Vous êtes sur la page 1sur 1

EQUALIZING

HOT WATER PIPING


BASIN TYP
MANUAL BALANCING
VFD VFD VFD
VALVE FURNISHING
WITH TOWER TYP.
SCREEN
INLET
TYP.
WATER LEVEL
TO
MODULATING 3" OVERFLOW
LEVEL
COLD WATER
CONTROL LC
BASIN TYP.
VALVE
M M M M M M

PI
MIN. 2" BALL
VALVE N.C.
TO
SANITARY
SEWER

SCALE : NONE
CONDENSATE
WATER SUPPLY
CONDENSATE
(FROM TOWER)
WATER RETURN
TO PUMP SUCTION

DETAIL TITLE / MULTIPLE


(TO TOWER)

DATE ISSUED: DECEMBER 2008


NOTE:

1. THE BASINS SHALL BE INTERCONNECTED BY FLUMES. EACH CELL SHALL BE

PIPING CONNECTIONS
PROVIDED WITH ITS OWN SUMP AND ANTI-CAVITATION PLATE.

MULTIPLE CELL COOLING TOWER -

CELL COOLING TOWER -


PIPING CONNECTIONS

CAD DETAIL NO.:


# NTS

DESIGNERS NOTES:

1.IF TOWER IS INSTALLED MORE THAN 5 FT [1500 MM] ABOVE THE ROOF OR
GRADE PROVIDE A PLATFORM AROUND THE PERIMETER.
2.PROVIDE ACCESS FOR ALL ELEVATED VALVES AND CONTROL DEVICES AND TO
EACH FAN MOTOR.
3.SEE HVAC DESIGN MANUAL.
4.COORDINATE WITH ELECTRICAL ON BASIN HEATER.

SD236500-01.DWG