Vous êtes sur la page 1sur 3

TECHNICAL PARTICULAR GUARANTEE

TPG 06.c : PHBTM BUS VT, LA


DESCRIPTION

NO

UNIT

PLN REQUIRED

PROPOSED AND GUARANTEE

A.

20 KV SWITCHGEAR

Manufacturer

to be mentioned

Indonesia

Type

to be mentioned

Simoprime A4

Branded / Pabrikasi
3

Type of designation (tempat pemasangan dan konfigurasi busbar)

. / .

Siemens / Indonesia

Indoor metal clad and single busbar

Indoor metal clad and single busbar

IEC 62271-200

IEC 62271-200

Standard

Rated voltage (Ur)

kV

24

24

Rated lightning impuls withstand voltage (Up)

kV

125

125

Rated power frequency withstand voltage (Ud)

kV

50

50

Rated frequency

Hz

50

50

Rated normal current


-

Main busbar

2000

2000

VT/LA busbar

630

1250
25

10

Rated short-time withstand current ( I k )

kA

25

11

Rated duration of short circuit

sec.

12

Rated peak withstand current ( I p )

kA

2,5 x I k

63

13

Degrees of protection (IP)

Minimum IP 4X

IP 4X

14

Insulation medium

air

air

15

Busbar system :
-

Material

Copper with heatshrink

Yes (Main Busbar only)

Main busbar at upper side

mm2

to be mentioned

2 x 10 x 100

Terminal for Busbar Cable at lower side

mm2

to be mentioned

80 x 10

Earthing busbar

mm2

to be mentioned

10 x 30

16

Number of phase busbar

17

Auxiliary supply
-

Rated supply voltage of closing and opening devices

Vdc

110

110

Rated supply voltage of control circuit (aux, relay)

Vdc

110

110

Rated supply voltage of auxiliary (heater)

Vac

230

230

LSC2B

LSC2B

AFLR 25

AFLR 25

18

Loss of service continuity catagory (LSC)

19

Internal arc classification (IAC)

Unrestricted

Name of Bidder

kA-1sec

Signed of Bidder

Page 1 of 3

TECHNICAL PARTICULAR GUARANTEE


TPG 06.c : PHBTM BUS VT, LA
DESCRIPTION

NO
20

21

UNIT

PLN REQUIRED

PROPOSED AND GUARANTEE

Minimum thickness of steel sheet :


-

front panel for relay, energy meter and others mounted

mm

2.5

2.5

other section

mm

refer to IAC complied

2 mm (1.5 mm for LV box and Shutter)

Dimension of switchgear cubicle :


-

width

mm

to be mentioned

800

depth

mm

to be mentioned

1900

height

mm

to be mentioned

2728

set

to be mentioned (power and range temperature)

Heater 100W and 0-60


Trafoindo

22

Heater with temperature control

B.

20 KV VOLTAGE TRANSFORMER

Manufacturer

to be mentioned

Type

to be mentioned

VTB-24

Standard

IEC 60044-2

IEC 60044-2

Type of design

Indoor

Indoor

Rated voltage (Ur)

Minimum Rated voltage factor

Rated Frequency

Ratio, class, rated output :


a.

kV

24

24

1,2 Continuous and 1,9 - 30 s

1,2 Continuous and 1,9 - 30 s

Hz

50

50

- ratio

20.000:3 / 100:3

20.000:3 / 100:3

- class

0.2

0,2

VA

30

30

- ratio

20.000:3 / 100:3

20.000:3 / 100:3

- class

3P

3P

VA

25

25

for metering

- burden
b.

for protection

- burden
9

Rated lightning impulse withstand voltage (Up)

kV

125

125

10

Power frequency withstand voltage (Ud)

kV

50

50

C.

DISCONNECTOR SWITCH

Manufacturer

To be mentioned

Type

To be mentioned

Unrestricted

Name of Bidder

VT with Withdrwable

Signed of Bidder

Page 2 of 3

TECHNICAL PARTICULAR GUARANTEE


TPG 06.c : PHBTM BUS VT, LA
DESCRIPTION

NO
4

Standard

UNIT

PLN REQUIRED

PROPOSED AND GUARANTEE

IEC 60265

Rated voltage

kV

24

Rated nominal current

630

Rated lightning impuls withstand voltage

kV

125

Rated short-time withstand current (Ik)

kA

25

10

Making capacity

kA

2,5 x Ik

11

Rated frequency

Hz

12

Interrupting medium

13

Mechanism type

14

Mechanical endurance

M2 (5.000 times)

D.

PROTECTION RELAY

Lihat Spesifikasi Protection Relay (TPG)

Under Frequncy relay (81U)

Included in 7RW80

Under Voltage relay (27)

Included in 7RW80

Port communication comply to IEC 61850

E.

TEST PLUG FOR PROTECTION RELAY AND METERING

Manufacturer

To be mentioned

Fuji

Type

To be mentioned

KTQ-A4H AG & KTQ-V4H AG

Type of designation

Banana plug

Yes

To be mentioned

Siemens

50
SF6 or Vacuum
manual
7RW80

optical port

F.

FUSE

F.1

FUSE-BASE

Manufacturer

Rated voltage

kV

24

24

Rated current

100

100

To be mentioned

Siba

Indoor, limiting current

Yes

F.2

FUSE-LINK

Manufacturer

Type of designation

Rated voltage

kV

24

24

Rated current

6,3

Unrestricted

Name of Bidder

Signed of Bidder

Page 3 of 3