LINE LOSS COMPARISON - CO2 VS NH3

WET SUCTION LINE - MAIN PIPE + BRANCH SECTION FOR AIR COOLER

CO2 (R744) NH3 (R717)


LENGTH
ANSI [DN] DT [°K] DT ACCU [°K] ANSI [DN] DT [°K] DT ACCU[°K] Remarks
MAIN WET SUCTION LINE [m]

Section 1 - 943 kW 30 150 0.028 0.028 300 0.134 0.134 Ref. Danfoss report

Section 2 - 813 kW 24 150 0.069 0.097 250 0.095 0.229 Ref. Danfoss report

Section 3 - 683 kW 24 150 0.051 0.148 250 0.071 0.300 Ref. Danfoss report

Section 4 - 573 kW 18 125 0.068 0.216 200 0.117 0.417 Ref. Danfoss report

Section 5 - 463 kW 18 100 0.132 0.348 150 0.283 0.700 Ref. Danfoss report

Section 6 - 354 kW 18 100 0.082 0.430 150 0.174 0.874 Ref. Danfoss report

Section 7 - 244 kW 18 80 0.155 0.585 125 0.220 1.094 Ref. Danfoss report

Section 8 - 122 kW 18 65 0.128 0.713 100 0.194 1.288 Ref. Danfoss report

Sum 168 0.713 1.288

WET SUCTION - BRANCH

Air cooler - Room 1 (61.2 kW) 50 0.177 65 1.090 Ref. Danfoss report

TOLAL LINE LOSS 0.890 2.378

• Evaporating temp. = -32°C

• Circulation rate = 4
CO2 - PROPOSED DIMENSIONS FOR WET SUCTION LINE

8 - 18m 7 - 18m 6 - 18m 5 - 18m 4 - 18m 3 - 24m 2 - 24m 1 - 30m


122kW 244kW 354kW 463kW 573kW 683kW 813kW 943kW
DN 65 DN 80 DN 100 DN 100 DN 125 DN 150 DN 150 DN 150

2 x 61.2kW 2 x 61.2kW 2 x 54.9kW 2 x 54.9kW 2 x 54.9kW 2 x 54.9kW 2 x 64.9kW 2 x 64.9kW


122.4kW 122.4kW 109.8kW 109.8kW 109.8kW 109.8kW 129.8kW 129.8kW

MAIN WET
SUCTION LINE
NH3 - DIMENSIONS FOR WET SUCTION LINE

8 - 18m 7 - 18m 6 - 18m 5 - 18m 4 - 18m 3 - 24m 2 - 24m 1 - 30m


122kW 244kW 354kW 463kW 573kW 683kW 813kW 943kW
DN 100 DN 125 DN 150 DN 150 DN 200 DN 250 DN 250 DN 300

2 x 61.2kW 2 x 61.2kW 2 x 54.9kW 2 x 54.9kW 2 x 54.9kW 2 x 54.9kW 2 x 64.9kW 2 x 64.9kW


122.4kW 122.4kW 109.8kW 109.8kW 109.8kW 109.8kW 129.8kW 129.8kW

MAIN WET
SUCTION LINE
DANFOSS CALCULATION REPORTS
MAIN SUCTION LINE
CO2 – SECTION 1 NH3 – SECTION 1
CO2 – SECTION 2 NH3 – SECTION 2
CO2 – SECTION 3 NH3 – SECTION 3
CO2 – SECTION 4 NH3 – SECTION 4
CO2 – SECTION 5 NH3 – SECTION 5
CO2 – SECTION 6 NH3 – SECTION 6
CO2 – SECTION 7 NH3 – SECTION 7
CO2 – SECTION 8 NH3 – SECTION 8
DANFOSS CALCULATION REPORTS
BRANCH HEADER FOR COLD ROOM 1 AIR COOLER
CO2 NH3