EOCR-DS3(T)

Definite Time Type

MCU Based Motor Protection Relay/Digital Overload Relay(-Terminal type)


INTRODUCTION

RELAY FACIA

MCU (Microprocessor Unit) based.


Compact design
Over current /Phase Loss / Phase Reversal /
Locked Rotor Protection
Wide adjustment range up to 1 : 10
Independently adjustable starting period & Trip delay
Visual adjustment aid (LED)
Identify cause of trip (2 LED signals)
Manual/Electrical reset

TYPICAL WIRING DIAGRAM

DIMENSION
DS3

DS3T

EASY TROUBLESHOOTING

ORDERING INFORMATION
EOCR DS3 05 N 220


EOCR : Electronic Overcurrent Relay
Model : DS3
DS3-T(Terminal Type)
Current Range
05 Type : 0.5 - 6A
30 Type : 3 - 30A
60 Type : 5 - 60A
Output Contact condition
N :Normally Energized 97
98 closed when power applied.
96 closed except trip.
R :Normally De-energized 95
Control Power
110 : 85~150VAC 50/60Hz
220 : 180~260VAC 50/60Hz
440 : 320~480VAC 50/60Hz
Terminal Type is optional.

SETTING GUIDE
After completion of wiring, set the values as following instruction :
1. Set starting period to known motor run up time or to the maximum if not known with D-Time knob.
2. Set trip delay to desired trip delay time with O-TIME knob.
3. Start the motor and notice run-up time. then, slowly turn the LOAD knob CCW, until red LED flashes, where the 100%
of the actual load current is indicated. Set the LOAD knob to desired trip current. 110125% setting of running current is
recommended.
4. Readjust D-TIME knob setting to normal motor run-up time.
5. Periodic testing with TEST button is recommended to ensure the full protection and regularly as a preventive maintenance.

PROTECTION
Protective Item
Overcurrent
Phase loss

Operating Characteristics
Trip if 1.1I > Is
(I : Actual Current, Is : Current Setting)
When single phasing occurs.

Trip Delay Time


Preset O-Time Delay
(in accordance with curve)
Within 4 sec

Phase Reversal

Trip instantaneously if Phase Reversal is detected

0.1 sec

Locked Rotor

In case of actual current more than 300% of current setting

Trip just after Preset D-Time Delay

SPECIFICATION
Model
CURRENT SETTING
CURRENT SETTING
CURRENT SETTING
RESET
Time Characteristics
Start-Up Delay
Operating Delay
Trip Indication
Tolerance
Tolerance
Ambient Temperature
Ambient Temperature
Ambient Humidity
Control Voltage
Control Voltage
Output Contacts
Output Contacts
Insulation
Dielectric Strength
Dielectric Strength
Dielectric Strength
Power Concumption
Mounting

EOCR-DS3(T)
TYPE
Ampere Range
05
0.5-6.0A
30
(Standard Type Models)
3.0-30A
60
5.0-60A
Over 60A
05 Type fitted with external CT.
Manual Reset
Manual(instantaneous) reset by depressing RESET button.
Electrical (Remote) Reset
Electrical(instantaneous) reset by interrupting power supply
Definite
D-Time : 1 to 50 sec, Adjustable
O-Time : 0.2 to 10 sec, Adjustable
2 LEDs(power input LED & overload LED)
Current
5%
Time
10%
Storage
-30~80
Operation
-25~70
45~85% RH without Condensation
110
85-150VAC
Voltage
220
180-260VAC
Frequency
50-60Hz
Contacts
2-SPST 5A/250VAC(1a1b)
Condition
96 Open, 97
98 Close.
Normally Energize : 95
Between Casing & Circuits
Over 10 (500VDC Megger)
Between Casing & Circuits
2kV, 50./60Hz, 1min.
Between Contacts
1kV, 50./60Hz, 1min.
Between Circuits
2kV, 50./60Hz, 1min.
Under 1W
35mm DIN rail

VISUAL AID OF LEDS


Visual Adjustment Aid
Ammeter +
Setting Accuracy

With the visual aid of LED, flashing where the current value of adjustment dial (LOAD) is 100% of
actual load current, actual load current can be determined without the aid of ammeter.

2 LEDs make signals and let the operators monitor motor running. If tripping is occurred, the
operator can identify cause of tripping and troubleshoot easily.
The run-up current of motor (starting current) does not cause relay trip because overcurrent protection of EOCR is not applied
by D-Time during motor run-up time.
Trip Cause Indication

Tel +82 2 3473-2340 / Fax +82 2 3473-1159