Vous êtes sur la page 1sur 2

Series 852-3xx

Ashridge Engineering Ltd

Transformer
Temperature
Monitor
Specification
Inputs
3 wire PT100, class B
CT's: 0-1 to 0-10A user selectable)
Fans & Pumps CT's or
contact closure
Contact rating: 5A
(Breaking: 110VDC/0.4A)

Environmental:
Temperature range: 0-70 Deg C
Damp Heat to IEC 68-2-30
Power supply:
Universal, 44-265Vac, 44-260Vdc
Power consumption:<10VA
Dimensions:
283 (W) X 216 (H) X 143 (D)
Fixing dimensions:
242 (W) X 177 (H)

The 852-2xx and 852-3xx from Ashridge Engineering


The new 852 range from Ashridge Engineering offers dual display on all models (continuously indicating Top Oil
and Hot Spot temperatures), the 852-2** offers a winding temperature indicator with one or two windings with
multiple output relays for complex cooling systems. The 852-3xx offers a winding temperature indicator with three
windings and multiple output relays for complex cooling systems (** see Models, for correponding type).
Original features only found on the 852 range include full monitoring of Fan and Pump running currents with
'deviation from normal' alarm relay output. 1 to 3 gradient selection, Optional Auto Cool mode, allowing
Cooler exercising at timed intervals between 1 and 30 days plus many other features offering substantial
benefits to the user.
Full isolation is maintained between input and all outputs for maximum system integrity.
All models may be AC or DC powered over an operating range of 44 to 265 Volts AC/DC
Hot Spot oil temperature correction conforms to IEC 354
Many models offered :From One winding with 2 relays through to 3 Windings with 8 relays
852-318 Rev 003, Subject to change without notification

Order codes:
852-116 (Wall mounted) 1 winding, 3 Dig i/ps, single PT100 for oil temperature and 6 relays, 2 analogue o/ps
852-216 (Wall mounted) 2 windings, 3 Dig i/ps, single PT100 for oil temperature and 6 relays, 2 analogue o/ps
852-318 (Wall mounted) 3 windings, 3 Dig i/ps, single PT100 for oil temperature and 8 relays, 4 analogue o/ps

Specification:
Accuracy, resolution: 12 bit, < 0.5% +/-1 Deg C
Analogue outputs: 0-10, 0-20 & 4-20mA (User selectable) with 12 bit resolution. Maximum loop resistance 800W .
CT input: user selectable 1 -10 Amps, +/- 1% @ 20C, (CT = 0.03VA, 1:1000) Overload 75A for 3 secs
Hot Spot Gradient to IEC 354
Relay outputs: 1 off supervisory, plus 6 or 8 (model dependant ) all with N/O or N/C volt free contacts (user selectable
by links).
Relay rating: Contact life (for 1.2x10 5 operations): 5A Non inductive (Breaking: 110Vdc/0.4A, for inductive de-rate
using L/R=7msecs, i.e. approx 0.2A@125VDC).
Environmental: Operating temperature range: 0 to 70C.
Wall mounted enclosure to IP65, Panel mounted enclosure to IP55. Weight: 1.5 & 1.2Kg
Power supply: Universal input, 44-265 Volts ac, 44-260 Volts dc, power consumption less than 6VA.
EMC: Meets the intent of Directive 89/336 and LVD 73/23/ECC, EN61004-16, EN60255-22-1, IEC255-5, EN55022,
EN50081-2, EN55011, EN6100-4-2,
EN6100-4-5 (surge at 4kV for mains connection and 2kV for signals),
EN6100-4-3 (radiated immunity at 10V/metre),
EN6100-4-4 (fast transients 4kV),
EN6100-4-6 (conducted immunity at 10V/metre),
EN6100-4-11, EN6100-4-12 (damped oscillatory wave 2.5kV),
Damp Heat to IEC 68-2-30
Environmental: EN60068-2-2, IEC 255-21-1, IEC 255-21-2 & IEC 68-2-56
Seismic to IEC 255-21-3 (Class 2)
852-2xx Dimensions
214

11

10

105

10

59
852Plus
Wall Mounted
side View

185

126

96

15

16

Manufacturer:

Ashridge Engineering Ltd


West View Road
Okehampton
Devon. UK

852Plus
Wall Mounted
Front View

EX20 1NF
Web: www.ash -eng.co.uk

852-3xx Dimensions
257

11

10

133

216

157

16.5

Agent:
ARGENTINA - Arfin srl
Email: arfin@arfin.com.ar

Dimensions: 241 X 185 X 105 Deep


Fixing dimensions: 3 holes, 198 (W) X 145 (H)

BRAZIL - Tectron Ltda. Email:


Tectronbr@aol.com
10
852
Wall Mounted
Front View

Dimensions: 283 X 216 X 143 Deep


Fixing dimensions: 3 holes, 242 (W) X 177 (H)

70
852
Wall Mounted
side View

Vous aimerez peut-être aussi