D931 Fixed Orifice Double Regulating Valve
(FODRV)
PN25 Bronze Balancing Valve

..

The D931 provides the accuracy of a fixed orifice performance, all within one valve, saving
you time trouble and money over a traditional commissioning set. The D931 represents the
best value balancing option.
Key features:
Fixed orifice performance - accurate at any handwheel setting.
Cost effective replacement for commissioning sets and variable orifice valves.
Positive flow control at all handwheel settings.
Handwheel and pressure tappings orientated for maximum convenience.
Insertion test points for quick connection.
PN25 pressure rating.
Compact design - less space, fewer joints.
Copper compression adapters as standard in 1/2" and 3/4" valves.
WRAS Approved
Bill of Materials
Sequence Description
Material
Sizes
1

Body

Bronze BSEN1982 CC491K

All

Bonnet

DZR Brass BSEN12165 CW602N

All

Stem

DZR Brass BSEN12164 CW602N

All

Disc

DZR Brass BSEN12165/BSEN12164 CW602N 1 - 2 only

Balancing Cone DZR Brass BSEN12164 CW602N

1 - 2 only

Disc Face

P.T.F.E.

1 - 2 only

'O' Ring Seal

EPDM Rubber (BS4518 0106-24)

All

Handwheel

Plastic

All

Orifice Insert

DZR Brass BSEN12164 CW602N

All

10

P84 Test Valve See Fig.No. P84

All

Dimensional Drawing

Dimensions and Weights


Size

Weight Flow A
B
C
(kg)
(KVs) (mm) (mm) (mm)

1/2"

0.65

2.2

87

105

46

3/4"

0.72

4.7

96

106

51

1"

0.91

8.6

100

127

56

1.1/4" 1.1

16.6

114

128

57

1.1/2" 1.44

24.5

125

143

61

2"

46.1

146

144

75

1.9

Pressure Rating: PN25


Installation Instructions:
The single unit commissioning valve D931 is designed for installation in circuits where
combined functions of regulation and flow measurement are required. Accuracy of flow
measurement is +/-5% across all handwheel settings.
UK End Connection: BS21 Parallel
US End Connection: ANSI B1.20.1
Operating Instructions:
The double regulating feature allows valve opening to be set with an Allen key. Operation of
the valve is by means of the Microset Handwheel.
Specification:
Y-Pattern globe valves having characterised throttling disk lending towards equal
percentage performance. Integral square edged enterance orifice plate and P84 insertion
test points fitted.

31/1/2003

.. ..: : 3 , .:210483631520, :2104817000. /: 2 /, .:23107546813, :2310751835

2702xxB 2/8
End Connections:
1" to 2" BS21 (ISO 7) Parallel
1/2" and 3/4" BS2779 Parallel
Sizes 1/2" and 3/4" supplied with compression adapters for optional connection to copper.
This valve is intended for group 2 liquids only, as defined by the Pressure Equipment
Directive 97/23/EC.
Temperature operating range: -10 to 120 degrees celsius.

..

For further assistance please call our technical helpline on +44 (0)1473 277400 or email us
at enquiries@cranefs.com.
Following a policy of continuous development, Crane Fluid Systems reserves the right to
alter specifications and dimensions shown in the e-catalogue without prior notice.
Additional Documents
Operation & Maintenance Instruction
PED Declaration
View All D931 Flow Charts
Some charts are in PDF format, and require Adobe Acrobat Reader to view them. If you
do not have Acrobat Reader, use the following link to get and install it.

| home | eCatalogue | web use statement | conditions of sale | eStore | links | crane |
Copyright 2000 Crane Co. All rights reserved.

31/1/2003
.. ..: : 3 , .:210483631520, :2104817000. /: 2 /, .:23107546813, :2310751835

2702xxB 3/8

Flow Measurement
..

Size 1/2 (15mm)


Fig. No. D931

6000

60

5000
4000

50
40

3000

30

2000

20

1000

10

500

(kPa)

SIGNAL (mm H 2 O)

Fixed orifice devices for standard applications


Kvs = 2.2

400

300

200

FLOWRATE
Q

K VS
36

Where
Q

100
70

p =
K VS =

1
0.7
0.05

0.1

0.2

0.3 0.4 0.5

Flowrate l/s
Signal kPa
Signal Coefficient

Flowrate l/s
HEAD / PRESSURE LOSS

Factor
1.38

E
AN

Fig. No.
D931 (Fully open)

CR

The loss resulting from the insertion of the


device in the pipeline may be calculated by multiplying
the signal by the appropriate factor

D931

31/1/2003
.. ..: : 3 , .:210483631520, :2104817000. /: 2 /, .:23107546813, :2310751835

2702xxB 4/8

Flow Measurement
..
Size 3/4 (20mm)
Fig. No.D931

6000

60

5000
4000

50
40

3000

30

2000

20

1000

10

Kvs = 4.7

(kPa)

SIGNAL (mm H 2 O)

Fixed orifice devices for standard applications

500

400

300

200

FLOWRATE
Q

K VS
36

Where
Q

100
70

p =
K VS =

1
0.7
0.05

0.1

0.2

0.3 0.4 0.5

Flowrate l/s
Signal kPa
Signal Coefficient

Flowrate l/s
HEAD / PRESSURE LOSS

Factor
2.24

E
AN

Fig. No.
D931 (Fully open)

CR

The loss resulting from the insertion of the


device in the pipeline may be calculated by multiplying
the signal by the appropriate factor

D931

31/1/2003
.. ..: : 3 , .:210483631520, :2104817000. /: 2 /, .:23107546813, :2310751835

2702xxB 5/8

Flow Measurement
Size 1 (25mm)
Fig. No. D931

..

6000

60

5000
4000

50
40

3000

30

2000

20

1000

10

500

(kPa)

SIGNAL (mm H 2 O)

Fixed orifice devices for standard applications


Kvs = 8.6

400

300

200

FLOWRATE
Q

K VS
36

Where
Q

100
70

p =
K VS =

1
0.7
0.05

0.1

0.2

0.3 0.4 0.5

Flowrate l/s

Flowrate l/s
Signal kPa
Signal Coefficient

HEAD / PRESSURE LOSS

Fig. No.
D931 (Fully open)

Factor
2.37

E
AN
CR

The loss resulting from the insertion of the


device in the pipeline may be calculated by
multiplying
the signal by the appropriate factor

D931

31/1/2003
.. ..: : 3 , .:210483631520, :2104817000. /: 2 /, .:23107546813, :2310751835

2702xxB 6/8

Flow Measurement

..

Size 11/4 (32mm)


Fig. No. D931
6000

60

5000

50

4000

40

3000

30

2000

20

1000

10

500

(kPa)

SIGNAL (mm H O)
2

Fixed orifice devices for standard applications

Kvs = 16.6

400

300

200

FLOWRATE
Q

K VS
36

Where
Q

100
70

p =
K VS =

1
0.7
0.05

0.1

0.2

0.3

0.4 0.5

Flowrate l/s
Signal kPa
Signal Coefficient

Flowrate l/s
HEAD / PRESSURE LOSS

Factor
2.37

Fig. No.
931 (Fully open)

AN
CR

The loss resulting from the insertion of the


device in the pipeline may be calculated by multiplying
the signal by the appropriate factor

D931

31/1/2003
.. ..: : 3 , .:210483631520, :2104817000. /: 2 /, .:23107546813, :2310751835

2702xxB 7/8

Flow Measurement
Size 11/2 (40mm)
Fig. No. D931

..

6000

60

5000
4000

50
40

3000

30

2000

20

1000

10

500

(kPa)

SIGNAL (mm H 2 O)

Fixed orifice devices for standard applications


Kvs = 24.5

400

300

200

FLOWRATE
Q

Where
Q

100

70

0.7
0.5

p =
K VS =

Flowrate l/s

10

K VS

36
Flowrate l/s
Signal kPa
Signal Coefficient

50

HEAD / PRESSURE LOSS

D931 (Fully open)

E
AN

Fig. No.

CR

The loss resulting from the insertion of the


device in the pipeline may be calculated by multiplying
the signal by the appropriate factor
Factor
1.83

D931

31/1/2003
.. ..: : 3 , .:210483631520, :2104817000. /: 2 /, .:23107546813, :2310751835

2702xxB 8/8

Flow Measurement
Size 2 (50mm)
Fig. No. D931

..

6000

60

5000
4000

50
40

3000

30

2000

20

1000

10

500

(kPa)

SIGNAL (mm H 2 O)

Fixed orifice devices for standard applications


Kvs = 46.1

400

300

200

FLOWRATE
Q

Where
Q

100
70

p =
K VS =

1
0.7
0.5

10

K VS

36
Flowrate l/s
Signal kPa
Signal Coefficient

50

Flowrate l/s
HEAD / PRESSURE LOSS

Factor
2.5

E
AN

Fig. No.
D931 (Fully open)

CR

The loss resulting from the insertion of the


device in the pipeline may be calculated by multiplying
the signal by the appropriate factor

D931

31/1/2003
.. ..: : 3 , .:210483631520, :2104817000. /: 2 /, .:23107546813, :2310751835

Vous aimerez peut-être aussi