Vous êtes sur la page 1sur 4

CALCULO DE CAPACIDAD DE CABLE CYMCAP

CABLE XLPE 1200mm2 220 Kv / 548 Amp.

ENEL
220KV - 1200 MM2
GENERAL INPUT DATA
SELF CONTAINED CABLES IN DUCT BANK
NUMBER OF CABLES
NUMBER OF DIFFERENT CABLE TYPES.......
REFERENCE CABLE FOR CALCULATING AMPACITY
OF UNEQUALLY LOADED CABLES

12

FUNDAMENTAL OPERATING FREQUENCY ..... (HERTZ)


CONDUCTOR RESISTANCES CALCULATED PER IEC-228
AMBIENT TEMPERATURE................... (DEG C)
NATIVE SOIL THERMAL RESISTIVITY....... (C.M/W),

1
1
60.0
25.0
1.50

BACKFILL/DUCT BANK DATA


BACKFILL/DUCTBANK WIDTH.............. (M)
,XB =
1.200
BACKFILL/DUCTBANK HEIGTH............. (M)
,YB =
1.500
X LOCATION OF CENTRE OF BACKFILL/DUCTBANK, (M) ,AXB =
0.000
DEPTH OF CENTRE OF BACKFILL/DUCT BANK, (M)
,ALB =
4.10
BACKFILL/DUCTBANK THERMAL RESISTIVITY, (C.M/W) ,RHOB =
1.00
FRACTION OF THE RETURN CURRENT IN THE
CONCENTRIC NEUTRAL OF A SINGLE PHASE CABLE
0.000

CABLE CCT PHASE CABLE CABLE LOCATION CONDUCTOR DAILY LOAD DUCT
NO NO
ID TYPE
XL
YL TEMPERATURE
FACTOR NUMBER CURVE
INDEX (M)
(M)
(DEG C)
INDEX
-- --- ----- ---------------- ------ ------

LOAD

1
2
3
4
5
6
7
8
9
10
11
12

1
1
1
2
2
2
3
3
3
4
4
4

A
B
C
A
B
C
A
B
C
A
B
C

1
1
1
1
1
1
1
1
1
1
1
1

-0.50
0.00
0.50
-0.50
0.00
0.50
-0.50
0.00
0.50
-0.50
0.00
0.50

3.65
3.65
3.65
3.95
3.95
3.95
4.25
4.25
4.25
4.55
4.55
4.55

90.00
90.00
90.00
90.00
90.00
90.00
90.00
90.00
90.00
90.00
90.00
90.00

1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00

1
2
3
4
5
6
7
8
9
10
11
12

CABLE DESCRIPTION
*****************
CABLE TYPE No. : 1
==============
SINGLE CORE SELF CONTAINED CABLE

COMPOSITION
===========
ELEMENT
-------

MATERIAL DESCRIPTION THICKNESS EXTERNAL DIAMETER


(m)
(m)
-------- ----------- --------- -----------------

CONDUCTOR
SCREEN

COPPER

6 SEGMENTS

CUSTOM

0.04280

0.00140

0.04560

INSULATION
XLPE-UNF TAND=0.0010 0.02620
RHI=3.5
EPS=2.5
JACKET

PVC

0.00625

0.09800

0.11850

SKID WIRE/CONCENTRIC NEUTRAL ASSEMBLY (COPPER)


64 WIRES,
L= 0.0100
0.00220
0.10600
SKIN EFFECT FACTOR AKS................. : 0.62000
PROXIMITY EFFECT FACTOR AKP............ : 0.37000
CABLES IN DUCTBANK(DIRECTLY BURIED DUCTS)
---------------------------------CABLES IN DUCTBANK(DIRECTLY BURIED DUCTS)
CABLES IN DUCTBANK(DIRECTLY BURIED DUCTS)
POLYETHYLENE DUCT IN CONCRETE.
DUCT INTERNAL DIAMETER................. : 0.19200
DUCT EXTERNAL DIAMETER................. : 0.20000
BONDING ARRANGEMENT
------------------*
*
*
*
*

SINGLE CONDUCTOR CABLES


SHEATH CROSS BONDED
FLAT CONFIGURATION
CROSS BONDED CABLE SYSTEM
EQUAL SECTION LENGTHS

1
SOLUTION CONVERGED AFTER

3 ITERATIONS

m
m

GEOMETRIC FACTOR:

2.43

ENEL
220KV - 1200 MM2
CABLE
CONDUCTOR
DC
AC/DC
PHASE
NO TEMPERATURE AMPACITY RESISTANCE YCS YCP RATIO YS
(DEG C)
(A)
(OHMS/M)
-- -------- ------------ --- ----- --- ----1
2
3
4
5
6
7
8
9
10
11
12

84.0
86.3
84.0
86.8
89.5
86.8
87.3
90.0
87.3
85.6
87.8
85.6

548.
548.
548.
548.
548.
548.
548.
548.
548.
548.
548.
548.

0.1890E-04
0.1903E-04
0.1890E-04
0.1907E-04
0.1922E-04
0.1907E-04
0.1910E-04
0.1925E-04
0.1910E-04
0.1899E-04
0.1913E-04
0.1899E-04

0.116
0.114
0.116
0.114
0.112
0.114
0.114
0.112
0.114
0.115
0.113
0.115

0.001
0.001
0.001
0.001
0.001
0.001
0.001
0.001
0.001
0.001
0.001
0.001

1.117
1.115
1.117
1.115
1.113
1.115
1.115
1.113
1.115
1.116
1.114
1.116

0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000

0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000

YA

ID

A
B
C
A
B
C
A
B
C
A
B
C

CABLE
CONDUCTOR AC RESISTANCE (OHMS/M) AT ATTAINED TEMPERATURE
NO
SKIN EFFECT ONLY
TOTAL AC RESISTANCE
--------------------------------------1
2
3
4
5
6
7
8
9
10
11
12

0.2108E-04
0.2121E-04
0.2108E-04
0.2124E-04
0.2138E-04
0.2124E-04
0.2126E-04
0.2141E-04
0.2126E-04
0.2117E-04
0.2129E-04
0.2117E-04

0.2111E-04
0.2123E-04
0.2111E-04
0.2126E-04
0.2140E-04
0.2126E-04
0.2129E-04
0.2143E-04
0.2129E-04
0.2119E-04
0.2131E-04
0.2119E-04

CABLE CURRENT DEPENDENT LOSSES(W/M) DIELECTRIC TOTAL LOSSES


NO
CONDUCTOR SHEATH/ ARMOUR/
LOSS
IN CABLE
SHIELD PIPE
(W/M)
(W/M)
---------- ------ -------1
6.43
0.00
0.00
1.10
7.53
2
6.43
0.00
0.00
1.10
7.53
3
6.43
0.00
0.00
1.10
7.53
4
6.43
0.00
0.00
1.10
7.53
5
6.43
0.00
0.00
1.10
7.53
6
6.43
0.00
0.00
1.10
7.53
7
6.43
0.00
0.00
1.10
7.53
8
6.43
0.00
0.00
1.10
7.53
9
6.43
0.00
0.00
1.10
7.53
10
6.43
0.00
0.00
1.10
7.53
11
6.43
0.00
0.00
1.10
7.53
12
6.43
0.00
0.00
1.10
7.53

CABLE RESISTANCES IN THE THERMAL CIRCUIT((C/W)/M)


T1 = INSULATION THERMAL RESISTANCE
T2 = JACKET THERMAL RESISTANCE
INCLUDING ARMOUR BEDDING THERMAL RESISTANCE
OR THERMAL RESISTANCE OF PIPE FILLING MEDIUM
IN PIPE TYPE CABLES
OR THERMAL RESISTANCE OF FILLERS AND ARMOUR BEDDING
IN TYPE SL CABLES

T3 = ARMOUR SERVING THERMAL RESISTANCE


OR PIPE COATING THERMAL RESISTANCE
IN PIPE TYPE CABLES
T4 = EXTERNAL THERMAL RESISTANCE
AT UNITY DAILY LOAD FACTOR
T4P= EXTERNAL THERMAL RESISTANCE
AT SPECIFIED DAILY LOAD FACTOR
FOR CABLES IN AIR, T4P = T4
FOR CABLES IN DUCTS, T4 AND T4P INCLUDE
THE THERMAL RESISTANCES OF THE DUCT WALL
AND THE DUCT FILLING MEDIUM
CABLE
NO
T1
T2
-----

1
2
3
4
5
6
7
8
9
10
11
12

0.482
0.482
0.482
0.482
0.482
0.482
0.482
0.482
0.482
0.482
0.482
0.482

0.106
0.106
0.106
0.106
0.106
0.106
0.106
0.106
0.106
0.106
0.106
0.106

T3
--

T4
---

0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000

T4P

7.280
7.583
7.280
7.655
8.008
7.655
7.724
8.077
7.724
7.487
7.791
7.487

7.280
7.583
7.280
7.655
8.008
7.655
7.724
8.077
7.724
7.487
7.791
7.487

CABLE CALCULATED TEMPERATURES (DEG C)


NO
CONDUCTOR SHEATH/ ARMOUR/
EXTERIOR/
SHIELD PIPE OR JACKET
DUCT
---------- ------ ------------ -------1
2
3
4
5
6
7
8
9
10
11
12

84.0
86.3
84.0
86.8
89.5
86.8
87.3
90.0
87.3
85.6
87.8
85.6

80.6
82.9
80.6
83.5
86.1
83.5
84.0
86.6
84.0
82.2
84.5
82.2

79.8
82.1
79.8
82.7
85.3
82.7
83.2
85.8
83.2
81.4
83.7
81.4

78.1
80.4
78.1
80.9
83.6
80.9
81.4
84.1
81.4
79.6
81.9
79.6