147

5.027

0.149

5.028

0.148

5.028

0.148

5.028

0.148

5.028

0.147

5.029

0.148

5.027

0.148

5.028

0.148

5.028

0.148

5.029

0.147

5.028

0.147

5.027

0.148

5.028

0.148

5.027

0.148

5.028

0.149

5.028

13. BREAKER FAILURE TRIP : ( To Trip All Breakers in Same Bus Bar )
Input : External Trip + SF6 STG-2/ TC1 & TC2 Faulty
Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

41131107/00

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

54 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

project no.:

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

41131107/00

FINAL SETTING TEST REPORT


Trip Time = 120 mS
Bay No.

Measured Trip Time ( mSec )

87BU1

131

87BU2

130

87BU3

131

87BU4

131

87BU5-A

130

87BU5-B

130

87BU6-A

131

87BU6-B

131

87BU7

131

87BU8

130

87BU9

131

87BU10

131

87BU11

131

14. DIRECT TRANSFER TRIP TO REMOTE END :


FOR OHL FEEDERS:Bay No.

Protection

87BU3

CBF STAGE 2

Input

Measured Trip Time


( Sec )

External Trip

0.249

External Trip + SF6 STG-2/


TC1 & TC2 Faulty

0.132

Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

55 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

project no.:

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

FINAL SETTING TEST REPORT


DEAD
PROTECTION

ZONE

CBF STAGE 2
87BU8
DEAD
PROTECTION

ZONE

Breaker Open

5.030

External Trip

0.248

External Trip + SF6 STG-2/


TC1 & TC2 Faulty

0.132

Breaker Open

5.029

External Trip

0.249

External Trip + SF6 STG-2/


TC1 & TC2 Faulty

0.130

Breaker Open

5.027

External Trip

0.248

External Trip + SF6 STG-2/


TC1 & TC2 Faulty

0.132

Breaker Open

5.030

FOR SPARE and FETURE FEEDERS:-

CBF STAGE 2
87BU1
DEAD
PROTECTION

ZONE

CBF STAGE 2
87BU2
DEAD
PROTECTION

ZONE

Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

41131107/00

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

56 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

project no.:

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

FINAL SETTING TEST REPORT


CBF STAGE 2
87BU9
DEAD
PROTECTION

87BU10

ZONE

CBF STAGE 2

DEAD
PROTECTION

ZONE

CBF STAGE 2
87BU11
DEAD
PROTECTION

ZONE

External Trip

0.248

External Trip + SF6 STG-2/


TC1 & TC2 Faulty

0.131

Breaker Open

5.029

External Trip

0.248

External Trip + SF6 STG-2/


TC1 & TC2 Faulty

0.132

Breaker Open

5.028

External Trip

0.249

External Trip + SF6 STG-2/


TC1 & TC2 Faulty

0.132

Breaker Open

5.027

REMARKS:
Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :

41131107/00

SITE INSPECTION AND TEST RECORD

Date:

End Client:

Sheet:

17/11/2014

National Grid-SA -SOA

57 of 57

Description:

BUSBAR DIFFERENTIAL PROTECTION RELAY ( MICOM P741 & P743 )


Site:

Panel and Device ID:

132/33kV SABYA NORTH S/S

+EF811, +EF812, +EF813 & +EF814 87CU & 87PU

project no.:

41131107/00

FINAL SETTING TEST REPORT


--------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------END OF REPORT

Tested by:

Witnessed by: CSD Engineer

Name: Engr. GANESAN SELVAM


Signature & Date :

Name: Engr. EL-SAYED FATHY SULTAN


Signature & Date :