Académique Documents
Professionnel Documents
Culture Documents
SAB 202
Screw Compressor Unit
99.10
Instruction manual
for
SAB 202
Type of drive
Male drive
Female drive
Refrigerant
R717
R22
Other_________
Shop no
Designation
Transducers and manual regulation of Vi slide
Instrumentation
Oil filter
External
Oil cooling
Type B
OWSG/OWRG
OOSI
Oil temp.reg.
Ex-execution
0178-250-EN
safeguarded
Preface
S service schedules;
S procedure for dismantling and
reassembling of the compressor.
The instruction manual also draws attention
to typical sources of errors which may occur
during operations. It states their cause and
explains what should be done to rectify them.
It is imperative that the operators familiarize
themselves thoroughly with the contents of
In the space below you can enter the name and address of your local SABROE
REPRESENTATIVE :
Phone:
Telefax:
+45 86 27 12 66
+45 86 27 44 74
0171-702-EN
96.06
0171-500-EN
Table of Contents
Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11
15
16
17
20
24
25
25
26
30
34
39
42
43
44
44
45
47
49
50
52
56
57
59
60
61
Position transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
64
65
66
68
75
Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
77
System for regulating the capacity and the Vi-ratio of SAB 202 . . . . . . . . . . . . . . . . . . . . .
79
85
0178-250-EN
Oil separator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
87
90
93
95
97
Heating rods for heating the oil in reciprocating and screw compressors . . . . . . . . . . . . .
100
101
103
106
107
109
111
113
120
149
157
161
162
0661-855
0661-856
0661-853
0661-854
Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
order specific
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
order specific
Dimension drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
order specific
order specific
order specific
0178-250-EN
0178-253-EN
96.12
0178-250-EN
It is possible to regulate the compressor capacity steplessly from approx. 10% to 100%
by means of a regulating slide mounted
under the rotors. Once the slide has moved
away from the slide stop a gap is created so
that some of the sucked-in gas is returned to
the suction side. The bigger the gap, the
lower the compressor capacity.
The regulating slide is moved hydraulically by
a regulating piston and controlled by a
solenoid valve system.
The compressor also features a regulating
system by which the built-in Vi volume ratio
can be adjusted.
The result hereof is that the compressor
works optimally at varying operational
pressures in the plant.
To optimize the compressor volume ratio the
position of the Vi regulating slide must be
changed whenever the compressor works at
max. capacity. This is done by changing the
position of the slide stop.
At partial load the Vi volume ratio will only be
approaching the optimum.
Regulating the built-in Vi volume ratio can be
done in the following two ways, depending on
the compressor type (as to your type of compressor, see page 1).
Fig. 1
SABROE
AARHUS DENMARK
Type
Shop no
Max. speed
Swept volume
Working pressure
Test pressure
Refrigerant
Year
r.p.m.
m3/h
bar
bar
T0177093_2
0178-250-EN
Safety precautions
Screw compressors
WARNING
Read related safety precautions
before operating this machine. Failure
to follow safety instructions may result
in serious personal injury or death.
0170-124-EN
98.03
Important
The safety precautions for this Sabroe
Refrigeration machine have been set down to
assist the operator, programmer and
maintenance personnel in practicing good
shop safety procedures.
The operator and maintenance personnel
must read and understand these precautions
completely before operating, setting up,
running, or performing maintenance on the
machine.
0178-015-EN
Tool safety
Always make sure that the hand tools are in
proper working condition.
Remove hand tools such as wrenches,
measuring equipment, hammers, and other
miscellaneous parts from the machine
immediately after use.
Lifting and carrying safety
Contact Sabroe Refrigeration if you have any
questions or are not sure about the proper
procedures for lifting and carrying.
Before lifting or carrying a compressor/unit or
other parts, determine the weight and size by
referring to things such as tags, shipping
data, labels, marked information, or manuals.
Use power hoists or other mechanical lifting
and carrying equipment for heavy, bulky, or
hard to handle objects. Use hook-up
methods recommended by your safety
department and know the signals for safely
directing a crane operator.
Never place any parts of your body under a
suspended load or move a suspended load
over any other person. Before lifting, be
certain that you have a safe spot for
depositing the load. Never work on a
component while it is hanging from a crane
or other lifting mechanism.
If in doubt as to the size or type of lifting
equipment, method, and procedures for
lifting, please contact Sabroe Refrigeration
before proceeding to lift the compressor,
motor, unit or its components.
WARNING
Failure to follow the safety
instructions outlined on this page
may result in serious personal injury
or death.
0178-015-EN
WARNING
Failure to follow the safety
instructions outlined on this page
may result in serious personal injury
or death.
0178-015-EN
DANGER:
HIGH VOLTAGE
Before working on any electrical
circuits, turn the machine Main
Disconnect Device OFF and lock
it.
Dismantle the main fuses to the
compressor unit.
Unless expressly stated in
applicable Sabroe Refrigeration
documentation or by appropriate
Sabroe Refrigeration Field Service
Representative, do NOT work with
electrical power ON. If such express statement or advice exists,
working with electrical power ON
should be performed by a Sabroe
Refrigeration Field Service Representative. The customer and subsequent transferees must determine
that any other person performing
work with electrical power ON is
trained and technically qualified.
FAILURE TO FOLLOW THIS
INSTRUCTION MAY RESULT IN
DEATH OR SERIOUS PERSONAL
SHOCK INJURY.
10
0178-015-EN
Female
Male
WARNING
The compressor block alone may
be lifted in the lifting eye.
The same applies to the motor.
0178-015-EN
11
S In an explosion-prone environment, provided the compressor is fitted with approved explosion-proof equipment.
WARNING
The compressor must NOT be
used:
S For evacuating the refrigeration plant of air and moisture,
S For putting the refrigeration
plant under air pressure in
view of a pressure testing,
S As an air compressor.
It must not be possible to block the emergency stop without a stop instruction being released.
It should only be possible to set back the
emergency device by a deliberate act, and
this set back must not cause the compressor
to start operating. It should only make it possible to restart it.
Other demands to the emergency device:
S It must be possible to operate it by means
of an easily recognizable and visible
manual handle, to which there is free access.
Safety equipment
S It must be able to stop any dangerous situation, which may occur, as quickly as
possible without this leading to any further
danger.
Emergency device
Combustion motors
Failure to do so will involve a risk of the lubricating oil from the combustion motor mixing
with the refrigerant; at worst, this may give
rise to corrosion and damage the motor.
12
0178-015-EN
Safety symbols
Before putting a compressor/unit into operation they must be provided with warning
signs corresponding to the actual design of
compressor/unit and in accordance with the
rules and regulations in force.
The CAUTION sign
A CAUTION tag is fixed on the compressor
like the one illustrated below. This sign imposes upon the users to read the Safety Precautions section in the manual before handling, operating or servicing the compressor
and unit.
CAUTION
0178-015-EN
DANGER:
HIGH VOLTAGE
WARNING
Failure to follow this instruction
may result in death or serious
personal shock injury.
13
Pfyldt beskyttelsesgas
Charged with inert gas
Enthlt Schutzgas
Charg du gaz protecteur
Contiene gas protector
N2
0,2 bar
3 PSI
1534-169
T2516273_0
Safety at servicing
WARNING
Read related safety precautions before operating this machine. Failure to
follow safety instructions may result in
serious personal injury or death.
Before dismantling a compressor or unit
attention should be paid to the following
points:
S Read related Safety Precautions section
in this manual before opening the compressor and other parts of the refrigeration
plant.
S Make sure that the motor cannot start up
inadvertently. It is recommended to remove all main fuses.
S Switch off all electric components on the
compressor/unit before the dismantling.
S Make sure that there is neither
overpressure nor any refrigerant in the
part to be dismantled. Close all necessary
stop valves.
Internal protection
14
0178-015-EN
Inhalation
WARNING
No plant can ever be said to be
too safe.
Safety is a way of life.
General
Ammonia is not a cumulative poison. It has a
distinctive, pungent odour that even at very
low, harmless concentrations is detectable by
most persons. Since ammonia is self-alarming, it serves at its own warning agent, so
that no person will voluntarily remain in concentrations which are hazardous. Since ammonia is lighter than air, adequate ventilation
is the best means of preventing an accumulation.
Experience has shown that ammonia is extremely hard to ignite and under normal
conditions is a very stable compound. Under
extremely high, though limited concentrations, ammonia can form ignitable mixtures
with air and oxygen, and should be treated
with respect.
1. Move affected personnel into fresh air immediately, and loosen clothing restricting
breathing.
2. Call a doctor/ambulance with oxygen
equipment immediately
3. Keep the patient still and warmly wrapped
in blankets.
4. If mouth and throat are burnt (freeze or
acid burn), let the conscious patient drink
water, taking small mouthfuls.
5. If conscious and the mouth is not burnt,
give hot, sweet tea or coffee (never feed
an unconscious person).
6. Oxygen may be administered, but only
when authorized by a doctor.
7. If breathing fails, apply artificial respiration.
Eye injuries from liquid splashes or concentrated vapour
1. Force the eyelids open and rinse eyes immediately for at least 30 minutes with the
salt water solution just mentioned
2. Call a doctor immediately.
0178-015-EN
15
WARNING
No plant can ever be said to be
too safe.
Safety is a way of life.
General
HFC/HCFC form colourless and invisible
gasses which are heavier than air and smell
faintly of chloroform at high concentrations
only. They are non-toxic, non-inflammable,
non-explosive and non-corrosive under normal operating conditions. When heated to
above approx. 300C they break down into
toxic, acid gas components, which are
strongly irritating and aggessive to nose,
eyes and skin and generally corrosive.
Besides the obvious risk of unnoticeable,
heavy gases displacing the atmospheric
oxygen, inhalation of larger concentrations
may have an accumulating, anaesthetic
effect which may not be immediately
apparent. 24 hours medical observation is,
therefore, recommended.
16
0178-015-EN
WARNING
No plant can ever be said to be
too safe.
Safety is a way of life.
In high concentrations, R717 causes respiratory problems, and when ammonia vapour
and air mix 15 to 28 vol. %, the combination
is explosive and can be ignited by an electric
spark or open flame.
To this end, many countries have passed legislation in an effort to reduce pollution and
preserve the environment. These laws apply
to all fields of industry, including refrigeration,
and must be complied with.
The following table shows the values for refrigerant content in air, measured in volume %.
Certain countries may, however, have an official limit which differs from those stated.
Halogenated refrigerants
Ammonia
R134a
R404A
R507
R22
R717
0.1
0.1
0.1
0.1
0.005
Unit
TWA
Time weighted ave-
vol.%
0178-015-EN
vol.%
0.2
0.002
17
18
0178-015-EN
Lubricating oils
mineral oil
semi-synthetic oil
NOTE
This instruction provides only general information. The owner of the refrigeration plant is
responsible for ensuring that all codes, regulations and industry standards are complied
with.
0178-015-EN
19
Fig. 1
Fictional frame
Dimensional plane
1 meter
20
1 meter
99.06
Reflecting plane
0170-114-EN
0170-114--EN
0170-114-EN
21
RECIPROCATING COMPRESSORS
One-stage
Evaporating temperature
= 15C
Condensing temperature
=+35C
Refrigerant
= R22/R717
Number of revolutions
=1450 rpm.
Two-stage
Evaporating temperature
Condensing temperature
Refrigerant
Number of revolutions
Compressor block
Compressor block
LW
LP
CMO 24
84
69
CMO 26
86
71
CMO 28
87
72
SMC 104 S
95
79
SMC 106 S
96
80
SMC 108 S
97
81
SMC 112 S
99
82
SMC 116 S
100
83
SMC 104 L
96
80
SMC 106 L
97
81
SMC 108 L
98
82
SMC 112 L
100
83
SMC 116 L
101
84
SMC 104 E
96
80
SMC 106 E
97
81
SMC 108 E
98
82
SMC 112 E
100
83
SMC 116 E
101
84
Evaporating temperature
Condensing temperature
Refrigerant
Number of revolutions
Compressor block
= 15C
= +35C
= R22/R717
= 900 rpm.
LW
LP
= 35C
= +35C
= R22/R717
=1450 rpm.
LW
LP
TCMO 28
81
66
TSMC 108 S
95
79
TSMC 116 S
97
81
TSMC 108 L
96
80
TSMC 116 L
98
82
TSMC 108 E
96
80
TSMC 116 E
98
82
Evaporating temperature
Condensing temperature
Refrigerant
Number of revolutions
= 35C
= +35C
= R22/R717
= 900 rpm.
Compressor block
LW
LP
TSMC 188
100
82
Heat pump
Evaporating temperature
Condensing temperature
Refrigerant
Number of revolutions
Compressor block
= +20C
= +70C
= R22/R717
=1450 rpm.
LW
LP
HPO 24
91
76
HPO 26
93
78
HPO 28
94
79
HPC 104
97
81
SMC 186
101
83
HPC 106
98
82
SMC 188
102
84
HPC 108
99
84
22
0170-114-EN
SCREW COMPRESSORS
Evaporating temperature
Condensing temperature
Refrigerant
Number of revolutions
*Number of revolutions
Compressor block
= 15C
= +35C
= R22/R717
= 2950 rpm.
= 6000 rpm.
LW
LP
98
98
98
98
81
81
81
81
102
106
101
104
102
84
88
84
86
84
105
109
103
106
103
86
90
86
87
85
SAB 202 SM
SAB 202 SF
SAB 202 LM
SAB 202 LF
104
105
104
105
85
86
85
86
SAB 330 S
SAB 330 L
SAB 330 E
106
106
106
87
87
87
SV 17
SV 19
100
101
83
84
FV 19*
SV 24
101
103
86
85
FV 24*
SV 26
104
103
86
85
FV 26*
107
85
SAB 81
SAB 83
SAB 85
SAB 87
SAB 89
101
102
103
105
108
86
85
86
86
85
SAB 110 SM
SAB 110 SF
SAB 110 LM
SAB 110 LF
Evaporating temperature
= 35C
Condensing temperature
= 5C
Refrigerant
= R22/R717
Number of revolutions
= 2950 rpm.
Compressor unit
LW
LP
SAB 163 BM
106
88
SAB 163 BF
110
92
Evaporating temperature
= 15C
Condensing temperature
=+35C
Refrigerant
= R22/R717
Number of revolutions
= 2950 rpm.
Compressor block
LW
LP
VMY 347 H
97
82
VMY 447 H
100
85
VMY 536 H
104
88
Evaporating temperature
= 0C
Condensing temperature
=+35C
Refrigerant
= R22/R717
Number of revolutions
= 2950 rpm.
Compressor block
LW
LP
VMY 347 M
99
84
VMY 447 M
101
86
VMY 536 M
105
89
0170-114-EN
23
sor unit can - under normal circumstances be classified in Class III or IV according to
the following table from ISO 2372. Recip.
compressor units can be classified in class
IV, likewise under normal conditions.
Vibration severity ranges and examples of their application to small machines (Class I) medium size machines (Class II), large machines (Class III) and turbo machines (Class IV)
Examples of quality judgement
for separate classes of machines
0.28
0.45
0.71
1.12
1.8
2.8
4.5
7.1
11.2
18
28
45
Class I
0.28
0.45
0.71
1.12
1.8
2.8
4.5
7.1
11.2
18
Class II
Class III
Class IV
95.06
A
A
B
A
A
B
C
B
C
28
B
C
C
D
D
45
71
24
0178-250-EN
0170-115-EN
Range
Height
700
0178-254-EN
98.04
Length
Compressor
type
Refrigerant
Oil cooling
system 1)
SAB 202
R717
R22
R134a
R404A/R507
R407C
OWSG,
OOSI
Fig. 1
T290927_0
Width
Max. dimensions
Width
mm
Length
mm
Height
mm
Max. net
weight
Kg 2)
1905
3234
1915
4000
AARHUS
DENMARK
Type
Approval
no.
Serial no.
Max. operating
pressure
bar
Test pressure
bar
0178-250-EN
25
male
female 1.8-4.5
male
female 2.0-4.5
L = Rotor length
202
202
1.7
20
202
202
2.2
16
2950
1229
3550
1479
4425
1843
5325
2218
2950
1590
3550
1914
4425
2385
5325
2870
D = Rotor diameter
Block weight
Kg
Centre height
mm
950
315
950
315
1050
315
1050
315
Operating limits
26
0178-250-EN
SAB202S SAB202L
Operating
limits
60
MALE DRIVE
R717
Condensing temperature
50
40
FEMALE DRIVE
30
20
10
0
10
R717
20
30
60
50
40
30
20
10
10
20
Evaporating temperature
(T250842_0)
SAB202S SAB202L
Operating
limits
60
R22
MALE DRIVE
Condensing temperature
50
40
FEMALE DRIVE
30
20
10
0
10
R22
20
30
60
(T250841_0)
0178-250-EN
50
40
30 20 10
0
Evaporating temperature
10
20
27
Operating
limits
R134a
MALE DRIVE
70
Condensing temperature
60
SAB 202:
FEMALE DRIVE
50
HLI
40
HLI + ECO
SAB 202:
no HLI
operation
30
20
10
VMY 447:
Below curve
full flow oil
pump required
R134a
10
20
50
40
30
(T250821_1)
Operating
limits
0
10
20
20 10
Evaporating temperature
30
SAB202S/L VMY447H/M
R404A - R507
50
HLI
Condensing temperature
40
SAB 202:
FEMALE DRIVE
30
HLI + ECO
20
10
SAB 202:
no HLI
operation
0
10
VMY 447:
Below curve
full flow oil
pump required
20
R404A-R507
30
70
(T250830_2)
28
60
50
40
30
20
10
10
Evaporating temperature
0178-250-EN
Operating
limits
R407C
TC C
60
MALE DRIVE
50
HLI
Condensing temperature
40
FEMALE DRIVE
30
HLI +
econ
20
SAB 202:
No HLI
operation
10
0
10
VMY 447:
Below curve full flow
oil pump required
20
R407C
30
-70 60 50 40 30 20 10
10
20
TE C
Evaporating temperature
(T250133_1)
0178-250-EN
29
2. Initial start.
3. Current control requirements at normal
operation.
4. Normal stop.
5. Preparations before a lengthy standstill
period.
6. Pressure testing.
7. Evacuation.
8. Operating log.
30
e) Top up with new oil of a quality recommended in the oil instruction. Fill the oil
hose with oil, insert it into the vessel with
new oil and connect to valve pos. 62 (do
not use a hose with an inner diameter
smaller than valve pos. 62). Close valve
pos. 60, valve pos. 65 must also be
closed.
Start the pump by hand. In case the pump
refuses to suck, carefully open valve pos.
64 until gas pockets, if any, have been removed. Charge as much oil that the oil
level is visible in the upper sight glass.
The amount of oil appears from the table
on Oil Charging.
Important
Please, observe that the inner diameter
of the oil hose must be min. 28 mm and
the hose itself max. 3 metres long in order to avoid cavitation in the oil pump.
f) Open all internal valves.
g) Slowly open the suction and discharge
stop valves and fill up the plant with refrigerant according to the instruction manual
for this plant.
2. Initial start-up
a) Check that the compressor is easy to turn
by hand.
b) Check oil level in the oil separator.
0178-250-EN
97.02
0178-255-EN
During operation of the compressor, the below points should be observed. These are
described in detail in the following sections.
0178-250-EN
4. Normal stop
Regulate the compressor down to min. capacity.
Set the change-over switch on stop.
6. Pressure testing
Before charging the plant with refrigerant, it
must be pressure tested and emptied.
Pressure test the plant using:
S Dry air - Pressurized cylinders containing
dry atmospheric air may be used - never
use oxygen cylinders.
S Air compressor for high pressure.
S Nitrogen.
31
Important
Do not use the plant compressors for
pressurizing the plant. Water or any other
liquid must not be used in connection with
pressure testing.
In case nitrogen is used it is important to
place a reduction valve with pressure
gauge between the nitrogen cylinder and the
plant.
During pressure testing it is important that
pressure transducers and other control
equipment are not exposed to the test pressure. Similarly, the compressor stop valves
must be closed during testing.
Normally, the plant safety valves should be
blanked off during the pressure testing as
their opening pressure is lower than the test
pressure.
Important
During this pressure testing no persons
are allowed in the rooms with plant components or in the vicinity of the plant outside the rooms.
S The entire plant is strength tested according to the local rules for pressure testing.
S Usually, the test pressure must not be
allowed to exceed the design pressure.
However, also in this case the local rules
and regulation apply.
S In case there is a request for the compressor to be pressure tested together with the
unit, the test pressure on the compressor
must not exceed 24 bar.
S Hereafter, lower the pressure to 10 bar for
24 hours as a first leak testing as a
tight plant will maintain this pressure during the entire period.
32
7. Evacuation
After pressure testing the refrigeration plant
must be evacuated in order to remove atmospheric air and moisture. Evacuation must be
carried out on all types of refrigeration plants
regardless of the type of refrigerant to be
filled into the plant.
Note that HCFC, HFC and CFC refrigerants
hardly mix with water. Consequently, it is important to make a particularly thorough evacuation of these plants.
The boiling point of a liquid is defined as the
temperature by which the steam pressure is
equal to atmospheric pressure.
The boiling point of water is 100C. If the
pressure is lowered, so is the boiling point of
water.
The following table indicates the boiling point
of water at very low pressures:
Boiling point
of water C
At pressure
mm HG
6,63
10
9,14
15
12,73
20
17,80
0178-250-EN
S Next blow in dry air or nitrogen in the system to a pressure equal to atmospheric.
Important
Never use the refrigeration compressor for
emptying of the plant.
In order for an evacuation to be satisfactorily
carried out the final pressure must be below
5 mm Hg. Attention should be paid to the fact
that there is a risk that the water still present
in the refrigeration plant may freeze in case
the ambient temperatures are below 10C.
In that case it is necessary to heat up the
surroundings of the components as ice only
evaporates slowly.
8. Operating log
To be in control of the operating conditions of
the plant it is recommended to keep an operating log in order to be able to keep an eye
on any changes that may occur in the operating conditions.
Below table is an example of such an operating log. The information in this log is needed
in order to make a satisfactory diagnosis.
kW
0178-250-EN
Cooling water
Inlet
Outlet
lh
Temperature
Machine
room
rpm C
Number of
revolutions
Disch. man.
C C
Suction pipe
temperature
Condenser
Discharge
pipe temp.
Compressor
Suct. man.
Time
Power consump.
Electric motor
Fact.:
No.:
CV/kW:
COS :
n:
rpm
1
Air
Inlet
2
Suction pipe
Outlet
Pres.
Air
Suction pipe
C C
Temp.
Temp. of
ambient
air
C
33
Compressor and unit are now ready for inspection and dismantling, if required.
S Regulate the compressor down to its lowest capacity stage and stop it.
S Now close all stop valves in the pipe connections to the unit except for the suction
stop valve pos. 20, which remains open
until the pressure in the unit has been
equalized to the suction pressure. This is
described in the passage called The nonreturn valve.
S Close suction stop valve pos. 20.
S Any excess pressure in the unit is equalized to atmospheric through stop valve
pos. 24. See the Key to Piping Diagrams
and the chapter on: Protecting the Environment.
The heating element in the oil separator
must remain connected until the pressure
is completely equalized, thus boiling the
refrigerant out of the oil.
34
0178-028-EN
99.05
Before dismantling any part of the compressor or unit for inspection or repair, the pressure must be reduced to atmospheric
pressure. This is done as follows:
0178-028-EN
0178-028-EN
35
R717
HCFC
R717
HCFC
R717
Number of operating
hours from initial startup and after each main
inspection (see footnote)
50
200
1000
2500
5000
10000
15000
20000
25000
30000
35000
40000
NB:
It is not advisable to reuse oil drawn from compressor or plant. This oil has absorbed the
moisture in the air and is likely to cause operating problems.
Always turn off the power to the heating rod before draining off the oil.
36
0178-028-EN
Daily
Activity
1.1 External inspection and leak check.
1.2 Check the oil level in the oil separator.
1.3 Check pressures and temperatures.
1.4 Check for unusual vibrations or noise.
1.5 Record operating data in the log book.
3.2 Take an oil sample from the oil separator and appraise it visually, or send the sample to a laboratory for
anlysis.
Both methods are described in the section entitled
Assessing the oil.
3.3 Replace the filter cartridge in the oil filter, unless it
has been replaced earlier.
3.4 Clean all other oil filters and connections to and from
the compressor.
3.5 Check the coupling and its alignment (SAB 110*)
3.6 Check that all screws and nuts have the correct torque.
4.2 Take an oil sample from the oil separator and appraise it visually, or send the sample to a laboratory for
analysis.
Both methods are described in the section entitled
Assessing the oil.
5.2 Take an oil sample from the oil separator and send it to
a laboratory for analysis, as described in Assessing
the oil.
5.3 Fit a new oil filter cartridge.
5.4 Clean all other oil filters and connections to and from
the compressor.
5.5 Check the coupling and its alignment (SAB 110*)
5.6 Check that the pressure switches and thermostats
function correctly (refer to the set values in the instruction book).
If UNISAB II computerized control is fitted, check the
transducers
(see the instruction manual for UNISAB II )
Check the elastic intermediate part to see whether there are any visible oblique cracks in the rubber part.
If such cracks are observed, replace the intermediate part.
0178-028-EN
37
Periodic service
6
Activity
6.3 Clean all other oil filters and connections to and from
the compressor.
Major service
Carried out as specified
for the individual screw
compressor type.
(See the diagram for major
service)
38
Check the elastic intermediate part to see whether there are any visible oblique cracks in the rubber part.
If such cracks are observed, replace the intermediate part.
0178-028-EN
Visual assessment
If you pour the sample into a clean, transparent glass bottle or a test-tube and hold it up
to a clear light source, it will be easy to assess the quality. You can also compare the
sample with the fresh oil of the same make
and grade.
An oil which you approve on the grounds of a
visual assessment must:
0178-028-EN
Analytical evaluation
Naturally, the oil sample can be analysed by
the oil company which supplies the oil. As
a special offer to our customers SABROE
has developed an analytical concept, in
cooperation with Mobil Oil, which is able to
analyse all oil makes. This will mean a uniform reporting of the results. The analysis
allows the following to be determined:
S Whether or not the oil is still usable - after
filtering, if necessary - or whether it should
be replaced.
S Whether solid particles that may be present in the oil originate from the bearings or
other components exposed to wear and
tear in which case the compressor must
be inspected.
S Each report will include the corresponding
measuring results from the previous 3 oil
analyses. In this way you will be able to
follow up on the state of both the oil and
the compressor from one analysis to the
next.
Procedure
S A form set with a plastic sampling bottle
and a dispatching envelope can be requested from the local Sabroe Refrigeration representation.
S The oil sample must be drained from the
cleaned oil drain valve into the sample
bottle. Screw the lid loosely on and let the
bottle stand for a few hours to enable re-
39
The analysis
The following table states some average values that can be applied in practice. However,
you should be on the alert whenever the results of the analyses approach these values.
In some cases the water content of 100 ppm
in HCFC plants may be too much and thus
lead to Cuplating in the shaft seal.
Limiting values
Parameter
Unit
Method
Sabroe Oil AP 68
Target
Spec.
Target
Spec.
Min.
Max.
Min.
Target
Spec.
Max.
Min.
cSt
ASTM D 445
66
76
53
64
74
51
100
115
80
TAN *1)
mg KOH/g
ASTM D 664
0.03
0.2
0.01
0.2
0.05
0.2
SAN * 2)
mg KOH/g
ASTM D 665
Water
ppm
Karl Fisher
100
100
100
Appearance
report
report
report
Colour
ASTM D
1500
report
report
report
Pentane Insolubles
W%
MM 490
(5mm)
0.05
Oxidation
abs/cm
IR,1700-1720
/cm
Nitration
abs/cm
IR,1627-1637
/cm
Nitro Compounds
abs/cm
IR,1547-1557
/cm
Viscosity @ 40C
Max.
0.05
0.05
0.5
0.5
0.5
ppm
ICP
10
10
10
Copper
ppm
ICP
10
10
10
Silicium
ppm
ICP
25
25
25
Iron
ppm
ICP
100
100
100
Chromium
ppm
ICP
Aluminium
ppm
ICP
10
10
10
Tin
ppm
ICP
10
10
10
40
0178-028-EN
0178-028-EN
system must be completely closed, to prevent the oil being affected by moisture in
the air.
41
TC (C)
55
55
50
50
40
40
35
35
30
30
25
20
95.10
45
25
20
0178-030-EN
45
15
15
10
5
0
5
10
20
30
50
10
5
0
5
10
15
20
30
Booster conditions
40000 hour interval
50
R22
R717
50
30 20
10 5
10
15
20
25
Evaporating temp.
50
30 20
10 5
10
15
20
25
TE (C)
T0177068_0
42
0178-250-EN
0178-256-EN
96.02
OOSI
OOSI
OOSI
OOSI
OOSI
OWSG
OWSG
OWSG
OWSG
OWSG
OWSG
OWSG
HLI
1614
2114
2714
3214
4114
1615
1619
2115
2119
2719
3219
4119
11
20
Litres
SAB
163
SAB
202
11
20
31
48
11
20
31
48
86
25
25
Oil separator
Litres
SAB
SAB
SAB
128
163
202
Compressor + pipes
Litres
SAB
SAB
SAB
128
163
202
80
89
103
112
123
140
216
225
236
253
291
117
230
131
155
244
278
283
324
205
87
25
60
39
39
63
Total, unit
Litres
SAB
SAB
SAB
128
163
202
80
180
12
25
39
63
78
119
0
97
69
92
1614
2114
2714
3214
4114
1615
1619
2115
2119
2719
3219
4119
78
130
Kg
SAB
163
SAB
202
78
130
180
215
78
130
98
180
215
130
380
Basic Unit
Kg
SAB
SAB
SAB
128
163
202
Compressor block
Kg
SAB
SAB
SAB
128
163
202
1008
1060
1528
1580
1630
1665
3218
3270
3320
3355
3520
1580
3270
1660
1760
3350
3450
3580
3880
3160
1050
120
700
185
210
310
20
Total, unit
Kg
SAB
SAB
SAB
128
163
202
20
210
310
440
740
20
950
2100
230
500
1040
1115
950
1470
Compressor type
m3
SAB
SAB
SAB
128
163
202
OOSI
2114
OOSI
3214
OOSI
4114
OWSG 2115
OWSG 2719
OWSG 4119
HLI
0178-250-EN
5
8
11
6
9
4
12
10
43
Suction pressure
[bar]
High alarm
High warning
Low warning
Low alarm
Discharge pressure
[bar]
High alarm
High warning
Low warning
Low alarm
16,0
15,0
1,0
Low warning
Low alarm
4,0
2,5
2+4
2+4
Low warning
Low alarm
0,0
0,0
2+6
2+6
Low warning
Low alarm
1,0
0,5
2+6
2+6
SAB Mk 3 compressors
SAB 202 compressor
Stop/start of oil pump
Set point 1
Set point 2
2,5
4,0
Low warning
Low alarm
2,0
1,5
2+6+10
2+6+10
Low warning
Low alarm
4,0
3,0
2+6
2+6
VMY Mk 3 compressors
Stop/start of full flow
pump
Set point 1
Set point 2
5,5
7,0
High alarm
High warning
1,0
0,7
3
3
3
1
1
1
SAB Mk 1 compressors
44
2+7
2+7
0178-250-EN
96.12
Settings
Current plant
Factory
5,0
1,5
1,0
0178-275-EN
Measuring
Table 2
Screw compressors Measured and calculated temperatures
Settings
Measuring
Factory
Current plant
Notes
1
1
Discharge temp.
[C]
High alarm
High warning
Low warning
Low alarm
100,0
90,0
65,0
Oil temperature
[C]
High alarm
High warning
Low warning
Low alarm
60,0
55,0
25,0
20,0
2+4
2+4
2+4
2+4
Brine temperature
[C]
High alarm
High warning
Low warning
Low alarm
60,0
50,0
4,0
2,0
1
1
1
1
High alarm
High warning
Low warning
Low alarm
110,0
100,0
2,0
0,0
2+4
2+4
2+4
2+4
Low warning
Low alarm
10,0
0,0
2+4
2+4
Calculated value
Disch. gas superheat
[C]
Calculated value
0178-250-EN
45
Notes:
Note 1
The alarm cannot be switched off until the cause has been removed.
Note 2
Note 3
Note 4
Note 5
Note 6
Note 7
Note 8
Note 9
Note 10
46
0178-250-EN
Check
0171-470-EN
97.07
Interval
Condensing pressure
Pressure
and temp.
Filters
Daily
Filter in
liquid line
thermostatic valve
suction line
oil return
Clean when
needed
Dehumidifier
Activity
When
needed
0178-250-EN
47
Check
Interval
Refrigerant charge
Refrigerant
Automatic
controls
Leak detection
Periodically
Electric
motor
Periodically
Corrosion
Periodically
normally
min. 4
times a
year
Frosting-up
When
needed
Evaporator
Oil draining (ammonia plant)
48
The plant must be searched regularly for leaks. Flanges and joints
settle during the plants initial operation period. They must therefore be tightened and checked.
Adjust operating point and check
the function. Replace switch system if sticking.
Clean and lubricate according to
suppliers instructions. At temperatures lower than -25C, use special lubricant.
Alignment of coupling
V-belt drive
Condenser
Activity
Periodically
0178-250-EN
0178-260-EN
99.01
0178-250-EN
Tools
Apart from having the necessary tools at
hand (see the tool list in the instruction
manual), it is an advantage to place the
compressor on an iron plate when
dismantling completely. This will allow for
easy removal of oil leaking from the
compressor during disassembly.
It is also recommended to position the
compressor in a room with plenty of
surrounding space and to ensure that the
room is clean and dustfree.
Evacuation of refrigerant gas
Shut off suction and discharge stop valves
and evacuate the refrigerant gas as
described in the section Protecting the
environment.
Removal of various accessories
When working on the compressor, the power
to the compressor motor must be cut off and
it must be ensured that the compressor
cannot be inadvertently started (if needed,
remove the main fuses).
During an overhaul of the compressor or if
the compressor is removed from the unit,
dismantle the following parts:
1. Coupling between compressor and
motor.
2
49
Parts to be dismantled
Sequence
Oil filter
Suction filter and compr.protect.system
Non-return valve
Shaft seal, balance piston
and cap cover
Thrust cover/regulating cylinder
Regulating slide
1
2
3
7
8
4
5
6
9
10
1. Oil filter
Oil filter pos. 470 is a replaceable filter
cartridge, mounted in the compressor block
as shown on the spare parts drawing. As the
filter capacity of the filter cartridge is being
used the pressure loss across the filter will
increase. This is registered by the two
pressure transducers pos. 752 and pos. 753.
Make sure that a new filter cartridge is at
hand as the replaced oil filter cannot be
cleaned.
Before removing the filter cartridge from the
compressor block, stop the compressor and
50
0178-250-EN
1.2
Fitting of oil filter
1.2.1. After cleaning cover pos. 450 on the
inside, mount filter cartridge pos. 470
and O-ring pos. 453. Fasten these
parts with nut pos. 455.
1.2.2. Position the complete cover, pos. 450,
together with O-ring, pos. 452, in the
compressor and fasten with screws,
pos. 456. Make sure that the O-ring,
pos. 475, has been fitted.
Fig. 1.1
0178-250-EN
51
Suction filter
The suction filter is built into the
compressor housing above the rotors.
52
0178-250-EN
0178-250-EN
53
Fig. 1
Evaporator
Oil separator, condenser
Condensing pressure
Evaporating pressure
Compressor
Functional description
The pilot valve, shown in fig. 1, is actuated by
the high pressure P1. The valve is supplied
with a stainless metal bellow . The
reference pressure in the bellow is the
atmospheric pressure. The effective area of
the bellow is exactly equivalent to the area of
the valve seating, which means that the back
pressure P2 does not affect the opening
pressure of the valve.
The main valve is a normal closed valve. The
high pressure P1 is affecting the lower side of
the valve cone propagating up through the
piston rod to the upper chamber of the
valve, producing a pressure on the piston .
The area of the piston is larger than the area
of the valve seating. Together with the power
of the spring this will keep the valve closed.
When the pressure P1 reaches the set pressure of the pilot valve, it will start opening.
The pressure P2 of the pilot line and of the
lower chamber of the main valve will
54
0178-250-EN
7 bar
a: Shut the flange just mentioned on the manifold pos. 710 tightly and jam in flange
pos. 2 with the lateral connecting piece on
the POV valve, as shown in fig. 2.
Fig. 3
705
705
710B
710A
721A
722A
721B
722B
720
720B
715
0178-250-EN
55
3. Non-return valve
The non-return valve is mounted on the
intermediate flange pos. 253 and positioned
in the suction chamber. While the
compressor is idle the non-return valve is
closed by means of spring pos. 261. See
sectional drawing.
After start-up of the compressor the
non-return valve opens and the compressor
is able to suck in refrigerant gas.
When the compressor stops, the non-return
valve shuts off immediately and hereby
prevents the compressor from running
backwards.
In valve cone pos. 259 a hole of dia. 6 mm
has been bored which slowly equalises the
pressure in compressor and oil separator to
suction pressure at compressor standstill.
Dismantling
S Dismantle the compressor protection
valve and the suction filter as described
in section 2.
S Seal the opening to the rotors with a cloth
free of flocks in order to prevent foreign
particles from falling down to the rotors.
Do never use twisted yarn, paper or
several small cloths.
S Now the suction nonreturn valve can be
dismantled by means of the screw
pos. 258.
S Dismantle the valve cone pos. 259 by removing the countersunk screw pos. 265.
56
0178-250-EN
167
166
165
160D
161
110
113
160E
162
160B
160C
134
160A
T0177135_13
Pos. No.
160 A
Cast-iron seat
160 B
Inner O-ring
160 C
Outer O-ring
160 D
Pointed screw
160 E
166
The shaft seal must ensure complete tightness between the compressor shaft and the
compressor housing, so that the inside of the
compressor is completely sealed off from the
atmosphere.
The shaft seal shown in fig. 4.1. has a built-in
rotating part, which, apart from ensuring
tightness, also assimilates axial displacement
and provides the necessary compressive
force between the two slide faces mentioned
below.
The shaft seal is a slide ring type, consisting
of a stationary cast-iron seat, pos. 160B,
which is positioned in the shaft seal cover
pos 165. Rotation is prevented by retaining
the pin, pos. 161.
0178-250-EN
135
Designation
57
58
Cap cover
After dismantling the screws, pos. 167,
dismantle the cap cover, pos. 163, by
mounting two of the screws in the free
threaded holes in the flange of the cap cover.
Hereby the cap cover can be pushed out.
The cap cover is re- mounted in the same
way as the shaft seal cover.
0178-250-EN
Fig. 5.1
Fig. 5.2
62
60
9.2
22
T0177135_14
0178-250-EN
59
6. Regulating slide
Dismantle the complete capacity slide with
piston, pos. 201 og 202, as described in
section 5: Thrust cover and regulating
cylinder.
Any dismantling of the piston rod, pos. 207A,
and the slide, pos. 200, can be done by
removing the set screw, pos. 311, as well as
the locking device, pos. 312.
The circlip, pos. 207D, and the steel ball,
pos. 207E, act as a kind of non-return valve.
At an emergency stop this non-return valve
ensures the quick movement of the capacity
regulating slide to its minimum position as
the oil is emptied through the non-return
valve.
In case the sealing ring, pos. 204, has been
damaged it must be replaced. This is done
be removing the groove nut, pos. 206, and
the locking plate, pos. 208, whereby the
outer and inner rings of the piston can be
dismantled. Pay attention to the O-ring, pos.
203.
Antifriction tapes, pos. 209, have been fitted
on the end surface of the capacity slide.
Their length is adapted so that they can be
placed loosely in the groove of the capacity
slide.
Mounting
Mounting of the thrust cover, capacity slide
and capacity indicator is done in the following
order:
S Mount the two guide bushings, pos. 22, in
holes B of the compressor block, see fig.
5.2.
S Position the thrust cover with the O-rings,
pos. 43 and 49, against the compressor
block and guide it into its place by means
60
0178-250-EN
0178-250-EN
Dismantling
S After dismantling the screws, pos. 198, the
entire unit with the slide stop cover, pos.
181, and the bearing retainer, pos.185,
can be unscrewed by turning the spindle,
pos.180, anti-clockwise.
When the spindle has been unscrewed
completely from the thread in the threaded
washer, pos. 189, the unit can be removed
manually.
S By dismantling the screws pos. 196, the
cover, pos. 181, is dismantled from the
bearing retainer, pos. 185, and the sealing
washer, pos. 182, the sealing ring, pos.
183, and the O-ring, pos. 184, can be removed manually.
S The spindle, pos. 180, and the ball
bearings, pos. 186, can now be pushed
out of the bearing retainer, pos. 185.
S The slide stop, pos. 190, and the slide
guide, in which the spring has been fitted,
are pressed together and should normally
not be disassembled.
The whole unit cannot be extracted from
the compressor until the suction cover,
pos. 20, has been dismantled. Cf. section
8 or the description found in section 5.
61
Fig. 7.2
T0177135_1
62
0178-250-EN
0178-250-EN
395
63
Position transmitter
S In case arm no. 4 has been dismantled
from the transmitter, it must be fitted
correctly as follows:
S Find the 4mA point of the transmitter
by turning the shaft as described in
the Instruction manual for UNISAB
II.
5
4
3
64
0178-250-EN
Fig. 7.3
3
9
AA
S
NS
SN
N
S
N
S
N
S
N
S
N
S
10
4
11
N
S
SN
NS
390
1
A
6
7
406
from T4161061_0
Dismantling:
S After the magnetic coupling has been dismounted from the compressor as already
described, dismantle circlip no. 1. The
magnet retainer no. 2 and bearing no. 3
can now be pulled out against the magnetic force which is rather strong.
S After removing screw no. 4 spindle pos.
390 can be dismantled.
S Bearing no. 3 can be released once circlip
no. 5 has been removed.
S Should it be necessary to dismantle the
magnetic coupling, screw no. 6 can be
loosened by inserting a 2.5 mm Allen key
0178-250-EN
65
Fig. 8.1
17.1
20
45
T0177135_2
Dismantling
S Dismantle the screws, pos. 113, at the
balance pistons, pos. 134 and 137.
Fig. 8.2
Holes for pointed screws
Holes for
stay bolts
T0177135_3
66
0178-250-EN
Fig. 8.4.b
Fig. 8.3
4 9.2 2
111
20 111
20
112
112
T0177135_7
T0177135_6
Mounting
To mount the slide bearings, pos. 111, carry
out the following procedure:
S Before the slide bearing, pos. 111, is
pushed into place on the cover, pos. 20,
the guide pin, pos. 112, should be
mounted as illustrated in fig. 8.4.a.
The guide pin is knocked just 5 mm into
the hole in the slide bearing and is
straightened up to stand at a right angle to
the end plate.
Fig. 8.4.a
Fig. 8.4.c
111
112
0178-250-EN
112
40
9.1
111
20
T0177135_7
67
Dismantling
17.3
14
16.1 17.3
110
17.2
68
132
18
16.2
15
17.3
14
16.1
17.3
15
17.2
12
133
T0177135_0 V13
0178-250-EN
Fig. 9.4
141
140
10
143
142
T0177135_15
144
141 111 10
3
4.2
T0177135_8
0178-250-EN
S An adjustment device fitted at each discharge port must be loosened before the
discharge ports can be dismantled. The
adjustment device exists in two different
designs dependent on whether the compressor was delivered before or after
January 1999.
S Design 1 (before January 1999)
As shown in fig. 9.4.b., the locking
screw, pos. 146, is first dismantled by
means of an NV5 Allen key, and then
the adjusting screw, pos. 145, is loosened 2 turns with the same Allen key.
69
Fig. 9.4.b
10
145
146
140
141
T0177135_15
148
147
10
149B 149A
70
0178-250-EN
Fig. 9.5.c
7
141 140 10
Fig. 9.5.a
40
111
112
When placing the slide bearing on the compressor block, turn the bearing for the guide
pin to reach the 6 mm hole in the discharge
port - as illustrated in fig. 9.5.b.
8
8
8
Female
Fig. 9.5.b
140 141 112
10
Male
111
0178-250-EN
71
10
25.2
14
Fig. 9.8
10
T0177135_10
72
110 141
46
44
45
T0177135_12
0178-250-EN
22
25.1 20
21
50
Female
19
23
24
Adjustment
9.1
9.2
a:
b:
0178-250-EN
Male
T0177135_9
9.3
9.4
73
9.6
The adjustment completed, loosen adjusting screw pos. 44 and toggle pos.
46 and dismantle inner cover pos. 153.
With tools as shown in fig. 9.5 mount
the outermost inner ring, and fasten
the thrust washer, pos. 114, by means
of the screw, pos. 115.
Tighten screw with 70 Nm.
9.7
9.8
9.9
74
0178-250-EN
Function:
On moving the capacity slide pos. 200 the
spindle, pos. 210, is turned by means of the
helical key groove in the spindle. The spindle
turns the transmitter, pos. 350, via the
magnetic coupling, pos. 216, which is completely tight so that neither oil nor refrigerant
can pass through it.
50
70
71
216
221
210
218
217
61
Dismantling
After cover, pos. 60, has been dismantled
from cylinder, pos. 50, remove the following
parts:
S By removing screws, pos. 73, the
following parts are dismantled:
Flange pos. 72
Sight glass, pos. 75
60
219
223
224
350
75
74
72
73
O-ring pos. 74
hand.
0178-250-EN
75
AA
1
S
218
NS
SN
N
S
N
S
N
S
N
S
N
S
N
S
SN
NS
219
from T4161067_2
76
40
0178-250-EN
Transmitter
Usage:
Assembly
The following drawing shows a position
transmitter for capacity signalling and
indication. The transmitter is fitted in the sight
glass with the plug facing vertically down.
The transmitter arm is turned by the indicator
dial by means of pin no. 3 engaging in the
slot of the dial, pos. 221.
Slide position
4.5 4.
3.5
Volume ratio
3.
100%
2.5
SPAN + ZERO
No. 3
2.
0%
T0177063_0
Terminal
1
2
3
Used for
Signal 020 mA
Power supply
24 V DC +/20%
Earth connection 0V
Not used
Adjustment:
S Turn the transmitter shaft until the output
signal is approx. 4mA. On UNISAB II the
display shows 0%. Secure the arm opposite the 0% mark on the sight glass. Fit
sight glass with transmitter on the compressor. Make sure that the pin no. 3
catches the slot in the indicator dial!
0178-250-EN
77
Notes:
78
0178-250-EN
0178-258-EN
98.05
1. Regulating of compressor
capacity
The regulating system is a complete
assembly as shown in fig. 1. It regulates the
compressor capacity by supplying or draining
oil from the capacity cylinder pos. 50 (see
spare parts drawing).
The system is connected to the oil pressure
at connecting branch B and the oil returns
0178-250-EN
79
Fig. 1
C
A
72
72
NO
71
74
NC
70
73
Function
1. At a constant capacity both solenoid
valves are closed so that pos. 70 is dead
whereas pos. 71 is supplied with current.
2. On regulating to a higher capacity power
is supplied to coil pos. 70 so that both
coils are now supplied with current. Hereby, pos. 70 opens and puts oil pressure on
the capacity cylinder, and pos. 71 remains
closed.
80
3. On regulating to a lower capacity the current is cut to both coils. Hereby, pos. 70
closes and cuts the oil pressure to the capacity cylinder. Pos. 71 opens and lets oil
flow away from the capacity cylinder
through the force of spring pos. 191.
4. By standstill of the compressor the current
to both solenoid valve coils is interrupted.
Hereby, the capacity piston is moved to its
0% position as described in pt. 3, and
the compressor is unloaded at the next
start-up.
0178-250-EN
In the following functional description the solenoid valve in the Vi-regulating system designated as indicated in the dash-and-dot line
frames on drawing in fig. 1.
0178-250-EN
81
Function
The Vi-slide pos. 190 works as a movable
stop for the capacity slide, thus regulating the
size of the discharge port (pos. 140/141) and
consequently the built-in Vi volume ratio of
the compressor.
The Vi-slide is moved by turning the spindle
pos. 180 a predetermined number of revolutions.
S By turning the spindle clockwise a lower
Vi is obtained.
S By turning the spindle anti-clockwise a
higher Vi is obtained
Important
S Adjustment must only take place while the
compressor is at standstill.
S On regulating the Vi-slide to max. or min.
position it must not be tightened against
the end stops. This could impede the
movement of the capacity slide.
82
0178-250-EN
Adjustment of the
Vi-slide position
SAB 202S
R22
R134a
R404A/R507
R407C
2 2.5
Volume
ratio Vi
3 3.5
Vi
4.5
Vi
ECONOMIZER
SAB 202S
R22
R134a
R404A/R507
R407C
0
10
TC
C
20
30
55
50
40
30
20
10
40
50
Adjustment
of Vi
ECONOMIZER
40
2 2.5
Volume
ratio Vi
60
3 3.5
3.5
4
62
4.5
Vi
Single stage
4.5
TE
20
Vi
ECONOMIZER
SAB 202L
R22
R134a
R404A/R507
R407C
10
Evaporating temperature
Single stage
60 62 Turns on the adjusting screw
40
0 20
T250824
Adjustment of the
Vi-slide position
SAB 202L
R22
R134a
R404A/R507
R407C
10
25 20
0
10
TC
C
20
30
55
50
40
30
20
10
40
50
60
C
25 20
0
Adjustment
of Vi
40
60
10
Condensing temperature
Evaporating temperature
10
Condensing temperature
TE
20
0178-250-EN
4.5
Single stage
60
T250825
3.5
Single stage
67 Turns on the adjusting screw
ECONOMIZER
0 20
40
60
67
83
Adjustment of the
Vi-slide position
SAB 202S
R717
Volume
ratio Vi
2 2.5
3.5
4.5 Vi
ECONOMIZER
2 2.5 3
3.5
4.5 Vi
Single stage
SAB 202S
TE
20
Evaporating temperature
0
TC
C
10
20
55
50
40
30
20
10
0
30
40
50
60
C
25
020
Adjusting
of Vi
T250826
Adjustment of the
Vi-slide position
SAB 202L
R717
Volume
ratio Vi
40
2 2.5
10
Single stage
60 62 Turns on the adjusting screw
40
0 20
20
Condensing temperature
R717
10
2 2.5 3
60
3.5
3.5
4.5 Vi
ECONOMIZER
4
4
ECONOMIZER
62
4.5 Vi
Single stage
SAB 202L
TE
20
Evaporating temperature
0
TC
C
10
20
55
50
40
30
20
10
0
30
40
50
60
C
25
0 20 40
Adjustment
of Vi
T250827
84
0 20
40
20
Condensing temperature
R717
10
10
Single stage
67 Turns of the adjusting screw
60
60
ECONOMIZER
67
0178-250-EN
94.12
Kpm
10
12
14
16
18
20
22
24
27
2.2
4.1
7.0
11
15
23
30
38
52
68
ft.lbf.
2.1
3.9
6.8
16
30
50
80 110
Nm
2.7
5.2
9.2
22
40
69 108 147
0171-465-EN
M
Kpm
10
12
14
16
18
20
22
24
27
0.42 0.78
1.4
3.2
6.1
10
16
23
34
44
55
76 100
ft.lbf.
3.0
5.7
10
23
44
75 120 160
Nm
4.1
7.6
14
31
60
98 157 225
HPC/SMC 100
SMC 180
UNF
5/16
3/8
5/8
Kpm
2.1
4.4
17
ft.lbf.
15
32
130
Nm
20
43
167
T0177082_0
0172-133-EN
85
SMC 180
Kpm
3.2
10.2
35
ft.lbf.
23
75
255
Nm
32
101
344
A
Compressor type
Coupling
type
HPO/CMO/TCMO
AMR225
NORMEX
Nm
5/16
3.5
25
34
104-108 AMR312S
7/16
5.6
40
55
112-116 AMR350S
1/2
13
95
128
186-188 AMR450S
11/16
28
200
275
H148
M8
2.2
16
22
H168
M8
2.2
16
22
225
5/16
3.5
25
34
262
3/8
4.2
30
41
312
7/16
5.6
40
55
200
5/16
3.5
25
34
225
5/16
3.5
25
34
262
3/8
4.2
30
41
312
7/16
5.6
40
55
350
1/2
13
95
128
375
9/16
18
130
177
425
5/8
25
175
245
450
11/16
28
200
275
128
163
SAB
128
Series 52
163
86
depending
on the
motor size
Series 52
202
VMY
Torque (A)
ft.lbf.
NORMEX
HPC/
SMC/
TSMC
Thread
Kpm.
Series 52
AMR
HPO/CMO
0172-133-EN
Oil separator
Fig. 1
27A
27B
31
30
98.05
30
0178-259-EN
34
Oil separator
As illustrated in fig. 2, the discharge gas and
the oil from the compressor first pass the
demisters in which the main part of the oil is
separated from the discharge gas and
drained into the oil vessel.
Fig. 2
Demister
27B
27A
To oil vessel
Fine oil separator elements, pos. 55
0178-250-EN
87
2: Refrigerant R717
S All units types LM-SF og LF are delivered with two built-in fine filters and both
connecting branches, 27A and 27B, are
connected to the refrigeration plant.
S Unit type SM is delivered with one fine
filter and only the open connecting
branch, 27A/27B, is connected to the
refrigeration plant.
Fig. 1
to condenser
Fig. 2
to condenser
Fig. 3
88
Throttle valves pos. 52 are used for adjustment of the oil flow through the oil return systems. Their adjustment is just enough to
make the pipelines feel warm during operation. In general, it is recommended not to
open the throttle valves more than 4 turns.
At the same time gas bubbles should be
visible in sight glass pos. 53.
0178-250-EN
Oil vessel
As already mentioned, the lubricating oil is
collected in the oil vessel. The oil level in
the vessel must always be visible in sight
glasses pos. 31. The correct amount of oil in
the unit is stated in a table in a previous
chapter of this book.
The oil vessel contains 2 heating elements,
pos. 30, which must be on whenever the unit
0178-250-EN
is not operating, and off when the compressor is started. Remember to switch off the
heating elements when oil is drained off the
oil vessel before an oil renewal.
Also remember that if the unit has been idle
for a lenghty period without the heating elements being switched on, these must be connected at least 8 hours before the unit is set
into operation.
89
Used for
Hot oil inlet
Cooled oil outlet
Water inlet
Water outlet
Type plate
Air purging from water side
Design
The oil cooler consists, in principle, of a cylindrical jacket with a steel tube insert.
The cooler has oil inlet and outlet sockets in
the jacket, whereas the inlet and outlet for
water are placed in one of the end covers.
The covers are made of cast iron. The tube
insert consists of two tube plates, each with a
number of tubes welded in.
Baffle plates are placed between the tubes to
extend the oils passage through the cooler,
thus causing the oil to flow across the tubes,
90
0171-561-EN
No
1
2
3
4
5
6
95.10
T0177037_0
which significantly improves the heat transmission from the oil to the cooling water.
The end covers on the cooler are formed to
guide the water back and forth a number of
times in order to ensure an adequate water
velocity.
Oil cooler type OWRG is made of stainless
steel in two versions for fresh water and sea
water, respectively. The type is indicated on
the type plate of the cooler.
Futher, the oil cooler can be manufactured
with corrosion plugs on the end covers. To
maintain the corrosion resistance of the two
types of oil cooler, it is a condition that the
pipes never become overheated. Consequently, they must not be uncovered.
To avoid this, it is important that:
0178-268
Application
The OWSG type oil cooler is designed for
connection to a fresh-water system incorporating anti-corrosion and anti-scaling measures.
0178-268
When operating with a cooling tower, rust inhibitors, algicides and anti-fouling must be
added to the water according to normal practice in connection with cooling tower systems.
The OWRG oil cooler type is used where the
quality of the water cannot be guaranteed
satisfactory and constant.
Cleaning
Fouling or soiling of the water side of the
cooler will reduce the heat transfer, and hence the capacity of the cooler.
The cooler must therefore be checked and
cleaned at regular intervals, depending on
the degree of purity of the cooling water. The
internal pipe diameter is 8 mm.
The OWSG/OWRG oil cooler can be cleaned
by removing the end cover with no connection branches and scrubbing the piping clean
with a bronze brush.
Give the tubing a final rinse with fresh water.
Alternatively, ready-mixed inhibitive scouring
acids can be used, with subsequent neutralization. Such agents must be designed for
untreated steel tube heat exchangers. The
chemical manufacturers instructions should
be followed precisely.
91
92
0178-268
4
5
1 pass
1
6
3
4
5
2
2 pass
1
6
0178-261-EN
97.03
T0177101_0/1
1
2
3
Oil inlet
Oil outlet
Refrigerant inlet
For cooling of the oil with refrigerant a closed, welded tubular heat exchanger of the
OOSI type can be used.
Description
The OOSI oil cooler is an all-welded tubular
heat exchanger manufactured in steel. On
the inside the pipes are equipped with a special insert in order to improve the heat transfer.
The oil flows through the pipes, while the refrigerant evaporates outside the pipes. It is a
flooded system, which is to say that the refrigerant leaves the oil cooler as partly evaporated (mixture of liquid and vapour). This
ensures that, under normal conditions, no oil
is accumulated on the refrigerant side.
Mounting
In order for the condenser to function correctly it has to be mounted higher than the oil
cooler to ensure a natural circulation of the
0178-268
4 Refrigerant outlet
5 Oil draining (oil side)
6 Oil draining (refrigerant side R717)
93
Ex. 1
Ex. 2
Condenser
Alternative
arrangement
C
Receiver
H1
E
to the evaporator
or main receiver
H2
Decrease 1:300
to the receiver
A
A
Oil cooler
R
Oil cooler
R
Increase 1:300
94
0178-268
0171-562EN
95.10
No.
1
2
3
4
Used for
Hot oil inlet
Cooled oil outlet
Water inlet
Water outlet
T0177038_1
Construction
The B-type oil cooler is a stainless steel plate
heat exchanger. A V-pattern is moulded into
each plate together with the inlet and outlet
holes. The plate heat exchanger is assembled by turning the V-pattern upwards and
downwards, alternately. All points of contact
between the V-patterns are copper-welded. A
supporting plate is soldered onto either side.
Between the support plate fitted with connecting branches and the first heat- exchanger
plate, a row of channels is visible. By means
of a welding rod, for instance, check that the
V-pattern faces up-wards, preventing water
from accumulating here. Owing to the principle of its design, the heat exchanger cannot
be stripped down and must not be used in
R717 plants.
Application
The B-type oil cooler can only be used with
freshwater as cooling agent.
0178-250-EN
Cleaning
Since the oil cooler cannot be dismantled,
mechanical cleaning is not possible. It is therefore recommended that the water filter be
fitted before the oil cooler. Cleaning can only
be done with a cleaning fluid. The cleaning
intervals for the cooling water side of the heat
exchanger should be determined on the basis of the waters hardness and tendency to
deposit scale.
For cleaning purposes a weak acid can be
used as e.g. a 5% phosphoric acid or, if the
heat exchanger is cleaned often, a 5% oxalic
acid solution. Rinsing with plenty of pure water is then required to remove any remaining
acid and dirt.
95
96
0178-250-EN
Fig.1
Fig. 2
To the compressor
Oil cooler
0178-277-EN
98.05
Three-way
valve
Valve
dimension
Welded
connection
SAB 110
RT3
DN 25
SAB 128
RT3
DN 25
SAB 163
RT5
DN 40
SAB 202
RT6
DN 50
SAB 330
RT6
DN 50
VMY 536
RT6
DN 50
0178-085-EN
97
During operation the thermo element will adjust the regulating cone modulatingly so that
the two oil flows are mixed to the set oil temFig. 3
Fig. 4
B
Varm oil
from oil
separator
B
Varm oil
from oil
receiver
Cooled
oil from
oil cooler
C
Cooled
oil from
oil cooler
2
1
A
Thermo element in cold position
Oil with
correct
mixed temp.
Assembling:
Dismantling:
98
0178-085-EN
Notes:
0178-085-EN
99
Note:
The heating rod must not be energized if
the oil level in the reservoir is below the
minimum mark in the sight glass, and it
should generally be switched off during
compressor operation. Remember to turn
off the heating rod whenever the crankcase of the reciprocating compressor is
opened for inspection.
The following table indicates which heating
rods are used for the various compressor
types. In the spare parts lists for compressor
or unit you will find the current part numbers.
Marking:
NV 50
50
30
30
G 1 1/4
Prod. nr.
Watt
Volt
Manu. date
L1
L2
80
Heating rods
Power
Watt
Voltage
V
270
270
270
250
230
115*
460
460
460
250
230
115*
L1
mm
L2
mm
Used for:
158
175
100
0178-085-EN
98.05
0170-017-EN
In order to keep the lubricating oil in the compressor warm during a period of standstill,
the oil reservoir has one or two heating rods
built in. Before start-up, the heating rod (s)
must have been activated for 6-8 hours in
order to ensure that there is only a minimum
of refrigerant in the oil. When containing
much refrigerant, the oil will lose its lubricating property and the following operational interruptions may occur:
0178-266-EN
97.12
Stopping the compressor at too high a differential pressure happens with a 30 second
delay as the pressure difference may momentarily exceed 1.0 bar if the compressor is
started up with cold oil.
0178-250-EN
101
Top up the filter housing with clean refrigerant oil after positioning the whole filter cartridge.
Note:
Remember to open the stop valves before
and after the oil filter before restarting the
compressor.
Note:
While the compressor is working, both
discharge valves should be open to avoid
that a hydraulic pressure arises in the filter
housing.
102
0178-250-EN
0178-265-EN
97.12
Description
The oil pump, pos. 63, is an internally
toothed gear pump with built-in pressure
relief valve and slide ring shaft sealing. The
pump is fitted with suction inlet facing downwards and discharge connection and outlet
from pressure relief valve facing upwards.
The pump is fitted on an intermediate piece
which again is mounted on the electric motor.
The electric motor is fastened to the oil separator by means of a small frame.
In consideration of bearings and shaft sealing, the pump may only run without an oil
flow for brief periods. On charging of oil to a
completely empty oil separator it must be
made sure that the pump is filled with oil in
accordance with the instruction: Preparations
before Start-up.
2. Dismantle the screws between the intermediate piece and the oil pump.
Dismantle the screws that keep the motor
fixed to the oil separator, at the same time
supporting the motor. The motor with the
intermediate piece can now be pulled
away from the oil pump. It may be necessary to dismantle the wires leading to the
electric motor in order to remove it sufficiently. Now carry out the replacement of
the shaft seal with the pump still mounted
in the pipe system.
Service
Start-up
0178-015-EN
103
3
S Pull off the shaft seal housing by turning
thrust screw no. 2. Replace the O-ring
pos. 6, which seals the shaft seal housing,
if damaged.
S Loosen the 3 pointed screws in the rotating part of the shaft seal pos. 9, and pull if
off the pump shaft. In order to remove the
fixed part of the shaft seal, bearing pos.
10 must first be pressed out with punch
no. 5.
Remember to dismantle locking ring pos.
11. The fixed part of the shaft seal can
now be pushed into the shaft seal housing.
S Tape over the key way in order to protect
the O-ring of the shaft seal and lubricate
the shaft in refrigerating machine oil. Take
care not to damage the lapped surfaces
on the shaft seal parts.
S Press the rotating part of the shaft seal
over the shaft. On mounting of the shaft
seal, press it against the oil pump housing
with a 0.05 mm feeler gauge in between.
Tighten the 3 pointed screws in turns.
S Mount the fixed part of the shaft seal inside the shaft seal housing. Make sure
104
0178-015-EN
Pos.
1
2
3
4
5.
6
8
9
10
11
12
13
14
Designation
Pump cover
Pump shaft
O-ring
Pump wheel
Housing
O-ring
Shaft seal housing
Shaft seal
Bearing
Circlip
Rotor shaft
Shim
Shim
0178-015-EN
Tools
4
1
3
No.
1
2
3
4
5
6
Designation
Puller
Screw M10 x 75
Threaded rod M8 x 150
Nut M8
Punch, solid
Punch, hollow
105
94.05
0178-264-EN
106
Note:
Some oil will be present in both the filter
and the oil pump. This oil may be drained
off through valve pos. 62.
The filter element can be cleaned in a cleaning fluid by means of a stiff brush and pressurized air. Hereafter, refit the filter element
and close valves pos. 62 and 64. At the
same time open valves pos. 60 and 65.
0178-250-EN
Safety devices
95.10
Pos. 28
0171-566-EN
0178-250-EN
On units to be approved by TV
(Germany), the KP5 is replaced
by a pressure cut-out KP 7ABS
which has been approved by
TV. This high pressure cut-out
will stop the compressor in the
event of damage to the cut-out
bellow or excessively high discharge pressure.
Pos. PDAZ 11 Differential oil pressure cutout MP55. This pressure cut-out
is designed to ensure sufficient
lubricating pressure and oil
pressure for capacity regulation.
The pressure cut-out is equipped with a time lag of 45 secs.
If the preset differential pressure
has not been obtained by that
time, the compressor will stop.
The MP55 is equipped with
manual reset.
Pos. 0376-A12
Differential pressure cut-out for
control of pressure drop across
oil filter. If pressure drop across
oil filter becomes excenssive
107
108
Monitoring devices
Pos. PI15
Pos. PI16
Pos. TI5
Pos. TI6
Pos. TI7
0178-250-EN
4. Keep a close eye on the suction pressure gauge! When the suction pressure is
equal to atmospheric, stop the compressor and quickly shut off the discharge stop
valve. Shut off any stop valve in the oil return line.
94.05
0171-464-EN
bled of refrigerant. Adjust any constantpressure valves to bring evaporator pressure down to atmospheric.
0171-702-EN
Dismantling plant
In order to prevent moisture penetrating into
the refrigeration plant during any repair work,
it is advisable to follow the rules below:
1. No component should be opened unnecessarily.
2. When dismantling the system, the pressure in the system should be a little higher
than atmospheric.
109
3. Note:
If the piping system is colder than the surroundings, there is a considerable risk of
damp precipitation (condensation) on cold
plant parts. Plant components to be dismantled must be warmer than the ambient temperature.
110
Note:
If the oil in the crankcase of the piston
compressor or the oil separator of the
screw compressor has been in contact
with the atmospheric air for any length of
time, it must be replaced with fresh oil of
the same grade and make.
0171-702-EN
Experience shows that pressure and temperature variations in a refrigerant system can
provide information about the operating condition of the refrigeration plant.
0171-627EN
95.01
Example
Observed error: excessive suction
pressure - error code 5.
Cause codes: 2. (compressor lacks capacity) and 48. (safety valve leaky or opens prematurely).The entry keys to the subsequent
section are therefore (5,2) and (5,48).
Observed Fault
Probable causes
1
2
3
10
11
12
13
14
15
3, 4, 12.
3, 4.
15, 16, 17.
16
17
18
31, 32.
47, 50.
5, 7,
19
20
21
5
6
7
8
9
0178-012-EN
8,
6, 12, 13, 19, 34, 35, 36, 40, 41, 45, 46,
2, 3, 4, 42, 48, 49.
1, 31, 32.
47
111
Code
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
112
Cause
Code
Cause
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
52
0178-012-EN
Remedying Malfunctions
1. Excessive suction temperature
1.2
Inadequate capacity
Increase capacity
1.28
1.48
2.32
Excessive capacity
3.14
3.27
3.28
3.29
3.30
3.33
3.42
Insufficient charge
0178-012-EN
113
4.14
4.27
4.28
4.29
4.30
4.33
4.39
4.42
4.49
5.48
114
7.22
7.23
7.24
0178-012-EN
7.26
7.38
7.43
7.44
Check whether compressor capacity corresponds to load on plant. Regulate water supply to
condenser.
8.25
9.11
9.31
9.32
0178-012-EN
115
10.18
10.20
10.48
11.50
13.4
Change or fix
13.12
116
14.3
14.4
0178-012-EN
Clean filter
15.16
15.17
16.32
If the compressor is stopped and the current interrupted at the main switch, any refrigerant in
the oil reservoir will evaporate. As the heating
element in the oil reservoir has also been cut off,
the heat needed for evaporation must be taken
from the surroundings. The oil will therefore go
very cold and will require heating up before restarting.
17.50
0178-012-EN
117
18.7
Tighten bolts
18.8
Adjust alignment
18.9
18.10
18.31
18.32
18.48
118
19.6
19.12
19.13
19.19
19.34
19.35
19.36
19.40
19.41
19.45
Fuses blown
19.46
19.47
Switch power on
0178-012-EN
20.3
20.4
20.42
20.48
20.49
Reduce capacity
21.31
21.32
0178-012-EN
119
120
0170-151-EN
99.02
0170-151-EN
2%. For the other area, the max. oil concentration must not exceed 5%. For area B:
please contact YORK Refrigeration.
Plants with several different compressor
types/makes
In plants comprising several different interconnected compressor types and makes, it is
strongly recommended that all compressors
should use the same type of oil. This is essential where automatic oil return systems
are employed.
If it is intended to change the oil from one
type to another, please refer to the Oil changing on SABROE compressors later in this
publication.
Selecting the lubricating oil
There are a number of operating diagrams
for the selection of lubricating oils for Sabroe
compressors operating with various refrigerants. Once the general conditions concerning the lubrication of the compressor and oil
type in the plant have been considered, the
specific plant conditions must be taken
into consideration.
Use the Oil recommendation diagrams to select the appropriate oil code number.
The oil code number consists of letters designating the oil type together with the Sabroe
viscosity grade number.
Code
design
Oil types
Mineral oil
PAO
AP
0170-151-EN
121
122
Screw compressors:
The oil temperature before injection in
the compressor, but after the oil cooler
Max. permitted oil temperature = setting point for alarm
Min. permitted oil temperature = setting point for alarm
Condensing pressure
Evaporating pressure
S Oil viscosity in the compressor during
operation and under the influence of:
Refrigerant type and solubility of refrigerant in the oil
Operating temperatures
Vapour pressure in the oil reservoir
Reciprocating compressor: Suction
pressure and oil temperature in the
crankcase.
Screw compressor: Discharge pressure
and gas temperature.
S Compatibility with the neoprene O-rings:
the aniline point gives an indication of how
the O-ring material reacts to the oil.
At an aniline point less than approximately
100C the material tends to swell, and at
an aniline point higher than approximately
120C it tends to shrink.
For this reason it is not recommended to
change oil type from M oil to PAO oil as a
leakage may occur if the O-rings are not
changed. YORK Refrigeration therefore
recommends using the Sabroe AP68 oil
as it reduces the risk of leaks considerably
in this case.
0170-151-EN
0170-151-EN
123
Code no
Area no
1
Please observe !
Plants may operate at different conditions
from time to time, for example at different
evaporating temperatures due to plant
variations or at different condensing temperatures due to seasonal changes.
By plotting TC and TE in the oil recommendation diagram, this example would
require a No 1 oil. If, however, TE
changes at certain times, e.g. from 3 to
+7C, a No 2 oil should be utilised. But, as
+7C is inside the marked area, the No 1
oil can be utilised also at this TE.
R134a
TC
F
C
158 70
140 60
Condensing temperature
122 50
104 40
86 30
68 20
50 10
32
E5
E9
Y
Y
14 -10
-4 -20
-22 -30
-60 -50 -40 -30 -20 -10 0 10 20 30 C
-76 -58 -40 -22 -4 14 32 50 68 86 F
Evaporating temperature
TE
124
0170-151-EN
l :
A :
B :
C :
* :
Dry expansion systems only. Flooded systems to be considered individually: contact YORK Refrigeration
SH :
0170-151-EN
125
Sabroe
Viscosity
Viscosity
Spec.
Flash p.
Pour p.
Anilin
Acid no.
code
cSt
40C
cSt
100C
Index
grav. at
15C
COC
C
C
point
mg
KOH/g
M1
63
6.4
14
0.91
202
36
81
0.02
A3
97
8.1
13
0.86
206
32
78
0.05
AP1
64
9.3
121
0.858
195
51
121
0.04
PAO3
66
10.1
136
0.835
266
<45
138
0.03
PAO5
94
13.7
147
0.838
255
<45
144
0.03
PAO9
208
25
149
0.846
260
<39
154
0.03
E3
E5
E9
E11
Due to the big difference between polyolester-based lubricants from various suppliers, it is
not possible to present typical data for these oils. When using another oil brand than the one
recommended by YORK Refrigeration, please contact the oil supplier to select the correct
oil type.
The listed data are typical values and are intended as a guideline only when selecting a similar
oil from a different oil company. Data equivalence alone does not necessarily qualify the oil for
use in YORK Refrigerations Sabroe compressors.
126
0170-151-EN
Part no.
20 litre pail
M 1 (M68)
1231-264
1231-296
A 3 (A100)
1231-263
1231-262
AP 1 (AP68)
1231-257
1231-260
PAO 3 (P68)
1231-256
1231-259
PAO 5 (P100)
1231-282
1231-283
PAO 9 (P220)
1231-284
1231-285
E 3 (E68)
1231-272
1231-273
E 5 (E100)
1231-274
1231-275
E 9 (E220)
Sabroe H oil
E11 (E370)
1)
1231-279
3914 1512 954 1)
The oils recommended by the former Stal Refrigeration correspond to the following oils:
Stal Refrigeration oil type
0170-151-EN
Sabroe oil
M1 (M68)
Sabroe H oil
E 11 (E 370)
127
R717
TC
one-stage
reciprocating
compressors
Area no
122 50
Condensing temperature
Code no
104 40
86
30
68
20
50
10
32
14 -10
1
PAO 3
AP 1
M1
Y
l/Y
-4 -20
-22 -30
See note
-60
-50
-40
-30
-20
-10
10
20
-76
-58
-40
-22
-4
14
32
50
68
TE
Evaporating temperature
Note: YORK Refrigeration recommends that the use of M oils is restricted to moderately loaded compressors and
that the oil quality is monitored carefully via regular oil analyses.
Y
l :
128
0170-151-EN
R717
TC
two-stage
reciprocating
compressors
122 50
Code no
Area no
Condensing temperature
104 40
86 30
68
20
50
10
32
14 -10
1
Y
PAO 3
AP 1
l/Y
M1
See note
-4 -20
-22 -30
-60
-50
-40
-30
-20
-10
10
20
-76
-58
-40
-22
-4
14
32
50
68
TE
Evaporating temperature
Note: YORK Refrigeration recommends that the use of M oils is restricted to moderately loaded compressors and
that the oil quality is monitored carefully via regular oil analyses.
Y
l :
0170-151-EN
129
R717
TC
176 80
Condensing temperature
158 70
140 60
122 50
104 40
86 30
68 20
50 10
Code no
Area no
1
PAO 5
32
0
-30
-20
-10
10
20
30
40
50
-22
-4
14
32
50
68
86
104
122
TE
Evaporating temperature
Please observe: PAO 5 oil is the only oil which can be used in the HPO and HPC compressors.
Y
130
0170-151-EN
R22
TC
Condensing temperature
one-stage
reciprocating
compressors
Code no Area no
122
50
104
40
86
30
68
20
50
10
32
14 -10
-4 -20
1
A3
-22 -30
-60
-50
-40
-30
-20
-10
-76
-58
-40
-22
-4
14
10
20 C
32
50
68 F
TE
Evaporating temperature
0170-151-EN
131
R22
TC
two-stage
reciprocating
compressors
122 50
Condensing temperature
104 40
Code no Area no
86
30
68 20
50 10
32
14 -10
-4 -20
1
A3
-22 -30
-60
-50
-40
-30
-20
-10
10
20
-76
-58
-40
-22
-4
14
32
50
68
TE
Evaporating temperature
132
0170-151-EN
R134a
TC
140 60
Condensing temperature
Code no
122 50
104 40
E5
E9
86
30
68
20
50
10
32
14 -10
Area no
1
C
158 70
F
one-stage
reciprocating
compressors
-4 -20
2
-22 -30
Y
-60 -50 -40 -30 -20 -10
10
20
30 C
32
50
68
86 F
-4
14
TE
Evaporating temperature
Y:
0170-151-EN
133
R134a
TC
two-stage
reciprocating
compressors
C
158 70
Condensing temperature
140 60
122 50
86
30
68
20
50
10
32
14 -10
-4
Code no Area no
1
E5
104 40
-20
-22 -30
-40 -40
-70 -60 -50 -40 -30 -20 -10
-94 -76 -58 -40 -22
-4
10
20
30 C
14 32
50
68
86 F
TE
Evaporating temperature
134
0170-151-EN
R407C
TC
one-stage
reciprocating
compressors
122 50
Condensing temperature
104 40
Code no Area no
86
30
68 20
50 10
32
14 -10
-4 -20
1
E3
-22 -30
-60
-50
-40
-30
-20
-10
10
20
-76
-58
-40
-22
-4
14
32
50
68
TE
Evaporating temperature
Y:
B :
C :
0170-151-EN
135
R407C
TC
two-stage
reciprocating
compressors
122 50
Condensing temperature
104 40
Code no Area no
86
30
1
B
68 20
50 10
32
14 -10
-4 -20
1
E3
-22 -30
-60
-50
-40
-30
-20
-10
10
20
-76
-58
-40
-22
-4
14
32
50
68
Evaporating temperature
Y:
B :
C :
136
TE
0170-151-EN
R404A
TC
one-stage
reciprocating
compressors
122 50
Code no
Area no
1
E3
Condensing temperature
104 40
86
30
68 20
50 10
32
14 -10
-4 -20
Y
-22 -30
Y
E5
-60
-50
-40
-30
-20
-10
10
20
-76
-58
-40
-22
-4
14
32
50
68
TE
Evaporating temperature
Y:
C :
:
0170-151-EN
137
R404A
TC
two-stage
reciprocating
compressors
122 50
Condensing temperature
104 40
Code no Area no
86
30
68
20
50 10
32
14 -10
-4 -20
1
E3
-22 -30
-60
-50
-40
-30
-20
-10
10
20
-76
-58
-40
-22
-4
14
32
50
68
Evaporating temperature
Y:
C :
138
TE
0170-151-EN
R410A
TC
HPO og HPC
reciprocating
compressors
122
60
104
50
Condensing temperature
40
Code no Area no
86
30
68
20
50
10
32
0
A
-10
14
-20
-4
-30
1
E5
-22 -40
-60 -50 -40 -30 -20 -10
10
20
30
40
50
TE
-76 -58 -40 -22
-4
14 32
50
68
Evaporating temperature
Y:
A :
0170-151-EN
139
R507
TC
one-stage
reciprocating
compressors
122 50
Condensing temperature
104 40
Code no Area no
86
30
68 20
50 10
32
14 -10
-4 -20
1
E5
-22 -30
-60
-50
-40
-30
-20
-10
10
20
-76
-58
-40
-22
-4
14
32
50
68
Evaporating temperature
Y:
C :
must be introduced.
Min suction temperature 50C: at TE< 50C superheating most
140
TE
0170-151-EN
R507
TC
two-stage
reciprocating
compressors
122 50
Condensing temperature
104 40
Code no Area no
86
30
1
68 20
50 10
32
14 -10
-4 -20
1
E5
-22 -30
-60
-50
-40
-30
-20
-10
10
20
-76
-58
C
-40
-22
-4
14
32
50
68
Evaporating temperature
Y:
C :
0170-151-EN
TE
141
R717
TC
Condensing temperature
Screw compressors
Code no Area no
1
PAO 3
AP 1
l/Y
M1
See note
122
50
104
40
86
30
68
20
50
10
32
14 -10
-4
-20
-22 -30
-60
-50
-40
-30
-20
-10
10
20
-76
-58
-40
-22
-4
14
32
50
68
TE
Evaporating temperature
Note: YORK Refrigeration recommends that the use of M oils is restricted to moderately loaded compressors and
that the oil quality is monitored carefully via regular oil analyses.
HLI:
Y :
l :
C :
142
0170-151-EN
R22
TC
Screw compressors
122 50
SH25
Code no
Area no
1
2*
A3
PAO 5
Condensing temperature
104 40
SH5
86 30
SH10
68 20
50 10
32
14 -10
SH20
-4 -20
-22 -30
SH20
-60
-50
-40
-30
-20
-10
10
20
-76
-58
-40
-22
-4
14
32
50
68
TE
Evaporating temperature
Using the calculating programme COMP1 it is possible to optimize the requirement for suction superheat values
(SH) as stated in the diagram. See Oil types and oil companies in this section. Due to the ongoing development of
lubrication oils, please contact YORK Refrigeration for an update on the requirement for superheat.
HLI: Calculation must be performed using COMP1.
Y :
A :
C :
* :
Dry expansion systems only. Flooded systems to be considered individually: contact YORK Refrigeration
SH :
:
0170-151-EN
143
R134a
TC
Screw compressors
158 70
Condensing temperature
140 60
Code no
104 40
86
30
68
20
50
10
32
Area no
(See note)
1
E5
E9
122 50
14 -10
SH30
SH20
SH10
SH5
SH20
-4
Y
-20
-50
-58
-40
-30
-20
-10
10
20
30 C
-40
-22
-4
14
32
50
68
86 F
TE
Evaporating temperature
Note: For the compressors type S, Rotatune, SAB 81, SAB 83, and SAB 85 only Sabroe oil H is approved.
Using the calculating programme COMP1 it is possible to optimize the requirement for suction superheat values
(SH) as stated in the diagram. See Oil types and oil companies in this section. Due to the ongoing development
of lubrication oils, please contact YORK Refrigeration for an update on the requirement for superheat.
HLI: Calculation must be performed using COMP1.
Y :
SH :
144
0170-151-EN
R404A
TC
Screw compressors
SH15
Area no
(See note)
1
2
3
Code no
E3
E5
E9
Condensing temperature
104 40
86
30
68
20
50
10
32
SH10
2 (3)
(2)
14 -10
-4 -20
SH15
-22 -30
-70
-60
-50
-40
-30
-20
-10
-94
-76
-58
C
-40
-22
-4
14
10
32
50
TE
Evaporating temperature
Note: For the compressors type S, Rotatune, SAB 81, SAB 83, and SAB 85 only Sabroe oil H is approved.
Using the calculating programme COMP1 it is possible to optimize the requirement for suction superheat values
(SH) as stated in the diagram. See Oil types and oil companies in this section. Due to the ongoing development
of lubrication oils, please contact YORK Refrigeration for an update on the requirement for superheat.
HLI: Calculation must be performed using COMP1.
Y :
B :
C :
SH :
0170-151-EN
145
R407C
TC
Screw compressors
122
50
40
Condensing temperature
104
Code no
Area no
(See note)
1
2
E3
E9
86
30
68
20
50
10
32
-4
-20
SH5
-22 -30
SH5
14 -10
SH10
-70
-60
-50
-40
-30
-20
-10
-94
-76
-58
-40
-22
-4
14
10
20 C
32
50
68 F
TE
Evaporating temperature
Note: For the compressors type S, Rotatune, SAB 81, SAB 83, and SAB 85 only Sabroe oil H is approved.
Using the calculating programme COMP1 it is possible to optimize the requirement for suction superheat values
(SH) as stated in the diagram. See Oil types and oil companies in this section. Due to the ongoing development
of lubrication oils, please contact YORK Refrigeration for an update on the requirement for superheat.
HLI: Calculation must be performed using COMP1.
Y :
B :
C :
SH :
146
0170-151-EN
R507
TC
Screw compressors
104 40
Condensing temperature
Code no
E5
E9
Area no
(See note)
1
2
Y
86
30
68
20
50
10
32
SH5
SH5
SH15
14 -10
-4 -20
SH30
-22 -30
-70
-60
-50
-40
-94
-76
-58
C
-40
-30
-22
-20
-10
-4
14
10
32
50
TE
Evaporating temperature
Note: For the compressors type S, Rotatune, SAB 81, SAB 83, and SAB 85 only Sabroe oil H is approved.
Using the calculating programme COMP1 it is possible to optimize the requirement for suction superheat values
(SH) as stated in the diagram. See Oil types and oil companies in this section. Due to the ongoing development
of lubrication oils, please contact YORK Refrigeration for an update on the requirement for superheat.
HLI: Calculation must be performed using COMP1.
Y :
C :
SH :
0170-151-EN
147
Oil Types
Company
Aral
Avia
BP
Castrol
Chevron (UK: Gulf Oil)
CPI Engineering Services
DEA
Elf / Lub Marine 1
Esso/Exxon
Fina
Fuchs
Hydro-Texaco
PAO
AP
ICI
Kuwait Petroleum (Q8)
Mobil
Petro-Canada
Shell
Statoil
Sun Oil
148
0170-151-EN
Notes:
0170-151-EN
149
Note:
Before work on the coupling can proceed,
it must be ensured that the compressor
cannot be started inadvertently. If need
be, remove the motor protection devices.
Vibrations may be caused by the following:
a) Distortion between compressor unit and
foundation.
b) Distortion between compressor and base
frame.
c) Distortion between motor and base frame.
d) Strains from pipe connections between
compressor and plant.
e) Incorrect alignment of coupling between
compressor and motor.
f) Untruth in compressor or motor shafts.
g) Untruth in coupling.
h) Imperfect balancing of coupling.
i) Imbalance in compressor and motor.
The fitter who sets up the unit is responsible
for points a-b-c-d-e. The other points must be
checked by the compressor or motor manufacturer prior to delivery.
The following sections will deal with the individual points concerning the fitter.
150
When installing the unit straight onto a foundation, the foundation should be cast in accordance with the foundation drawing
forwarded.
When the foundation has been cast, with the
holes marked out as shown, and has set, the
unit should be positioned, allowing it to rest
on sleepers, laid with a spirit level, at a
suitable height so that the foundation plate is
slightly recessed into the foundation.
Check that the foundation plates are hard on
the base frame - this is best done by tying
them up to the base frame with steel wire.
The concrete which is cast down around the
foundation bolts should have only minimal
water content to allow it to be rammed well
down around the bolts and up under the
foundation plates. Low water content does
not cause the hardening concrete to shrink.
10-14 days should pass before tightening the
foundation bolts. Remove the steel wire beforehand and check that there is no air space
between the footplate of the base frame and
the foundation plate. Otherwise, shims must
be inserted between the plates before
lashing them down.
0178-250-EN
95.01
0171-669-EN
fitted correctly, as shown in the drawing forwarded, since the load on the foot-plates
varies.
Standard type
A 1 to 2 mm.
Marine type
A
A 3 to 5 mm.
T0177040_0
Standard type
The machine room or ship floor on which the
unit is to be placed must possess the
necessary bearing strength and be level
enough for the difference in height between
the foundation plates not to exceed the
scope for adjustment on the vibration
dampers, as stated in the positioning
drawing.
The vibration dampers are installed on the
unit in their unstressed state while it is suspended from the crane; the unit is then
placed in its final position.
The unit is aligned with the aid of wedges
placed in the vicinity of the vibration
dampers.
When the unit is horizontal, both longitudinally and laterally, the vibration dampers are
tightened exactly enough to release the
wedge.
0178-250-EN
The vibration dampers are intended to compress between 1.0 and 2.0 mm under the expected load at the corresponding point of
support.
To check that the vibration dampers are
adjusted for the correct load, make a note of
measurement A in the unloaded state for
each individual damper. After mounting and
adjustment, A should be reduced by 1 to 2
mm.
When the adjustment is correct, tighten down
the lock nut.
Alignment of the unit against the foundation
is now complete.
Marine type
Always fit the vibration dampers directly
under the feet of the base frame.
Measure the A-measure of the vibration
dampers while unit is still suspended in the
crane. Measure it again once the unit is back
151
152
min. 1.5 m.
Connection to
compressor unit
0178-250-EN
0178-250-EN
T0177059_0
153
Z
2
X
a
C
T0177120_0/V1
Coupling alignment
The principle of the alignment procedure is to
move the motor so that its shaft forms a continuation of the compressor shaft, but with
the motor shaft 0.05 mm higher than the
compressor shaft. In operation, the compressor shaft is lifted, owing to the fact that it
rests in slide bearings.
Mounting
1) Dismantle the coupling. Note the placing
of bolts, washers and nuts, as these must
be mounted in the same order again. Tie a
string or a piece of thread through one of
the bolt holes in the coupling discs in order to avoid the plates being turned rela-
154
0178-250-EN
Compressor
Bushing
and shaft
must be
flush
with each
other
Tighten the screws on the bushing crosswise, first to 18 Nm and then to the final
torque of 35 Nm. The screws must be
tightened cross-wise and a torque wrench
must be used.
Coupling
No.
Diam.
A
mm
Distance
C
mm
Torque
200
225
138
145
127
127
34
34
262
168
127
41
312
198
140
55
350
221
152
128
375
246
178
177
425
267
178
245
450
287
203
275
Nm
0178-250-EN
rotation
Pos. 1
Horizontal
mm
0 0.05
Pos. 2
Vertical
mm
mm
0.10 0.15
0 0.05
155
b
2a
4. Lift the motor by placing shims with thickness Z / 2 + 0.05 mm underneath all four
feet.
5. After securing the motor, repeat the measurement and compare the results with the
values in the table.
156
0178-250-EN
T0177045_0
0178-250-EN
157
Pressure transducer
(suction pressure)
PDAZ10
PT2
Pressure transducer
(discharge pressure)
PDAZ11
PT3
Pressure transducer
(oil pressure after oil filter)
TAZ12
Pressure transducer
(oil pressure before oil filter)
Thermostat
(oil temperature in manifold)
TAZ13
PT5
Pressure transducer
(oil pressure after oil pump)
Thermostat
(discharge gas temperature)
TC14
Thermostat
(pilots solenoid valve pos. 82)
TT5
Temperature transducer
(discharge gas temperature)
PI15
TT6
Temperature transducer
(oil temperature in flow control)
PI16
High-pressure manometer
PDI17
Temperature transducer
(suction gas temperature)
FT18
Level switch
19
20
21
Non-return valve
GT9
22
PAZ10
23
Low-pressure cut-out
(only for classified systems)
24
25
Oil separator
PAZ2
High-pressure cut-out
26
PDAZ3
27
Thermometer
(discharge gas temperature)
28
TI6
29
TI7
30
31
32
PT4
TT7
GT8
PAZ1
TI5
GT8
158
Position transmitter
(capacity slide)
0178-085-EN
0171-575-EN
PT1
99.11
33
60
Stop valve
34
61
Oil filter
35
62
63
Oil pump
36
64
37
65
Stop valve
38
66
39
Oil filter
67
40
41
68
Stop valve
42
69
Non-return valve
43
70
44
71
45
72
46
Thermostatically-controlled 3-way
valve for oil temperature
regulation
73
74
75
Non-return valve
76
80
Stop valve
81
82
TC83
84
Stop valve
90
91
47
48
49
50
Stop valve
51
Oil filter
52
Nozzle/throttle valve
53
54
Stop valve
55
56
Non-return valve
57
Hand-regulated valve
92
58
93
59
Oil receiver
94
0178-085-EN
159
95
127
Stop valve
128
Stop valve
96
129
130
Stop valve
97
Economizer connection
131
Stop valve
98
132
Liquid filter
99
140
100
141
Main valve
142
Pilot valve
101
143
Solenoid valve
144
Stop valve
145
Float valve
147
Liquid filter
148
149
Non-return valve
150
Stop valve
151
Safety valve
152
Solenoid valve
153
Stop valve
154
Stop valve
160
Stop valve
200
201
202
Stop/non-return valve
203
204
102
Non-return valve
103
Stop valve
104
Nozzle
105
Flow switch
106
107
108
110
Stop valve
TC111
Thermostatic valve
112
113
Liquid filter
114
Stop valve
115
116
Economizer vessel
120
Stop valve
205
Filter
122
Main valve
206
Nozzle
123
207
124
208
125
Safety valve
FT209
126
Float valve
210
Non-return valve
160
0178-085-EN
211
Stop valve
223
212
224
213
Non-return valve
225
214
Filter
226
215
227
220
221
222
Note:
On units supplied without valves the
bracketed figures near the branches refer
to the component numbers in this list.
These components are to be fitted by the
customer.
0178-085-EN
161
1.
3.
2.
Part No.
162
When ordering spares, please advise the forwarding address, and the address to which
the invoice should be sent. If appropriate,
please state the name of your local bank, the
way in which you want the goods transported
and required delivery date.
4.
Classification certificate
If you require a certificate from a Classification authority, please mark the order
appropriately, as the inspection and issuing
procedures take extra time and incur extra
expenses.
5.
Quotation No.
If a quotation no. has been given during earlier correspondence, please refer to this when
placing your order it will help us to identify
and execute your order quickly.
0178-925-EN
94.05
All compressors are fitted with an identification plate, which states the type and shop no.
of the compressor and indicates what refrigerant is to be used.
Forwarding instructions
0171-466-EN
Shop No.
Compressor block:
0171-945-EN
98.03
0178-085-EN
Safety valve:
Gaskets, cone, O-rings
Oil by-pass system:
Gaskets, teflon ring
Oil pump:
O-rings
S Certificate set of spares:
Further to the parts contained in the standard set of spares this set also includes
spare parts for the below-mentioned components:
Coupling:
Screws and discs
Oil separator:
Sight glass, oil separator element,
heating element
Capacity regulating system:
Solenoid valve
Safety valve:
Spring
Solenoid valves:
Coils
Oil pump:
Shaft seal, filter
163