PI/SQF/CCL/CT/433

COMMISSIONING TEST REPORT


Pages: 1 of 2
FOR CURRENT TRANSFORMER
Date: 14.09.2007

Client : M\S SAINT GOBAIN


Location :
Equipment
: APFC PROTECTION CT
Details
J.B.ELECTRONICS,MUMBAI.
Make & Sr. No. :
R – 10/9/2181
Ratio : 1X4000/5A

Burden 15 VA

Class 1

OUTDOOR / INDOOR INSTALLATION: INDOOR

I. Insulation Resistance Measurement : ( Values in MΩ ) Minimum Value : 1 MΩ /KV


Instrument used : 500V Megger Make:CIE 444 Temperature : __35___ °C
Sr. No: 60380,

R-Ph
Primary -Earth >100MΩ
Primary - Secondary >100MΩ
Secondary -Earth >100MΩ

II. Polarity Check :


Test set up with P1 +ve P2 -ve
S1 should show +ve kick with respect to S2

Result Core 1
R-Ph OK

III. Winding Resistance Measurement (Acceptable Value +/-2% of mfg Test Report Value)

Reff R Phase
Core 1 0.49Ω
Tested By : Witnessed by :

Siemens Ltd.

Date :

SIEMENS LTD. Dept./Ref. No. PI Ref :

Office
PI/SQF/CCL/CT/433
COMMISSIONING TEST REPORT
Pages: 2 of 2
FOR CURRENT TRANSFORMER
Date: 14.09.2007

IV. Primary Injection Test : Accepted value : ± 10% of calculated value


This is being done to ensure that there is no transit damage. Current selected shall be max.
100A or Rated current whichever is lower.

Secondary
Primary Current Amp Current Amp
CORE 1
R- Ph
200
0.22
400
0.47
800 0.97

CT found healthy : YES

Tested By : Witnessed by :

Siemens Ltd.

Date :

SIEMENS LTD. Dept./Ref. No. PI Ref :

Office