Vous êtes sur la page 1sur 1

Electrical Parameters

Study:

Sequence Impedances Study of Undergorund Cables (MERALCO)

Execution:

500MCM 35kV in Underground Ducts (Single Circuit)

Date:

5/5/2011

Description

No
1

Unit

Cable type no

Resistances (DC/AC)
2

DC Resistance of Conductor @ 20C

/km

0.07198

0.07198

0.07198

DC Resistance of Conductor @ Operating Temperature

/km

0.09107

0.09179

0.09138

AC Resistance of Conductor @ 20C

/km

0.07305

0.07305

0.07305

AC Resistance of Conductor @ Operating Temperature

/km

0.09243

0.09313

0.09274

DC Resistance of Sheath @ 20C

/km

0.64253

0.64253

0.64253

DC Resistance of Sheath @ Operating Temperature

/km

0.79132

0.79764

0.7941

Losses
8

Conductor Losses

W/m

21.91596

21.91596

21.91596

Dielectric Losses

W/m

10

Metallic Screen Losses

W/m

7.45265

7.39836

7.42869

11

Armor/Pipe Losses

W/m

12

Total Losses

W/m

29.36862

29.31432

29.34466

Capacitance, Inductance, Impedance


13

Capacitance

F/km

0.23768

0.23768

0.23768

14

Inductance of Conductor

mH/km

0.62103

0.62103

0.62103

15

Reactance of Conductor

/km

0.23412

0.23412

0.23412

16

Inductance of Metallic Sheath

mH/km

0.42859

0.42859

0.42859

17

Reactance of Metallic Sheath

/km

0.16157

0.16157

0.16157

18

Positive Sequence Impedance

/km

0.09243 +
j0.23412

0.09313 +
j0.23412

0.09274 +
j0.23412

19

Negative Sequence Impedance

/km

0.09243 j0.23412

0.09313 j0.23412

0.09274 j0.23412

20

Zero Sequence Impedance

/km

0.71452 +
j0.16157

0.71452 +
j0.16157

0.71452 +
j0.16157

21

Surge Impedance

51.11668

51.11668

51.11668

Others
22

Dielectric Stress at Conductor Surface

kV/mm

3.13379

3.13379

3.13379

23

Dielectric Stress at Insulation Surface

kV/mm

1.74697

1.74697

1.74697

24

Insulation Resistance @ 20C

M.km

93.00018

93.00018

93.00018

25

Insulation Resistance @ 90C

M.km

0.93

0.93

0.93

26

Reduction factor

0.97978

0.97978

0.97978

27

Charging Capacity of three phase system at Uo

28

Charging Current for One Phase

29

Voltage Drop for Three Phase System

30

Induced Voltage on Metallic Sheath

31

Induced Current on Metallic Sheath (see formula)

kVAR/km

109.77324 109.77324 109.77324

A/km

1.81074

1.81074

1.81074

V/A/km

0.16009

0.16131

0.16062

V/km

97.04613

96.3087

96.72065

0.1

0.1

0.1

Short-Circuit Current
32

Short Circuit Time

33

Non Adiabatic Short Circuit Current of Conductor

kA

99.41056

98.10297

98.83673

34

Non Adiabatic Short Circuit Current of Sheath

kA

12.36676

12.21353

12.29949

35

Non Adiabatic Short Circuit Current of Armour

kA

Vous aimerez peut-être aussi