Vous êtes sur la page 1sur 9

Mediciones de la sub No.

1 EDIFICIO ADMINISTRATIVO
90 600V

500KVA 3F 4H

TARIFA TIPO HM
MEDICIONES
Valores

fase 1

I=

194.5 163

V=

131.1 -13 1

KW=

24.3 19.9

KVA=

25.24 21.25

KVAR=

6.39 7.16

F. P.=

fase 2
175 170

fase 3
132 168

131.5 131.5

130.7 130.7

23.35 21.7

17 19.5

24 23

17.0 20.84

6.24 6.76

3. 10 8.0

97 94

96 96

98 - 92

NEUTRO = 54A

I maxI min
357.5290
x 100
x 100=18.88
I max
357.5

PT= 124.93 KW
ST= 130.97 KVA
QT= 37,87 KVAR
F. P. T 95.5%
CONOCER LA CAPACIDAD DE TRABAJO DEL TRASFORMADOR EN %

130,97 KVA
X 100=26.19
500 KVA
DEMANDA MAX 125 KW
ENERGIA CONSUMINDA
BASE ( 00.00-06.00)
INT. (06:00 18:00 Y 22:00 -00:00)

= 12%
=86%

PUNTA ( 18:00 22:00)

=2%
TOTAL

100%

ENERGIA CONSUMIDA
DEMANDA MAX X TIEMPO
125 KW X 12 HORAS X DIA = 1500 KWA/ DIA CONSUMO PROMDIO
C.P.D.= 1500 KWH/ DIA X 30.4 DIA
CONSUMO TOTAL
DEMAN. MAX =

45000 KWH/ MES 100%

125 KW X $194.53

BASE = 5400 KWH/M

=$3522,42

INTER= 38700 KWH/M

=$ 30340,80

PUNTA= 900 KWH / M

= $ 1601,01

ENERGIA CONSUMIDA
DEMAN. MAX.

= $ 24 316.25

= $35464,23
=$ 24 316.25

ENERGIA CONSUMIDA. =$35 464.23

TRIANGULO DE POTENCIA

S=130.97 KVA

Q=37.87 KVAR

P= 124.93 KW

SUB ESTACION No. 2

BIBLIOTECA

500 KVA

4H

3F

MEDICIONES
F1 CON BANCO
KW =
17.76
KVA = 17.10
KVAR = 6.21
F.P. =
92
F2 CON BANCO
KW =
KVA =
KVAR =
F.P. =

16.66
17.37
5.33
94%

F3 CON BANCO
KW
= 1297
KVA =14.44
KVAR = 5.97
F. P. = 90%

SIN BANCO
19.5
18.3
9.66
84
SIN BANCO
15.27
17.97
8.65
86%.26
SIN BANCO
13.7
15
6.62
89%

SUBESTACION 2 BIBLIOTECA CAP 500 KVA


KW t= 45.39
KVAt= 49.41
KVARt = 17.47
F. P. = 92 %

DEM. MAX = 46 X $ 194.50


BASE = 1988 X 0.6522
INT
= 1424 X 0.754
Pta
= 331 X 1.7739

= $ 8 948.38
= $ 1296.77
= $ 11 164.94
= $ 588.81
$ 21 990.90

CONSUMO E = DEM. MAX. X TIEMPO


Ec= ( 46 KW X 12 HRS) X 30 DIAS

16569

BONIFICACION = (1- 90% /92% ) = 0.54 %


( 21 998.9 +IVA 0.54 % ) = 21 889.10 + IVA

SIN BANCO DE CAPACITORES


KWt = 44.57
KVAt = 51.53
KVARt = 24.93
F. P. = 86.33%
DEM. MAX. = ( 45 KW X 12 ) ( 30 ) = 16 200 KW
BASE = 1944 KW X 0.652 = $1268.07
INT. = 13 932 KW X 0.784 = $ 10 922.63
Pta. = 324 KW X 1.7789 = $ 5576.36
Dmax. = 45 KW X 194.55 = $58 753. 88
TOTAL
$ 21 520.97

PENALIZACION = ( 3/5) ( 90/ 36.33


21 520.97 + 2.55 % = $ 22064.75

-1)X100= 2.55%
DIF.= $ 189.64

TRIANGULO DE POTENCIA CON BANCO DE


CAPACITORES
S=49.41 KVA

Q=17.47 KVAR

P= 45.39 KW

TRIANGULO DE POTENCIA SIN BANCO DE


CAPACITORES

S=51.53 KVA

Q= 24.93 KVAR

P= 44.57 KW

SUBESTACIN NO. 3 BIOQUIMICA 4H 3F


Valores
I=

fase 1

fase 2

fase 3

251

243

284

KW=

33.85

28.33

28.55

KVA=

33.07

F.P. =

100

99

N= 61 A

280 A

242 A

29.52

38.80
99
285 A

P = 100.75 KW
S = 101.34 KVA
Q= 9.14 KVAR
F.P. = 99.3%
101 X 12 HORAS = 1212 KW-H
ENERGIA CONSUMIDA = 1212 KW X 30 DIAS = 36 360 KWK/ MES
DEM. MAX = 101 KW X $ 194.53 = $ 19 647.53
BASE = 4363 KWH/ MES X $ 0.6523 = $ 2 846.11
INT. = 31 270 KWH/ MES X $ 0.7848 = $ 24 540 . 69
PUNTO. = 727 KWH/ MES X $ 1.7769 = $ 1295.61
TOTAL =
+ IVA

$48 329.94 + IVA - 1131.54 = $ 47 196.39

BONIFICACION
|1- 90/99.3 | X 100 = 2.34 %

TRIANGULO DE POTENCIA
S =101.34 KVA

Q =9.14 KVAR

P = 100.75 KW
SUBESTACION NO. 4

KW
KVA
KVAR
F.P.

7.62
7.63
0.17
100

300 KVA TIPO COSTA MARCA SELIMEC

12.36
13.33
5
93

11.87
11.92
0.95
100

14.40
14.97
0.39
96

13.41
13.41
3.05
98

8.85
8.94
1.89
98

CORRIEMTE DE NEUTRO = 41.39 A


P = 63.51 KW
S= 70.53 KVA
Q= 11.45 KVAR
F.P. = 97.5%
ENERGIA CONSUMIDA = 69 KW X 12 HRS = 828 X 30 DIAS = 24 540
KW-H / MES
DEM . MAX. = 67 KW X $ 194.53 = $ 13 432.57
BASE =
2981 X $ 0,6523 = $ 1944.50
INT,=
21 362 X $0.7845 = $ 16 758.48
PUNTO =
497 X $ 1.7789 = $ 884.11
TOTAL =
$ 33 016.07 + IVA - 1.92 %
BONIFICACION
| ( 1-

$ 32 382.16 + IVA

90/97.8)|X 100 = 1.92 %

TRIANGULO DE POTENCIA

S= 70.53 KVA

Q= 11.45 KVAR

P= 63.55KW

SUBESTACION N. 5 ARQUITECTURA
MEDIA 3/0 BAJA 500KCM
VALORES
KW
KVA
KVAR
F.P.

500 KVA

FASE 1

FASE 2

FASE 3

5.94
8.05
5.40
74

9.35
10.42
4.75
92

9.81
9.92
1.23
99

MARCA: PROLEC

CORRIENTE DE NEUTRO = 15.20 A


P= 25.1 KW

DEM. MAX =26 KW

S= 28.39 KVA

BASE= 1123 KWH/M

Q= 1138 KVAR

INT. = 8050 KWK/M

F. P. = 88.33%

PTA= 187 KWH/M


TOTAL = 9 360 KWH/M

DEM. MAX . = $ 194.53 = 5057,78


BASE
= $ 0,6523 = 732,53
INT.
= $ 0,7848 = 6317,64
PTA
= $1,7789 = 332,67
TOTAL=

$ 12 440,60

DEM. MAX A TIEMPO


PENALIZACION=

26KW X 12 HRS = 312 KWH X 30 DIAS = 9360KWH/M

3 90
1 X 100=1,15
5 88.33

TRIANGULO DE POTENCIA

S=28.39 KVA

Q=1138 KVAR

P=25.1 KW

SUBESTACION 6
ITP 1
KW
KVA
KVAR
F. P.

F1
.2
.21
.003
99

ITP 3
KW
KVA
KVAR
F.P.

F1
3.57
3.67
.64
98

ITP 4
KW
KVA
KVAR
F. P.

F1
2.19
2.30
0.7
95

SISTEMAS

F2
1.37
1.38
.001
100

F3
1.82
1.84
.2
99

F2
3.58
3.60
.053
100

3F

500 KVA

ITP 2
KW
KVA
KVAR
F.P.

F3
2.95
3.07
.8
96

F2
0.71
0.96
0.6
74

4H

BUSS
KW
KVA
KVAR
F.P.

F1
1.05
1.1
.2
99
F1
16
17
3.6
98

F2
.63
1.25
1.02
48
F2
17.37
17.40
100
100

F3
1.55
2.22
1.49
70
F3
25.15
23.35
99
99

F3
1.49
1.64
0.6
91

P = 77.43
S= 80.28
Q= 12.88
F. P. =90.8
ENERGIA CONSUMIDA = 78 X 12HRS= 937 X 30 DIAS = 23 08 KW-H/MES
DEM. MAX. = 78 KW-H/MES X $194.53 = $ 15 173.34
BASE = 3370 KW-H/MES X $ 0.6523 = $ 2198.25
INT = 24149 KW-H/MES X $ 0.7848 = $ 18 952
PUNTA = 561 KW-H /MES X $1.7739 = $ 997.96
TOTAL
$ 37 321.68 - 100.39 = 37 221.29 +
IVA
BONIICACION

|1/4( 1- 90/ 90.8) |= 0.26%


TRIANGULO DE POTENCIA
S=80.28 KVA

Q=12.88 KVAR

P= 77.43 KW

Vous aimerez peut-être aussi