The document contains input parameters for calculating heat transfer through an insulated pipe, including insulation thickness, fluid properties, pipe geometry and material properties, mass flow rate, and inlet/outlet temperatures. The calculation determines the outlet temperature is 399.966867 °C given an inlet of 400.0 °C, ambient temperature of 23.8 °C, and other specified parameters.
The document contains input parameters for calculating heat transfer through an insulated pipe, including insulation thickness, fluid properties, pipe geometry and material properties, mass flow rate, and inlet/outlet temperatures. The calculation determines the outlet temperature is 399.966867 °C given an inlet of 400.0 °C, ambient temperature of 23.8 °C, and other specified parameters.
Droits d'auteur :
Attribution Non-Commercial (BY-NC)
Formats disponibles
Téléchargez comme XLS, PDF, TXT ou lisez en ligne sur Scribd
The document contains input parameters for calculating heat transfer through an insulated pipe, including insulation thickness, fluid properties, pipe geometry and material properties, mass flow rate, and inlet/outlet temperatures. The calculation determines the outlet temperature is 399.966867 °C given an inlet of 400.0 °C, ambient temperature of 23.8 °C, and other specified parameters.
Droits d'auteur :
Attribution Non-Commercial (BY-NC)
Formats disponibles
Téléchargez comme XLS, PDF, TXT ou lisez en ligne sur Scribd
Average Heat Capacity of Fluid= 2.570 KJ/kg K Fluid Viscosity= 5.200 cP The Chemical Engineers' Resource Page Thermal cond of Fluid= 0.600 W/m K Thermal cond of Pipe= 30.000 W/m K Pipe R1= 0.020 m R2= 0.026 m R3= 0.526 m Mass Flow= 350000.000 kg/h Ax pipe= 0.001 m^2 R1 Transfer Coefficient Outside Pipe= 50.000 W/m^2 K R2 Heat Transfer Coefficient in Pipe= 40394.425 W/m^2 K Overall Heat Transfer Coefficient= 0.044 W/m^2 K R3 Thermal cond of insulation= 0.070 W/m K Length of pipe= 150.000 m Inlet Temperature of Pipe (T1)= 400.000 0C Ambient Temperature= 23.800 0C Unit 1 T1 T2 Unit 2