Output
S-100-24
24Vdc 4.5A
Electrical Specifications:
DC output voltage
Output voltage tolerance
Output Voltage Adjustment Range
Rated output current
Output current range
Ripple and Noise
Line Regulation
Load Regulation
Rated Output Power
Efficiency
AC Input Voltage Range
AC Line Frequency
AC Current (typical)
AC Inrush Current
Leakage Current
Overload Protection
Setup, rise, hold-up time
Isolation Resistance
Withstand Voltage
Working Temp
Working Humidity
Overal Dimension
Weight
Safety Standard
EMC Standard
24Vdc.
1%.
21.6V26.4V
4.5A.
0-4.5A.
100mVp-p.
0.2%.
0.2%.
100W
84%
85-132Vac
180-264Vac
47-63Hz
3.0A/115V
1.5A/230V
30A/115V
60A/230V
<1.0mA/240Vac
135-165%
200,50,20ms
500Vdc/100M
I/P-O/P:3KVAC
I/P-FG:1.5KVAC
O/P-FG:0.5KVAC
-10C - +60C
20% - 90% RH
199x98x38mm
0.65kg
UL1012,
TUVEN60950
FCC part15J class B
Manufactured by:
YOEQING SUNWOR ELECTRIC CO., LTD.
Other Features:
AC Input Range selectable by switch.
Overload Protection type:
Output cutout.
Recovers automatically after
fault condition removed
100% Full Load Burn-in Test.
Installation Issues:
AC Voltage Selector Switch is located inside the
case (below yellow sticker). You will need to insert
small screwdriver thru the hole and move the
switch. No need to remove the cover. Make sure it
is set to correct voltage.
Always connect ground to the Ground terminal.
This way the case will be safe to touch.
Provide adequate air circulation for cooling.
There are two or more terminals labeled
"+" and "-" provided for convenience. All terminals
labeled with the same symbol are internally
connected.
POWER SUPPLY
NOTICE: THIS MODEL FEATURE AC SELECTION SWITCH LOCATED ON PCB UNDER THE
CASE. PLEASE USE SMALL SCREWDRIVER, PASS IT THROUGH HOLES IN THE CASE AND
MOVE THE SWITCH TO CORRECT POSITION MATCHING YOUR AC LINE.
FOR 100 TO 130VAC LINE MOVE THE SWITCH TO 115V.
FOR 200 TO 240VAC LINE MOVE THE SWITCH TO 230V.
AC side connection:
L Live (Hot) - BLACK conductor (USA) or BROWN conductor (International)
N Neutral - WHITE conductor (USA) or BLUE conductor (International)
GND ( or FG or Earth or GND symbol) Ground - GREEN conductor (USA) or
GREEN/YELLOW conductor (International)
DC side connection:
+V positive DC voltage
- V ( or COM) negative DC voltage or COMMON (0V) for asymmetrical or single polarity output