Académique Documents
Professionnel Documents
Culture Documents
Address: .......................................................................................................................................................................................
Original Manufacturer: ...............................................................................................................................................................
g. mechanical operation T
V : visual T : test
2. Performance
a. dielectric properties T
Insulation value
Comments / Observation :
Having passed the above tests, the LV switchgear assembly under consideration is in compliance with the Std. IEC 61439-2 (CEI EN 61439-2).
.............................................................................................................................................................................................................................................
.............................................................................................................................................................................................................................................
Customer representative Quality Inspector Quality Manager
Current-carrying capability
Protect against burns by limiting > Temperature rise tests (10.10.2) > Visual inspection
excessive temperatures: > Random verification of tightness
> when any single circuit is > Or comparison with a tested
continuously loaded to its rated reference design, under restrictive
current and conditions
> when any circuit is continuously
loaded to its rated current > Or, under very restrictive
multiplied by its rated diversity conditions, calculations with safety
factor margins (including 20 % derating of
devices)
Protect persons against the fire > Glow wire test (10.2.3.3) > Special None
hazard: resistance to internal test according to IEC TR 61641,
glowing faulty elements, through where specified
selection of materials and various
design provisions