A single area consists of two generating units with the following characteristics

p=600 MVA, p=500MVA, the speed regulation R=6%, R=4%. The units are
operating in parallel, sharing 900 MW at the nominal frequency. Unit one supplies
500MW. Neglect losses and the study state frequency deviation and the new
generation on the each unit?
Select 1000 MWA for the apparent power base

The fuel cost curves for two generation are given as following:
C=500+4*p+0.002*(p)$/h
C=700+6*p+0.003*(p)$/h
Assuming the system is lossless; calculate the dispatch values of p and p for a
total load of 1000 MW, the incremental operating cost, and the total operating cost.

The fuel cost curves for two generation are given as following:
C=400+4*p+0.002*(p)$/h
C=600+6*p+0.003*(p)$/h
Assuming the system is lossless; calculate the dispatch values of p and p for a
total load of 1000 MW, the incremental operating cost, and the total operating cost.

A 250-MW, 60-Hz turbine generator set has a speed regulation of 5 percent based
on its own rating. The generator frequency decreases from 60 Hz to a steady state
value of 59.8 Hz. Determine the increase in the turbine power output.

A 300-MW, 50-Hz turbine generator set has a speed regulation of 4 percent based
on its own rating. The generator frequency decreases from 50 Hz to a steady state
value of 49.8 Hz. Determine the increase in the turbine power output.

The variable operating cost of units for a power system area are:
C=561+7.92*p+0.00156*(p)
C=310+7.85*p+0.00194*(p)
C=78+7.79*p+0.00482*(p)
Determine:
. Power output of each unit,
. Incremental operating cost
. Total operating cost C

$/h
$/h
$/h