HYDRAULIC CALCULATIONS AT SPECIFIED FLOW

THE FOLLOWING SPRINKLERS ARE OPERATING IN:


[ ] TEST AREA 1 [ ] TEST AREA 2 [ ] TEST AREA 3 [ ] REMOTE AREA

Elevation of sprinklers = Elevation above water test.

REF. PT. K ELEV. FLOW PRESSURE


m lpm bars

201 204.80 8.73 398.68 3.82


202 204.80 8.73 398.34 3.81
203 204.80 8.73 398.37 3.81
204 204.80 8.73 398.75 3.82
205 204.80 8.73 397.34 3.79
206 204.80 8.73 396.97 3.79
207 204.80 8.73 397.00 3.79
208 204.80 8.73 397.31 3.79
209 204.80 8.00 402.50 3.89
210 204.80 8.00 402.06 3.88
211 204.80 8.00 401.98 3.88
212 204.80 8.00 402.44 3.89

THE SPRINKLER SYSTEM FLOW IS 4791.74 lpm

THE OUTSIDE HOSE FLOW AT REFERENCE POINT N0. 1 IS 0.00 lpm


[ ] THE INSIDE HOSE [ ] RACK SPKLR'S.
[ ] YARD HYDT. FLOW IS 0.00 lpm
THE FOLLOWING PRESSURES & FLOWS OCCUR
---> AT REF. PT. 1 <---

STATIC PRESSURE 8.00 bars


RESIDUAL PRESSURE 7.00 bars AT 4800.00 lpm
TOTAL SYSTEM FLOW 4791.74 lpm
AVAILABLE PRESSURE 7.00 bars AT 4791.74 lpm
OPERATING PRESSURE 5.33 bars AT 4791.74 lpm
PRESSURE REMAINING 1.67 bars
PAGE 2

FITTING LEGEND
'-' Indicates Equivalent Length. 'T' Indicates Threaded Fitting
1=45 Elbow, 2=90 Elbow, 3='T'/Cross, 4=Butterfly Valve, 5=Gate Valve, 6=Swing Check Valve
=============================================================================================
FROM TO FLOW PIPE FITS EQV. H-W PIPE DIA. FRIC. ELEV. FROM TO DIFF
(lpm) (m.) (m.) C TYPE (mm) (b/m) (bars) (bars) (bars) (bars)

1 2 4791.74 1.50 45 10.14 120 301 205.010 0.003 0.147 5.33 5.15 0.04
2 3 4791.74 6.50 3 11.36 120 301 205.010 0.003 0.637 5.15 4.46 0.05
3 9 4791.74 20.82 2 5.68 120 301 205.010 0.003 0.000 4.46 4.38 0.08
9 10 4275.61 3.30 0 0.00 120 201 155.320 0.010 0.000 4.38 4.34 0.03
10 11 3825.57 3.30 0 0.00 120 201 155.320 0.008 0.000 4.34 4.32 0.03
11 12 3390.48 3.30 0 0.00 120 201 155.320 0.006 0.000 4.32 4.30 0.02
12 13 2916.33 3.30 0 0.00 120 201 155.320 0.005 0.000 4.30 4.28 0.02
13 14 2403.70 3.30 0 0.00 120 201 155.320 0.003 0.000 4.28 4.27 0.01
14 15 1622.39 3.30 0 0.00 120 201 155.320 0.002 0.000 4.27 4.27 0.00
15 16 816.90 3.30 0 0.00 120 201 155.320 0.000 0.000 4.27 4.27 -0.00
17 18 516.13 3.30 0 0.00 120 201 105.140 0.001 0.000 4.15 4.15 0.00
18 19 966.17 3.30 0 0.00 120 201 105.140 0.004 0.000 4.15 4.13 0.01
19 20 1401.26 3.30 0 0.00 120 201 105.140 0.008 0.000 4.13 4.11 0.03
20 21 1875.41 3.30 0 0.00 120 201 105.140 0.014 0.000 4.11 4.06 0.05
21 22 2388.04 3.30 0 0.00 120 201 105.140 0.022 0.000 4.06 3.99 0.07
22 23 1575.21 3.30 0 0.00 120 201 105.140 0.010 0.000 3.99 3.95 0.03
23 24 792.09 3.30 0 0.00 120 201 105.140 0.003 0.000 3.95 3.95 0.00
9 17 516.13 38.34 33 9.52 120 201 80.680 0.005 0.000 4.38 4.15 0.22
10 18 450.04 39.80 2233 14.27 120 201 80.680 0.004 0.000 4.34 4.15 0.20
11 19 435.10 39.80 2233 14.27 120 201 80.680 0.003 0.000 4.32 4.13 0.18
12 20 474.15 38.34 33 9.52 120 201 80.680 0.004 0.000 4.30 4.11 0.19
13 21 512.62 38.34 33 9.52 120 201 80.680 0.005 0.000 4.28 4.06 0.22
14 201 781.31 30.70 32 7.13 120 201 80.680 0.010 0.072 4.27 3.82 0.38
201 202 382.63 2.40 0 0.00 120 201 80.680 0.003 0.000 3.82 3.81 0.01
202 203 -15.71 2.40 0 0.00 120 201 80.680 0.000 0.000 3.81 3.81 -0.00
203 204 -414.07 2.40 0 0.00 120 201 80.680 0.003 0.000 3.81 3.82 -0.01
204 22 -812.82 1.90 23 7.13 120 201 80.680 0.011 -0.072 3.82 3.99 -0.10
15 205 805.50 30.70 32 7.13 120 201 80.680 0.011 0.072 4.27 3.79 0.40
205 206 408.15 2.40 0 0.00 120 201 80.680 0.003 0.000 3.79 3.79 0.01
206 207 11.18 2.40 0 0.00 120 201 80.680 0.000 0.000 3.79 3.79 -0.00
207 208 -385.82 2.40 0 0.00 120 201 80.680 0.003 0.000 3.79 3.79 -0.01
208 23 -783.13 1.90 23 7.13 120 201 80.680 0.010 -0.072 3.79 3.95 -0.09
16 209 816.90 29.97 3 4.76 120 201 80.680 0.011 0.000 4.27 3.89 0.38
209 210 414.40 2.40 0 0.00 120 201 80.680 0.003 0.000 3.89 3.88 0.01
210 211 12.33 2.40 0 0.00 120 201 80.680 0.000 0.000 3.88 3.88 0.00
211 212 -389.65 2.40 0 0.00 120 201 80.680 0.003 0.000 3.88 3.89 -0.01
212 24 -792.09 1.17 3 4.76 120 201 80.680 0.010 0.000 3.89 3.95 -0.06

A MAX. VELOCITY OF 4.58 m/sec OCCURS BETWEEN REF. PT. 21 AND 22


PAGE 3

FITTING LEGEND
'-' Indicates Equivalent Length. 'T' Indicates Threaded Fitting
1=45 Elbow, 2=90 Elbow, 3='T'/Cross, 4=Butterfly Valve, 5=Gate Valve, 6=Swing Check Valve
=============================================================================================
FROM TO FLOW PIPE FITS EQV. H-W PIPE DIA. FRIC. ELEV. FROM TO DIFF
(lpm) (m.) (m.) C TYPE (mm) (b/m) (bars) (bars) (bars) (bars)

Sprinkler-CALC Release 7.2 Win


By Walsh Engineering Inc.
North Kingstown R.I. U.S.A.
H Y D R A U L I C C A L C U L A T I O N S

C O V E R S H E E T

W A T E R S U P P L Y

STATIC PRESSURE (bars) 8


RESIDUAL PRESSURE (bars) 7
RESIDUAL FLOW (lpm) 4800

B O O S T E R P U M P S

NUMBER OF BOOSTER PUMPS 0

S P R I N K L E R S

MINIMUM FLOW PER SPRINKLER (lpm) 397

MINIMUM PRESSURE PER SPRINKLER (bars) 3.79

THIS SYSTEM OPERATES AT A FLOW OF 0.00 lpm AT A PRESSURE OF 0.00 bars


AT THE BASE OF THE RISER (REF. PT. 0)

PIPES USED FOR THIS SYSTEM


======================================
301 CAST IRON FLANGED BS 2035 CLASS `C`
201 STEEL BS 1387 MEDIUM