DATOS GENERALES CARGAS


Empresa Ejecutora
:
Proyecto
:
Localidad
:
Distrito
:
Provincia
:
Departamento
:
Fecha
:
Sistema (V)
:
Tensin base fase SP (V):
Tensin nominal
SP (V):
Factor de potencia (cos ) :

Factor de simultaneidad

RECOMENDACIN:

ELECTRONOROESTE S.A.
Encabezados:
AMPLIACIN DE REDES DE DISTRIBUCIN RP, RS Y AP
NUEVO HORIZONTE - SECTOR B
SULLANA
SULLANA
PIURA
3/30/2016
380/220
3
380
380
RESIDENCIAL:
0.90
C. ESPECIAL:
0.90
ALUMBRADO:
0.85
RESIDENCIAL:
C. ESPECIAL:
ALUMBRADO:

0.50
1.00
1.00

CALCULO DE CAIDA TENSION


SERVICIO PARTICULAR
ALUMBRADO PUBLICO

Frecuencia (Hz) :
AP (V) :
AP (V) :
FACTOR DE CARGA
SP :
AP :

ALIMENTADOR N
SED

60
220
220
0.45
0.50

:
:

N 03

Datos de Cargas residenciales en Lotes :


Potencia y
Factor de Simultaneidad
Carga [ W/lote]
f.s.
Potencia por lote (kW)
Factor de Potencia
Corriente (380 V)

800
0.5
0.4
0.9
0.675

1000
0.5
0.5
0.9
0.844

LOTES DOMESTICOS
C
800
0.5
0.4
0.9
0.675

600
0.5
0.3
0.9
0.506

LOTES
6
6000
1
6.00
0.9
10.129

12
12000
1
12.00
0.9
20.258

E
400
0.5
0.2
0.9
0.338

Datos de Cargas especiales en Lotes :


Potencia y
Factor de Simultaneidad
Carga [ W/lote]
f.s.
Potencia por lote (kW)
Factor de Potencia
Corriente (380 V)

Datos de Iluminacion :
Potencia y
Factor de Simultaneidad
Pot. Lmp. W + Prdidas
f.s.
Potencia por equipo (kW)
Factor de Potencia
Corriente (220 V)

1
1000
1
1.00
0.9
1.688

2
2000
1
2.00
0.9
3.376

3
3000
1
3.00
0.9
5.064

HORAS DE UTILIZACIN x DIA

50 W
58.28
1
0.0583
0.85
0.312

70 W
81.60
1
0.0816
0.85
0.436

4
4000
1
4.00
0.9
6.753

12

LAMPARAS
100 W
150 W
116.57
174.85
1
1
0.11657
0.17485
0.85
0.85
0.623
0.935

8
8000
1
8.00
0.9
13.505

horas

250 W
291.42
1
0.29142
0.85
1.558

16
16000
1
16.00
0.9
27.011

DIAS POR AO

40 W

ELEGIR

1
0
0.85
0.000

1
0
0.85
0.000

DATOS GENERALES CONDUCTORES


Temperatura de trabajo
D1
D2
D3
ALUMINIO
Cobre

:
40
:
200
:
200
:
400
: 0.00403
: 0.00347

C
mm
mm
mm
1/C
1/C

D1
D3
D2

Pgina 1

20
18000
1
18.00
0.9
30.387

365

24
70000
1
70.00
0.9
118.171

Ingresar los Datos solo en las Celdas


de Fuente color Rojo

Datos

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40

PERSONALIZAR CONDUCTORES, INGRESAR CODIGO Y FACTORES DE CAIDAS DE TENSION


Formacin
Factor SP [V/A-km]
factor AP [V/A-km]
3x95+2x10
0.3313208764
2.0371674534
3x70+2x10
0.4124954961
2.0371674534
3x50+2x10
0.5402757592
2.0371674534
3x35+2x10
0.6854230151
2.0371674534

Pgina 2

AMPLIACIN DE REDES DE DISTRIBUCIN RP, RS Y AP


SED :
ALIMENTADOR :
FECHA :

N 03
0
3/30/2016

CALCULO DE CAIDA TENSION


SERVICIO PARTICULAR

RESUMEN :

SISTEMA DE DISTRIBUCION SECUNDARIA

CARGAS RESIDENCIALES
FACTOR DE SIMULTANEIDAD (S.P.)

FACTOR DE POTENCIA

POTENCIA POR LOTE (W/lote)

TENSION NOMINAL (V)

0.50
0.90
590
380

TENSION FASE

TENSION NOMINAL

FRECUENCIA

FACTOR DE CARGA

FACTOR DE PERDIDAS

380 [V]
380 [V]
60 [Hz]
0.45
0.25

CIRCUITO: C-1-I
N
Estructur
a
0
1
2
3
4
5

Servicio Partidular
Punto

Tipo / N Lotes CORRIENTE


A

[A]

Cargas Especiales

POT.

POT. MEDIDA

POT.

[ kW ]

[ kW ]

[ kW ]

[A]

9.45

15.95

N C.E.
1

12

16

18

70

POT.

CORR.

POT.

POT.

Total

Total

[ kW ]

[A]

[ kW ]

[A]

[ kW ]

[A]

0.00

0.00

9.45

15.95

Long.

Tipo y Seccin de

F.C.T.

Cond.
[m]

[mm]

[V/A-km]

PERDIDAS

S.P.

Total

de

Potencia

[V]

[V]

[ kW ]

CAAI - 3x35+1x16+N25

1.543

0.074

0.074

0.02

13.95

30.05 CAAI - 3x35+1x16+N25

1.543

0.647

0.721

0.19

###
###
0.028 ###

10.96

30.58 CAAI - 3x35+1x16+N25

1.543

0.517

1.238

0.33

0.018

4.72

7.97

30.58 CAAI - 3x35+1x16+N25

1.543

0.376

1.614

0.42

0.009

0.00

2.95

4.98

30.58 CAAI - 3x35+1x16+N25

1.543

0.235

1.849

0.49

0.004

0.00

1.18

1.99

30.58 CAAI - 3x35+1x16+N25

1.543

0.094

1.943

0.51

1.99

1.18

0.00

9.45

15.95

0.0

0.00

0.00

0.00

9.45

15.95

2.99

1.77

0.00

8.26

13.95

0.0

0.00

0.00

0.00

8.26

2.99

1.77

0.00

6.49

10.96

0.0

0.00

0.00

0.00

6.49

2.99

1.77

0.00

4.72

7.97

0.0

0.00

0.00

0.00

2.99

1.77

0.00

2.95

4.98

0.0

0.00

0.00

1.99

1.18

0.00

1.18

1.99

0.0

0.00

0.00

32

15.95

9.45

0.51
3.00

155.37

0.004

###
###
0.001 ###
###
0.004 ###

AMPLIACIN DE REDES DE DISTRIBUCIN RP, RS Y AP


SED :
ALIMENTADOR :
FECHA :

N 03
0
3/30/2016

CALCULO DE CAIDA TENSION


SERVICIO PARTICULAR

RESUMEN :

SISTEMA DE DISTRIBUCION SECUNDARIA

CARGAS RESIDENCIALES
FACTOR DE SIMULTANEIDAD (S.P.)

FACTOR DE POTENCIA

POTENCIA POR LOTE (W/lote)

TENSION NOMINAL (V)

CIRCUITO:
C-1-II
N
Servicio
Estructur
Partidular
a
Punto Tipo / N Lotes CORRIENTE
A

0
6
7
8
9

[A]

0.50
0.90
590
380

POT.

POT. MEDIDA

POT.

[ kW ]

[ kW ]

[ kW ]

[A]

8.56

14.45

Car
gas
Esp
eci
ale
N C.E.
s
1
2

TENSION FASE

TENSION NOMINAL

FRECUENCIA

FACTOR DE CARGA

FACTOR DE PERDIDAS

12

16

18

70

380 [V]
380 [V]
60 [Hz]
0.45
0.25

POT.

CORR.

POT.

POT.

Total

Total

[ kW ]

[A]

[ kW ]

[A]

[ kW ]

[A]

0.00

0.00

8.56

14.45

Long.

Tipo y Seccin de

F.C.T.

Cond.
[m]

[mm]

[V/A-km]

PERDIDAS

S.P.

Total

de

Potencia

[V]

[V]

[ kW ]

1.99

1.18

0.00

8.56

14.45

0.0

0.00

0.00

0.00

8.56

14.45

3.00 CAAI - 3x35+1x16+N25

1.543

0.067

0.067

0.02

3.49

2.07

0.00

7.38

12.46

0.0

0.00

0.00

0.00

7.38

12.46

33.00 CAAI - 3x35+1x16+N25

1.543

0.634

0.701

0.18

###
###
0.025 ###

3.49

2.07

0.00

5.31

8.97

0.0

0.00

0.00

0.00

5.31

8.97

32.80 CAAI - 3x35+1x16+N25

1.543

0.454

1.155

0.30

0.013

2.99

1.77

0.00

3.25

5.48

0.0

0.00

0.00

0.00

3.25

5.48

34.00 CAAI - 3x35+1x16+N25

1.543

0.288

1.443

0.38

0.005

2.49

1.48

0.00

1.48

2.49

0.0

0.00

0.00

0.00

1.48

2.49

34.00 CAAI - 3x35+1x16+N25

1.543

0.131

1.573

0.41

0.001

29

14.45

8.56

0.41

136.80

0.003

###
###
###
0.003 ###

AMPLIACIN DE REDES DE DISTRIBUCIN RP, RS Y AP


SED :
ALIMENTADOR :
FECHA :

N 03
0
3/30/2016

CALCULO DE CAIDA TENSION


SERVICIO PARTICULAR

RESUMEN :

SISTEMA DE DISTRIBUCION SECUNDARIA

CARGAS RESIDENCIALES
FACTOR DE SIMULTANEIDAD (S.P.)

FACTOR DE POTENCIA

POTENCIA POR LOTE (W/lote)

TENSION NOMINAL (V)

0.50
0.90
590
380

TENSION FASE

TENSION NOMINAL

FRECUENCIA

FACTOR DE CARGA

FACTOR DE PERDIDAS

380
380
60
0.45
0.25

[V]
[V]
[Hz]

CIRCUITO: C-2
N
Estructura

Servicio Partidular
Punto

Tipo / N Lotes CORRIENTE


A

0
10
11
12
13
14
15
20
21
23
24
25

[A]

Cargas Especiales

POT.

POT. MEDIDA

POT.

[ kW ]

[ kW ]

[ kW ]

[A]

20.66

34.88

N C.E.
1

12

16

18

70

POT.

CORR.

POT.

POT.

Total

Total

[ kW ]

[A]

[ kW ]

[A]

[ kW ]

[A]

0.00

0.00

20.66

34.88

Long.

Tipo y Seccin de

F.C.T.

Cond.
[m]

[mm]

[V/A-km]

PERDIDAS

de

Potencia

[V]

[V]

[ kW ]

1.99

1.18

0.00

20.66

34.88

0.0

0.00

0.00

0.00

20.66

34.88

3.0

CAAI - 3x35+1x16+N25

1.543

0.161

0.161

0.04

0.018

0.00

0.00

0.00

19.48

32.89

0.0

0.00

0.00

0.00

19.48

32.89

13.7

CAAI - 3x35+1x16+N25

1.543

0.693

0.855

0.22

0.071

0.00

0.00

0.00

19.48

32.89

0.0

0.00

0.00

0.00

19.48

32.89

16.2

CAAI - 3x35+1x16+N25

1.543

0.820

1.675

0.44

0.084

1.99

1.18

0.00

19.48

32.89

0.0

0.00

0.00

0.00

19.48

32.89

5.4

CAAI - 3x35+1x16+N25

1.543

0.274

1.949

0.51

0.028

0.00

0.00

0.00

16.23

27.41

0.0

0.00

0.00

0.00

16.23

27.41

30.0

CAAI - 3x35+1x16+N25

1.543

1.269

3.217

0.85

0.108

3.49

2.07

0.00

16.23

27.41

0.0

0.00

0.00

0.00

16.23

27.41

30.0

CAAI - 3x35+1x16+N25

1.543

1.269

4.486

1.18

0.108

1.99

1.18

0.00

14.17

23.92

0.0

0.00

0.00

0.00

14.17

23.92

30.0

CAAI - 3x35+1x16+N25

1.543

1.107

5.593

1.47

0.082

1.49

0.89

0.00

6.20

10.46

0.0

0.00

0.00

0.00

6.20

10.46

20.4

CAAI - 3x35+1x16+N25

1.543

0.329

5.923

1.56

0.011

1.99

1.18

0.00

5.31

8.97

0.0

0.00

0.00

0.00

5.31

8.97

24.3

CAAI - 3x35+1x16+N25

1.543

0.336

6.259

1.65

0.009

1.99

1.18

0.00

3.54

5.98

0.0

0.00

0.00

0.00

3.54

5.98

13.5

CAAI - 3x35+1x16+N25

1.543

0.125

6.383

1.68

0.002

10

2.49

1.48

0.00

2.36

3.99

0.0

0.00

0.00

0.00

2.36

3.99

22.0

CAAI - 3x35+1x16+N25

1.543

0.135

6.519

1.72

0.002

11

1.49

0.89

0.00

0.89

1.49

0.0

0.00

0.00

0.00

0.89

1.49

22.0

CAAI - 3x35+1x16+N25

1.543

0.051

6.569

1.73

0.000

1.949

3.1

1.99

1.18

0.00

2.07

3.49

0.0

0.00

0.00

0.00

2.07

3.49

32.5

CAAI - 3x35+1x16+N25

1.543

0.175

2.124

0.56

0.002

3.2

1.49

0.89

0.00

0.89

1.49

0.0

0.00

0.00

0.00

0.89

1.49

34.0

CAAI - 3x35+1x16+N25

1.543

0.078

2.202

0.58

0.000

6.1

0.00

0.00

0.00

6.79

11.46

0.0

0.00

0.00

0.00

6.79

11.46

30.0

CAAI - 3x35+1x16+N25

1.543

0.531

6.124

1.61

0.019

6.2

1.00

0.59

0.00

6.79

11.46

0.0

0.00

0.00

0.00

6.79

11.46

30.0

CAAI - 3x35+1x16+N25

1.543

0.531

6.654

1.75

0.019

6.3

10

4.98

2.95

0.00

6.20

10.46

0.0

0.00

0.00

0.00

6.20

10.46

22.4

CAAI - 3x35+1x16+N25

1.543

0.361

0.892

0.23

0.012

6.4

11

5.48

3.25

0.00

3.25

5.48

0.0

0.00

0.00

0.00

3.25

5.48

33.9

CAAI - 3x35+1x16+N25

1.543

0.287

0.648

0.17

0.005

6.307

1.66

0.000

8.1

###
###
###
###
###
###
###
###
###

###
###
###

5.593

22

Total

16
17
18
19

1.75

26
27

V
S.P.

6.259
2

1.00

0.59

70

34.88

20.66

0.00

0.59

1.00

0.0

0.00

0.00

0.00

0.59

1.00

31.2

444

CAAI - 3x35+1x16+N25

1.543

0.048

0.579

###
###

R
E
D
E
S
D
E

D
I Loc
S
SED
T
ALIM
R
FECH
I
B
U
RESU
C
IFACTO

FACTO
N
FACTO

AMPLIACIN DE REDES DE DISTRIBUCIN RP, RS Y AP


SED :
ALIMENTADOR :
FECHA :

N 03
0
3/30/2016

CALCULO DE CAIDA TENSION


SERVICIO PARTICULAR

RESUMEN :

SISTEMA DE DISTRIBUCION SECUNDARIA


TENSION FASE
=
380 [V]
TENSION NOMINAL
=
380 [V]
FRECUENCIA
=
60 [Hz]
FACTOR DE CARGA
=
0.45
FACTOR DE PERDIDAS
=
0.25

CARGAS RESIDENCIALES
FACTOR DE SIMULTANEIDAD (S.P.)

FACTOR DE POTENCIA

POTENCIA POR LOTE (W/lote)

TENSION NOMINAL (V)

0.50
0.90
590
380

FACTO

R
% PER
P
,

CIRCUITO: C-2-I
N
Estructura

0
28
29
31
32
33
34
35

Servicio Partidular
Punto

Tipo / N Lotes CORRIENTE

Cargas Especiales

POT.

POT. MEDIDA

POT.

[ kW ]

[A]

[A]

[ kW ]

[ kW ]

15.64

26.41

1.99

1.18

0.00

16.82

1.99

1.18

0.00

1.99

1.18

1.49

0.89

3.99

4.48

10

N C.E.

POT.

CORR.

POT.

POT.

Total

Total

[ kW ]

[A]

[ kW ]

[A]

12

16

18

70

[ kW ]

[A]

0.00

0.00

15.64

26.41

28.40

0.0

0.00

0.00

0.00

16.82

15.64

26.41

0.0

0.00

0.00

0.00

0.00

14.46

24.42

0.0

0.00

0.00

0.00

11.22

18.94

0.0

0.00

0.00

2.36

0.00

10.33

17.44

0.0

0.00

2.66

0.00

7.97

13.45

0.0

0.00

4.98

2.95

0.00

5.31

8.97

0.0

3.99

2.36

0.00

2.36

3.99

0.0

Long.

Tipo y Seccin de

F.C.T.

Cond.

PERDIDAS

S.P.

Total

de

Potencia

[ kW ]

[m]

[mm]

[V/A-km]

[V]

[V]

28.40

3.0

CAAI - 3x35+1x16+N25

1.543

0.131

0.131

0.03

0.012

15.64

26.41

56.4

CAAI - 3x35+1x16+N25

1.543

2.298

2.430

0.64

0.189

0.00

14.46

24.42

32.0

CAAI - 3x35+1x16+N25

1.543

1.206

3.635

0.96

0.092

0.00

11.22

18.94

15.5

CAAI - 3x35+1x16+N25

1.543

0.453

4.088

1.08

0.027

0.00

0.00

10.33

17.44

29.2

CAAI - 3x35+1x16+N25

1.543

0.786

4.874

1.28

0.043

0.00

0.00

7.97

13.45

29.2

CAAI - 3x35+1x16+N25

1.543

0.606

5.480

1.44

0.025

0.00

0.00

0.00

5.31

8.97

29.0

CAAI - 3x35+1x16+N25

1.543

0.401

5.882

1.55

0.011

0.00

0.00

0.00

2.36

3.99

32.0

CAAI - 3x35+1x16+N25

1.543

0.197

6.078

1.60

0.002

1.00

0.002

1.60

30

2.1

R
S
###

Y
A
P

3.635
7

3.49

2.07

53

26.41

15.64

0.00

2.07

3.49

0.0

0.00

0.00

0.00

2.07

3.49

30.0

CAAI - 3x35+1x16+N25

1.543

0.161

3.797

###
256

0.402

R
E
D
E
S
D
E

D
I Loc
S
SED
T
ALIM
R
FECH
I
B
U
RESU
C
IFACTO

FACTO
N
FACTO

AMPLIACIN DE REDES DE DISTRIBUCIN RP, RS Y AP


SED :
ALIMENTADOR :
FECHA :

N 03
0
3/30/2016

CALCULO DE CAIDA TENSION


SERVICIO PARTICULAR

RESUMEN :

SISTEMA DE DISTRIBUCION SECUNDARIA


TENSION FASE
=
380 [V]
TENSION NOMINAL
=
380 [V]
FRECUENCIA
=
60 [Hz]
FACTOR DE CARGA
=
0.45
FACTOR DE PERDIDAS
=
0.25

CARGAS RESIDENCIALES
FACTOR DE SIMULTANEIDAD (S.P.)

FACTOR DE POTENCIA

POTENCIA POR LOTE (W/lote)

TENSION NOMINAL (V)

0.50
0.90
590
380

FACTO

R
% PER
P
,

CIRCUITO: C-2-I
N
Estructura

Servicio Partidular
Punto

Tipo / N Lotes CORRIENTE


A

[A]

Cargas Especiales

POT.

POT. MEDIDA

POT.

[ kW ]

[ kW ]

[ kW ]

[A]

N C.E.
1

12

16

18

70

POT.

CORR.

POT.

POT.

Total

Total

[ kW ]

[A]

[ kW ]

[A]

[ kW ]

[A]

Long.

Tipo y Seccin de

F.C.T.

Cond.
[m]

[mm]

[V/A-km]

PERDIDAS

S.P.

Total

de

Potencia

[V]

[V]

[ kW ]

R
S
Y
A
P