SIZING OF GENERATOR

Assumed Power Factor = 80%

Assumed Demand factor of the System = 100%

Maximum Demand @ 100% demand factor of the system

Maximum Demand = Total Connected load X demand factor

= 273.74 A X 230 V X 1.0

=62.9602kVA

Total Maximum Demand @30% Load Growth Factor

Total Maximum Demand = Maximum Demand + 30% total Max. Demand

= 62.9602kVA + [(0.3)(74.91kVA)]

=81.85kVA

Generator Size = 80% of the Power Factor

=81.85kVA X 0.8

=65.5kVA

Use 85 kW, 240 V, 1800 rpm, 50 Hz, 3Φ


For Feeder Ampacity and Protection

IFL = 85 KW / (240 x 3)

= 204.48 A

Conductor Ampacity

Iw = 204.48 A x 1.25

= 255.6 A

Use 5 sets of 3 – 150 mm2 THW Cu wire in 80 mm dia. RSC

Use 300 AT / 400 AF


SIZING OF TRANSFORMER

Assumed Demand Factor = 80%

Assumed diversity factor = 130%

Maximum Demand @ 80% demand factor of the system

Maximum Demand = Total Connected load X demand factor

= 273.74 A X 230 V X 0.80

= 50.37kVA

Total Maximum Demand @115% Diversity Factor

Total Maximum Demand = Maximum Demand / Diversity Factor

= 50.37kVA / 1.30

=38.745kVA

Transformer Rating

Load Growth factor = 30%

Transformer Rating = Total Maximum Demand Factor + 30% total Max. Demand

=38.745kVA + [(0.3)(38.745kVA)]

=50.37kVA

Use 3-100kVA, 13.2kV/240 V, 60 Hz, Delta Connection


Minimum Ampacity of Primary Feeder Conductor

IFL = 501kVA X 100 VA / (13.2kV X √3)

= 21.91A

IW = 21.91A X 1.25

=27.39 A

Use 3-5.5 mm2 THW Cu 15mm dia. RSC

Maximum Setting of Primary Feeder Conductor

ICN = 21.91 A X 2.5

=54.788 A

Use 70AT / 100AF, 2P, 13.2kV

Minimum Ampacity of Secondary Conductor

IFL = 501kVA X 1000 VA / (240kV X √3)

= 1205.22 A

IW = 1205.22 A X 1.25

= 1506.53 A

Use 3sets of 2-400 mm2 THW Cu 80mm dia. RSC


For Feeder Ampacity and Protection

IFL = 800kW / (240V X √3)

= 1924.5 A

Conductor Ampacity

IW = 1924.5 A X 1.25

= 2405.63 A

Use 5sets of 3-400 mm2 THW Cu 100mm dia. RSC

Use 200 AT / 2500 AF