Vous êtes sur la page 1sur 1

CALIFORNIA ISO

SUPPLIED BY AT&T:

MILLIKEN LANDFILL SOLAR ISO # 15GEN1285


Folsom MV90

ION TCP/IP
DNP3 TCP/IP

Folsom EMS

SUPPLIED BY EPC or OWNER:

Alhambra MV90

ION TCP/IP

ECN

SUPPLIED BY TRIMARK:

DNP3 TCP/IP

Cat5e:
RS232

Alhambra EMS

RS485
Met Station 1

Substation Control Room and Switchgear


(UPS/Facility Battery Backup Power
until Generator Power is available*)

(UPS/Facility Backup Power until Generator


Power is Available*)

T1
ECN Network:
10.121.208.0/24

Modbus Port 502 to RIG


MDAS Port 7700 to CAISO
REVEN UE DATA ACCESSIBLE VIA IO N
PROTOCOL THRO UGH PORT 7700

ECN Router
ECN IP:10.121.208.1

Wind Speed (AI)


Wind Direction (AI)
Barometric Pressure (AI)
Ai r Temperature (AI)
POA Irradiance (AI)
Back Panel Temp. (AI)

MODBUS to RIG

MET 1

Access Control
Appliance

DNP3 TCP
Port 20000
to CAISO

CAISO
Main Meter
IP: 10.121.208.3
ID:TBD

RIG
(T1-S Gateway)
RTAC

ECN IP: 10.121.208.2

Heartbeat (AI)
UCON (DI)
Port Alarms (DI)

POD MW/MVAR (AI)


XFMR HS MW/MVAR (AI)
XFMR HS Voltage (AI)

DNP3 TCP/IP
to RIG

SEL Fast
to RTAC

SEL-351-P
Break er Status (DI)

* Meters connected t o Battery Backup 125VDC Power Supply. RIG, ECN Network Switch and Router connected to B attery Backup until Generator Power is available.

REV

DATE

BY

11/24/15

MB

NOTE

PROJECT NAME

DESCRIPTION
OWNER

RIG and Meter Communications Block Diagram

2365 Iron Point Road, #100


Folsom, CA 95630
(916) 357-5970

PVN Management, LLC

ISO Revenue Meter Engineering


DPG and RIG Engineering

Milliken Landfill Solar

INTERNAL ISO #

LOCATION
2050 S. Milliken Ave. Ontario, CA 91761

15GEN1285

DATE

VERSION

PROJECT #

11/24/2015

131134