 Sr.
 Oil temperature Deg. C  Correction factor(K)
No.
 1  10  0.8
 2  15  0.9
 3  20  1.0
 4  25  1.12
 5  30  1.25
 6  35  1.40
 7  40  1.55
 8  45  1.75
 9  50  1.95
 10  55  2.18
 11  60  2.42
 12  65  2.70
 13  70  3.00
 

If Tan Delta of bushing /winding/CVT/CT is measured at oil temperature T Deg. C.


Then Tan Delta at 20 Deg. C shall be as given below:

Tan Delta at 20 Deg. C = (Tan Delta at Temp T Deg. C )/ Factor K.