Vous êtes sur la page 1sur 1

Electrical Parameters

Study:

Sequence Impedances Study of Undergorund Cables (MERALCO)

Execution:

3/0AWG 35kV in Underground Ducts (Single Circuit)

Date:

5/5/2011

Description

No
1

Unit

Cable type no

Resistances (DC/AC)
2

DC Resistance of Conductor @ 20C

/km

0.22294

0.22294

0.22294

DC Resistance of Conductor @ Operating Temperature

/km

0.2822

0.28427

0.28311

AC Resistance of Conductor @ 20C

/km

0.22328

0.22328

0.22328

AC Resistance of Conductor @ Operating Temperature

/km

0.28263

0.28469

0.28354

DC Resistance of Sheath @ 20C

/km

DC Resistance of Sheath @ Operating Temperature

/km

DC Resistance of Concentric Wires @ 20C

/km

0.22046

0.22046

0.22046

DC Resistance of Concentric Wires @ Operating Temperature

/km

0.2682

0.27023

0.26909

Losses
10

Conductor Losses

W/m

21.14103

21.14103

21.14103

11

Dielectric Losses

W/m

12

Metallic Screen Losses

W/m

5.6737

5.65518

5.66557

13

Armor/Pipe Losses

W/m

14

Total Losses

W/m

26.81472

26.79621

26.8066

Capacitance, Inductance, Impedance


15

Capacitance

F/km

0.16341

0.16341

0.16341

16

Inductance of Conductor

mH/km

0.73519

0.73519

0.73519

17

Reactance of Conductor

/km

0.27716

0.27716

0.27716

18

Inductance of Metallic Sheath

mH/km

0.44902

0.44902

0.44902

19

Reactance of Metallic Sheath

/km

0.16928

0.16928

0.16928

20

Positive Sequence Impedance

/km

0.28263 +
j0.27716

0.28469 +
j0.27716

0.28354 +
j0.27716

21

Negative Sequence Impedance

/km

0.28263 j0.27716

0.28469 j0.27716

0.28354 j0.27716

22

Zero Sequence Impedance

/km

0.44340 +
j0.16928

0.44340 +
j0.16928

0.44340 +
j0.16928

23

Surge Impedance

67.07412

67.07412

67.07412

Others
24

Dielectric Stress at Conductor Surface

kV/mm

3.63552

3.63552

3.63552

25

Dielectric Stress at Insulation Surface

kV/mm

1.55401

1.55401

1.55401

26

Insulation Resistance @ 20C

M.km

135.26366

135.26366

135.26366

27

Insulation Resistance @ 90C

M.km

1.35264

1.35264

1.35264

28

Reduction factor

0.84565

0.84565

0.84565

29

Charging Capacity of three phase system at Uo

kVAR/km

75.47431

75.47431

75.47431

30

Charging Current for One Phase

A/km

1.24497

1.24497

1.24497

31

Voltage Drop for Three Phase System

V/A/km

0.48953

0.49311

0.4911

32

Induced Voltage on Metallic Sheath

V/km

33

Induced Current on Metallic Sheath (see formula)

145.44727

145.44727

145.44727

0.1

0.1

0.1

Short-Circuit Current
34

Short Circuit Time

35

Non Adiabatic Short Circuit Current of Conductor

kA

33.42297

33.01258

33.24293

36

Non Adiabatic Short Circuit Current of Sheath

kA

34.81308

34.42073

34.64089

37

Non Adiabatic Short Circuit Current of Armour

kA

Vous aimerez peut-être aussi