Vous êtes sur la page 1sur 1

1 2 3 4 5 6

EXST
REMOTE
[B3] [B3] (NOTE 6) [A3] (NOTE 10) CP (NOTES 4 AND 5) (NOTES 4 & 5)
P17-1001 M

[C2]

[B3] (NOTE 10)


EXST
VFD17-1001
[B36]
F18-1001 M MCC-2A

A
N

[C8] [C12]
c CH2M HILL 2009. ALL RIGHTS RESERVED.

APVD

CP17-1001 J
I. DOLAK

BY

[2"C, 36#14, 1#14G]


APVR

[C2]
SV17-2036

[C3]
HS18-1001 CS
APVD

[C12]
[B3] [B3] (NOTE 6)
[C2]
P17-1002 M

[C2]
J [8#14]
A.SODEIFI

(NOTE 1)
[C12]
J

EXST EXST
[B36]
CHK

PB-17-2 PB-17-3
F18-1002 M J
[C8] [C12]
REVISION

CP17-1002 J
DESCRIPTION

[C2]
SV17-2037 (NOTES 4 & 5)
[C3]
HS18-1002 CS
S. KORCSMAROS

DR

B
[B3] [B3] (NOTE 6) [B3] (NOTE 10) [C2]
EXST
P17-1003 M VFD17-1002

[C2] DCU-2
D.DOAR

DATE
DATE

(NOTES 4 AND 5)
NO
NO.
DSGN

[C8] [C12]
CP17-1003 J
[C12] [A1]
DPIT18-1001

[C2] EXST
J
SV17-2038 [B3] (NOTE 10) VFD17-1003
T

[A1]
R IC

DPIT18-1002
A D
RO
DIST

(NOTES 4 & 5)
N
I ON

[A3] PB-05-1
PT O
TAT

AM
NI

CABLE BLOCK DIAGRAM CBD-18-1


THIS DOCUMENT, AND THE IDEAS AND DESIGNS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS THE PROPERTY OF
CH2M HILL AND IS NOT TO BE USED, IN WHOLE OR IN PART, FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF CH2MHILL.

FE17-1410
H
SA

(1 REQUIRED)
IMPROVEMENTS - PHASE 1

[C1]
JAMES RIVER TREATMENT PLANT

C [B2] [C2]
FIT17-1410 TSH14-100XA

[A1]
NOTES:
[C2]
REUSE OF DOCUMENTS:

YS14-100X
1. THESE CONDUCTORS ARE INCLUDED IN THE DISCRETE (24 VDC) SIGNAL CONDUCTOR QUANTITIES
SHOWN IN THE DISCRETE (24 VDC) SIGNAL CONDUITS BETWEEN THE MCCS AND THE RIOS/DCUS
ON THE PLANS.
FE17-1420
[C2] CP14-100X
TSH14-100XB 2. THESE CONDUCTORS ARE INCLUDED IN THE CONDUCTOR QUANTITIES SHOWN IN THE CONDUITS
[C1] BETWEEN THE ANALOG AND 24 VDC WIREWAY AND THE RIOS/DCUS ON THE PLANS.
[B2] [B6] EXST
FIT17-1420 120V 3. SEE THE CIRCUIT SCHEDULE ON DRAWINGS E-21 AND E-22 AND DUCT BANK SECTIONS AA, BB,
J [B2]
PANEL AND CC, ON DRAWINGS SE-5 AND SE-6 FOR CONDUCTOR QUANTITIES AND DESTINATION DETAILS
B14-XXXX CT
FOR THESE CONDUCTORS AND CONDUITS.
[A1] (NOTE 11)
J 4. SEE THE CONCRETE ENCASED CONDUIT SECTIONS ON DRAWING SE-4 FOR ROUTING DETAILS.

5. SEE CIRCUIT SCHEDULE ON DRAWINGS E-21 AND E-22.


ELECTRICAL

FE17-1430 6. ROUTE ALL POWER CONDUCTORS FROM VFDS TO MOTORS IN DEDICATED PVC COATED
GALVANIZED RIGID STEEL CONDUITS.
[C1]
TSHXX-XXXX TSHYY-YYYY YSHXX-XXXX B14-XXXX
[B2] 7. PROVIDE ADDITIONAL JUNCTION BOXES AND PULLBOXES TO SUIT CIRCUIT ROUTING.
FIT17-1430
8. THE DEVICES CONDUIT, CONDUCTORS AND JUNCTION BOXES SHOWN INSIDE THE DASH LINES
CABLE BLOCK DIAGRAMS

TSH14-1001A TSH14-1001B YSH14-1001 B14-1001 ARE FUTURE. PROVIDE CAPPED CONDUIT IN NOTE 9.
[A1]
D
TSH14-1002A TSH14-1002B YSH14-1002 B14-1002 9. CAP EMPTY CONDUIT FOR FUTURE DEVICES. TERMINATE CONDUIT ON WALKWAY CONDUIT RACK
NEAR FUTURE DEVICE LOCATION.
TSH14-1003A TSH14-1003B YSH14-1003 B14-1003

10. ROUTE THROUGH EXISTING CONDUIT.

11. PROVIDE 2-20 A, 1 POLE CIRCUIT BREAKERS IN EXISTING SPACES AND CONNECT TO FIT17-1410 VERIFY SCALE
AND FIT17-1420. CONNECT FIT17-1430 TO EXST CB.
CABLE BLOCK DIAGRAM CBD-17-2 BAR IS ONE INCH ON
ORIGINAL DRAWING.
(1 REQUIRED) 0 1"

DATE FEBRUARY 2009


CABLE BLOCK DIAGRAM CBD-14-2
(3 REQUIRED) PROJ 363254

DWG E-14

SHEET 123

FILENAME: $FILENAME PLOT DATE: $PLOTDATE PLOT TIME: $PLOTTIME