Vous êtes sur la page 1sur 41

BOILER FEED PUMP-I

S.NO
1

S.NO
2

S.NO

TAG
11M02BFP1

TAG
11TM02V1

TAG

DESCRIPTION
BFP-1A

INTERLOCK
STOP
Any Motor Winding Temp >120deg [2 sec delay]
Any Motor Bearing Temp > 90deg [2 sec delay]
Any pump bearing temp > 90deg [2 sec delay]
VFC lube oil cooler oil O/L temperatures >60deg [2 sec delay]
VFC working oil I/L >130deg [2 sec delay]
VFC working oil I/L >85deg [2 sec delay]
VFC lube oil cooler oil I/L temperatures >70deg [2 sec delay]
PT-191_1A VFC Lube Oil Pressure >1.7Kg/cm2 Deaerator level low low (< 25%)
Dearator Level Normal value >25%
Suction valve close
Suction Valve Open
Pump suction strainer DP>175 mbar [ 2 Sec delay]
Discharge Valve Close
Any VFC coupling bearing temp>95deg [2 sec delay]
Discharge MOV Bypass Valve Close
Lube oil pressure < 0.8bar PT19.1A
No Stop Interlocks
Local push button stop acted
VFC Scoop Position < 35%
CCW discharge < 2kg/cm2 PT-982
Any motor vibration High High 100um/sec
Any pump vibration High High 80 um/sec
Water leak detector acted
BFP Tripped

DESCRIPTION
VFC-1

AUTO

START
Ready to start from Switch Gear
LPB Stop
PT-982 CCW Discharge Pressure >3.5kg/cm2
VFC Lube Oil pump-1 ON feedback

START

INTERLOCK
START
Ready signal from switchgear
No trip signal
No stop from local panel

DESCRIPTION

AUTO

STOP
BFP-1 running & lube oil pressure >2.9bar [PT-19.2A]
Stop from local panel

START
Lube oil pressure <1.7bar

INTERLOCK
OPEN

AUTO
CLOSE

OPEN

11MOV021034A DISCHARGE BY-PASS MOV

No Trip Signal

No Trip Signal

BFP Running

11MOV021034

No Trip Signal

No Trip Signal
BFP Stopped

BFP Running and BFP DISCHARGE BYPASS MOV OPENED FEEDBACK


BY-Pass Mov Open
ABOVE TWO Feedbacks With 5Sec Delay

DISCHAGE MOV

M/s SUPCON
NAME
SIGNATURE

M/s GREENESOL

M/s MPL

M/s SEPL C&I

STOP

FORCED
START
BFP-2 off signal & BFP-1 in auto mode

STOP

FORCED
START
STOP
Lube oil pressure <1.7bar and BFP-1 running [PT-19.2A]

CLOSE
BFP Stopped
NO BFP running

M/s SEPL OPERATION

FORCED
OPEN

STOP

CLOSE

BOILER FEED PUMP-II


S.NO
1

TAG
11M02BFP2

DESCRIPTION
BFP-1B

INTERLOCK
START
Ready to start from Switch Gear
LPB Stop
PT-982 CCW Discharge Pressure >3.5kg/cm2
VFC Lube Oil pump ON
PT-191 VFC Lube Oil Pressure >1.7Kg/cm2
Dearator Level Normal value >25%
Suction Valve Open
Discharge Valve Close
Discharge MOV Bypass Valve Close
No Stop Interlocks
VFC Scoop Position < 35%

S.NO

TAG

11TM02V2S

S.NO

TAG

DESCRIPTION
VFC-2

INTERLOCK
START
Ready signal from switchgear
No trip signal
No stop from locl panel

DESCRIPTION

STOP
BFP running & lube oil pressure >2.9bar [PT19.2A/PT19.2B]
Stop from local panel

11MOV021035A DISCHARGE BY-PASS MOV


11MOV021035 DISCHAGE MOV

M/s SUPCON
NAME

SIGNATURE

START

STOP

AUTO
START
Lube oil pressure <1.7bar [PT19.2A/PT19.2B]

INTERLOCK
OPEN

AUTO

STOP
Any Motor Winding Temp >120deg [2 Sec Delay]
Any Motor Bearing Temp > 90deg [2 Sec Delay]
Any pump bearing temp > 90deg [2 Sec Delay]
Variable lube oil cooler oil O/L temperatures >60deg [2 Sec Delay]
Variable lube oil cooler oil I/L temperatures >130deg [2 Sec Delay]
Deaerator level low low (< 25%)
Suction valve close
Pump suction strainer DP>175 mbar
Any VFC coupling bearing temp>95deg
Lube oil pressure < 0.8bar PT 19.1B
Local push button stop acted
CCW discharge < 2kg/cm2 PT-982
Any motor vibration High High 100um/sec
Any pump vibration High High 80um/sec
Water leak detector acted
BFP Tripped

AUTO
CLOSE

OPEN

CLOSE
BFP Stopped

No Trip Signal

No Trip Signal

BFP Running

No Trip Signal

No Trip Signal
BFP Stopped

BFP Running
BY-Pass Mov Open
ABOVE TWO Feedbacks With 5Sec Delay

M/s GREENESOL

STOP

M/s MPL

M/s SEPL

C&I

BFP Stop

M/s SEPL OPERATION

FORCED
START
BFP-1 off signal & BFP-1 in auto mode

STOP

FORCED
START
Lube oil pressure <1.7bar and BFP-1 running

STOP

FORCED
OPEN

CLOSE

BARRING GEAR
S.NO

TAG
11BGM02

DESCRIPTION
BARRING GEAR MOTOR

M/s SUPCON
NAME

SIGNATURE

INTERLOCK

AUTO

START
Lube Oil Header Pressure PT128 > 0.35kg/Cm2
Shaft Jacking Oil Pressure PT02J2003 > 80kg/cm2
Turbine Speed < 200RPM from TSI SI-401E

STOP
Lube Oil Header Pressure PT128 < 0.35kg/Cm2
Shaft Jacking Oil Pressure PT02J2003 < 80kg/cm2
Turbine Speed > 200RPM from TSI SI-401E

START

STOP

M/s GREENESOL

M/s MPL

M/s SEPL C&I

M/s SEPL OPERATION

FORCED
START
STOP

AUXILARY OIL PUMP


S.NO

TAG

DESCRIPTION
START

11TM02APS

AUXILARY OIL PUMP

M/s SUPCON
NAME
SIGNATURE

AOP ready Signal


No trip Signal
PUMP LCS PANEL SIGNAL OK
M/s GREENESOL

INTERLOCK
STOP

AUTO
START

Trip Signal
PUMP LCS PANEL SIGNAL NOT OK

M/s MPL

STOP

SWITCH PS63/2-BOP Lube oil pressere LOW


SWITCH PS63/1-BOP Lube oil pressere LOW

M/s SEPL C&I

M/s SEPL OPERATION

FORCED
START
TURBINE TRIP SIGNAL
and
[PS-63/2-BOP Lube oil pressure Low
or
PS-63/1 BOP Lube oil pressure Low]
with 3 Sec Delay

STOP

JACKING OIL PUMP-I


S.NO

TAG

DESCRIPTION
START

11JOP102

JACKING OIL PUMP-1

M/s SUPCON
NAME
SIGNATURE

Lube Oil Header Pressure PT-128 > 0.9kg/cm2


Turbine Speed < 600 rpm fromTSI[SI-401E]

M/s GREENESOL

INTERLOCK
STOP

AUTO
START

Lube Oil Header Pressure PT-128 < 0.9kg/cm2


Turbine Speed > 1200 rpm fromTSI[SI-401E]

M/s MPL

STOP

Shaft Jacking Oil Pressure[PT02J2003]<85kg/cm2


added
Other JOP running
Turbine Speed < 600 rpm from TSI [SI-401E]

M/s SEPL C&I

M/s SEPL OPERATION

FORCED
START

STOP

JACKING OIL PUMP-II


S.NO

TAG

DESCRIPTION
START

11JOP202

JACKING OIL PUMP

M/s SUPCON
NAME
SIGNATURE

Lube Oil Header Pressure PT-128 > 0.9kg/cm2


Turbine Speed < 600 rpm fromTSI[SI-401E]

M/s GREENESOL

INTERLOCK
STOP

AUTO
START

Lube Oil Header Pressure PT-128 < 0.9kg/cm2


Turbine Speed > 1200 rpm fromTSI[SI-401E]

M/s MPL

Shaft Jacking Oil Pressure[PT02J2003]<85kg/cm2


added
Other JOP running
Turbine Speed < 600 rpm fromTSI[SI-401E]

M/s SEPL C&I

AUTO
STOP

M/s SEPL OPERATION

FORCED
START

STOP

EMERGENCY OIL PUMP


S.NO

TAG

DESCRIPTION

START
11EP02S01Emergency Oil Emergency Oil Pump DC Supply Healthy Signal

M/s SUPCON
NAME
SIGNATURE

INTERLOCK
STOP
NO Emergency Oil Pump DC Supply Healthy Signal

Emergency Oil Pump FFR Operated Signal

NO Emergency Oil Pump FFR Operated Signal

Emergency Oil Pump DC Motor Ready Signal


No Trip Signal

Trip Signal

M/s GREENESOL

M/s MPL

AUTO
START
Lube Oil Pressure Switch [PS-63/2 EOP]

STOP

Lube Oil Pressure Switch [PS-63/1 EOP]

M/s SEPL C&I

M/s SEPL OPERATION

FORCED
START
Turbine Trip Signal 1 OUT OF 4
Lube Oil Pressure Switch [PS-63/2 EOP]
or
Lube Oil Pressure Switch[PS-63/1 EOP]

STOP

VACCUM SYSTEM-I
S.NO

TAG

DESCRIPTION
START

INTERLOCK
STOP

AUTO
START

1
11VP01

VACCUM PUMP-1

PUMP READY
LIQUID LEVEL LOW SWITCH
I/L ISOLATION VALVE CLOSE FEEDBACK
NO STOP INTERLOCK

LPB
TRIP SIGNAL
INLET TEMPERATURE SWITCH
BEARING TEMPERATURE HIGH >150deg temp

STOP

Vaccum pump-2 stop FB + Vaccum pump-2


DP switch unhealthy + Exhaust pressure >
-0.5 Kg/cm2 + Vaccum pump-1 in Auto

I/L ISOLATION VALVE CLOSE FB + PUMP RUN FB WITH 15


SEC DELAY
VACCUM RECIRCULATION PUMP ON FB + VACCUM PUMP
ON + O/L FLOW LEVEL SWITCH(FIS) WITH 10sec DELAY

S.NO

TAG

DESCRIPTION
START

S.NO

11VRCP1

TAG

VACCUM RECIRCULATION PUMP-1

INTERLOCK
STOP

PUMP READY
NO TRIP CONDITIION

PUMP TRIP
LPB STOP

NO LPB STOP

VACCUM PUMP-1 ON + VACCUM RECIRCULATION PUMP-1


ON + O/L FLOW SWITCH UNHEALTHY

DESCRIPTION

INTERLOCK

S.NO

11SV02VP1I
TAG

11SV02VP1LMI

VACCUM PUMP I/L ISOLATION VAVLE

SIGNATURE

OPEN

CLOSE

VACCUM PUMP -1 I/L DP SWITCH HEALTHY + VACCUM PUMP ON FB

DESCRIPTION

INTERLOCK

AUTO

OPEN

CLOSE

OPEN

CLOSE

M/s GREENESOL

M/s MPL

M/s SEPL C&I

M/s SEPL OPERATION

VACCUM PUMP LIQUID MAKEUP I/L


ISOLATION VALVE

M/s SUPCON
NAME

STOP

AUTO
CLOSE

OPEN
3

AUTO
START
PUMP IN AUTO MODE + VACCUM PUMP-1 IN
ON WITH 10 Sec DELAY

FORCED
START

STOP

FORCED
START

STOP

FORCED
OPEN
VACCUM PUMP I/L DP SWITCH
HEALTHY

CLOSE

FORCED
OPEN
CLOSE
VACCUM PUMP LIQUID LEVEL LOW VACCUM PUMP LIQUID LEVEL HIGH SWTCH
SWTCH ACTED
ACTED

VACCUM SYSTEM-II
S.NO

TAG

DESCRIPTION

INTERLOCK

AUTO
STOP

START
1
11VM02V2

VACCUM PUMP-2

PUMP READY
LIQUID LEVEL LOW SWITCH
I/L ISOLATION VALVE CLOSE FEEDBACK
NO STOP INTERLOCK

LPB
TRIP SIGNAL
INLET TEMPERATURE SWITCH
BEARING TEMPERATURE HIGH >150deg temp

START

FOR
STOP

START

STOP

START

Vaccum pump-1 stop FB + Vaccum pump-1


DP switch unhealthy + Exhaust pressure >
-0.5 Kg/cm2 + Vaccum pump-1 in Auto

I/L ISOLATION VALVE CLOSE FB + PUMP RUN FB WITH 15


SEC DELAY
VACCUM RECIRCULATION PUMP ON FB + VACCUM PUMP
ON + O/L FLOW LEVEL SWITCH(FIS) WITH 10sec DELAY

S.NO

TAG

DESCRIPTION

INTERLOCK
STOP

START
2

S.NO

11VRCP2

TAG

VACCUM RECIRCULATION PUMP-2

PUMP READY
NO TRIP CONDITIION

PUMP TRIP
LPB STOP

NO LPB STOP

VACCUM PUMP-2 ON + VACCUM RECIRCULATION PUMP-2


ON + O/L FLOW SWITCH UNHEALTHY

DESCRIPTION

INTERLOCK

S.NO
4

11SV02VP2I
TAG

11SV02VP2LMI

VACCUM PUMP I/L ISOLATION VAVLE

SIGNATURE

OPEN

FOR
CLOSE

OPEN
VACCUM PUMP I/L DP SWITCH
HEALTHY

OPEN
VACCUM PUMP LIQUID LEVEL LOW
SWTCH ACTED

VACCUM PUMP -2 I/L DP SWITCH HEALTHY + VACCUM PUMP ON FB

DESCRIPTION

INTERLOCK

AUTO

FOR

OPEN

CLOSE

OPEN

CLOSE

M/s GREENESOL

M/s MPL

M/s SEPL C&I

M/s SEPL OPERATION

VACCUM PUMP LIQUID MAKEUP I/L


ISOLATION VALVE

M/s SUPCON
NAME

FOR

AUTO
CLOSE

OPEN
3

AUTO
START
PUMP IN AUTO MODE + VACCUM PUMP-2 IN
ON WITH 10 Sec DELAY

FORCED
STOP

FORCED
STOP

FORCED
CLOSE

FORCED
CLOSE
VACCUM PUMP LIQUID LEVEL HIGH SWTCH
ACTED

CONDENSATE EXTRACTION PUMP-I


S.NO

TAG

DESCRIPTION

INTERLOCK
START

11M02CEP1

CEP-1

M/s SUPCON
NAME

SIGNATURE

CEP READY
NO LPB
NO TRIP
DISCHARGE VALVE CLOSE
SUCTION VALVE OPEN
NO HOTWELL LEVEL LOW LOW [20%]
NO INTERLOCK STOP
HOTWELL NORMAL >30%
M/s GREENESOL

AUTO
STOP

TRIP
HOTWELL LEVEL LOW LOW [<20%]
MOTOR WINDING TEMPERATURE HIGH >120 deg
MOTOR BEAERING TEMPERATURE HIGH >90 deg
LPB
SUCTION VALVE CLOSE + CEP RUN FB
DISCHARGE VAVLE COLSE + CEP RUN FB [10 sec delay]

M/s MPL

START

FO
STOP

CEP-2 OFF
CEP Discharge Pressure LOW[PS-941]
Hotwell High High[LT-907A,B &C] 85%

M/s SEPL C&I

M/s SEPL OPERATION

START

FORCED
STOP

CONDENSATE EXTRACTION PUMP-II

S.NO

TAG

DESCRIPTION

INTERLOCK
START

11M02CEP2

CEP-2

M/s SUPCON
NAME

SIGNATURE

CEP READY
NO LPB
NO TRIP
DISCHARGE VALVE CLOSE
SUCTION VALVE OPEN
NO HOTWELL LEVEL LOW LOW < 20%
NO TRIP INTERLOCK
Hotwell Level Normal > 30%

M/s GREENESOL

AUTO
STOP

TRIP
HOTWELL LEVEL LOW LOW
MOTOR WINDING TEMPERATURE HIGH >120 deg
MOTOR BEAERING TEMPERATURE HIGH >90 deg
LPB
SUCTION VALVE CLOSE + CEP RUN FB
DISCHARGE VAVLE COLSE + CEP RUN FB

M/s MPL

START

STOP

CEP-1 OFF FB
CEP DISCHARGE HEADER PRESSURE LOW[PS-941]
HOTWELL LEVEL HIGH HIGH

M/s SEPL C&I

M/s SEPL OPERATION

FORCED
START

STOP

CLOSED CIRCUIT COOLING WATER-I


S.NO
1

TAG
11M02CCW1

DESCRIPTION
CLOSED CIRCUIT COOLING WATER(CCCW)-1

INTERLOCK
START
START READY
NO TRIP FEEDBACK
NO LPB STOP
COMMON SURGE TANK LEVEL > 25% [LT901A]

M/s SUPCON
NAME

SIGNATURE

M/s GREENESOL

AUTO

STOP
COMMON SURGE TANK LEVEL < 25% [LT901A]
MOTOR WINDING TEMP > 120deg
MOTOR BEARING TEMP >90deg
MOTOR SUCTION DIFFERENTIAL PRESSURE HIGH [DPT-945]
LPB STOP
TRIP FEEDBACK

M/s MPL

START

M/s SEPL C&I

AUTO
STOP

M/s SEPL OPERATION

FORCED
START
STOP

CLOSED CIRCUIT COOLING WATER-II


S.NO
1

TAG
11M02CCW2

DESCRIPTION
CLOSED CIRCUIT COOLING WATER(CCCW)-2

M/s SUPCON
NAME

SIGNATURE

INTERLOCK

AUTO

STOP
START READY
COMMON SURGE TANK LEVEL < 25% [LT-901A]
NO TRIP FEEDBACK
MOTOR WINDING TEMP > 120deg
NO LPB STOP
MOTOR BEARING TEMP >90deg
COMMON SURGE TANK LEVEL > 25% [LT-9MOTOR SUCTION DIFFERENTIAL PRESSURE HIGH[DPT-946]
LPB STOP
TRIP FEEDBACK
START

M/s GREENESOL

M/s MPL

START

M/s SEPL C&I

AUTO
STOP

M/s SEPL OPERATION

FORCED
START
STOP

S.NO

TAG

DESCRIPTION

11TM02SO

START UP OILPUMP

M/s SUPCON
NAME
SIGNATURE

START UP OIL PUMP


INTERLOCK
START
READY SIGNAL
NO Trip Signal
No LCS Stop PB

M/s GREENESOL

START UP OIL PUMP


INTERLOCK
STOP
Trip Signal
TurbineSpeed > 3000 rpm[3 Sec Delay]
LCS Stop PB

M/s MPL

AUTO
START
MOP[Main OilPumpOulet pressure < 1.27 Mpa [PT-126]
TurbineSpeed< 2800 rpm [SI401E]

M/s SEPL C&I

STOP

M/s SEPL OPERATION

FORCED
START

STOP

S.NO

TAG

DESCRIPTION

11TM02H1S

HOT CONDENSATE WATER PUMP-1

M/s SUPCON
NAME
SIGNATURE

HOT CONDENSATE WATER PUMP-1


INTERLOCK
START
PUMP READY SIGNAL
NO Trip Signal
LP HEATER-1 LEVEL LOW SW-LS-906
NO LCS Stop PB
LP HEATER-1 LEVEL NOT < 15% [ LT-904]
M/s GREENESOL

NDENSATE WATER PUMP-1


INTERLOCK
STOP
LP HEATER-1 LEVEL LOW SW-LS-906
LP HEATER-1 LEVEL < 15% [ LT-904]
LCS Stop PB

M/s MPL

AUTO
START
LP HEATER-1 LEVEL < 80% [ LT-904]
LP HEATER-1 LEVEL HIGH SW-LS-907
HOT CONDENSATE PUMP-2 OFF Feedback

M/s SEPL C&I

STOP

M/s SEPL OPERATION

FORCED
START

STOP

S.NO

TAG

DESCRIPTION

11TM02H2S

HOT CONDENSATE WATER PUMP-2

M/s SUPCON
NAME
SIGNATURE

HOT CONDENSATE WATER PUMP-2


INTERLOCK
START
PUMP READY SIGNAL
NO Trip Signal
LP HEATER-1 LEVEL LOW SW-LS-906
NO LCS Stop PB
LP HEATER-1 LEVEL NOT < 15% [ LT-904]
M/s GREENESOL

NDENSATE WATER PUMP-2


INTERLOCK
STOP
LP HEATER-1 LEVEL LOW SW-LS-906
LP HEATER-1 LEVEL < 15% [ LT-904]
LCS Stop PB

M/s MPL

AUTO
START
LP HEATER-1 LEVEL < 80% [ LT-904]
LP HEATER-1 LEVEL HIGH SW-LS-907
HOT CONDENSATE PUMP-1 OFF Feedback

M/s SEPL C&I

STOP

M/s SEPL OPERATION

FORCED
START

STOP

Vous aimerez peut-être aussi