A. Scope
This standard specifies the conductors that are to be used for new transmission line
construction.
B. General
The standard conductors to be used and their corresponding voltage class in the
PacifiCorp transmission system are as follows:

Voltage Conductor Stranding Code Word


46/69 kV 1/0 AWG 6/1 ACSR Raven
4/0 AWG 6/1 ACSR Penguin
397.5 kcm 26/7 ACSR Ibis
115 kV 397.5 kcm 26/7 ACSR Ibis
795 kcm 26/7 ACSR Drake
795 kcm 37 AAC Arbutus
1557.4 kcm 36/7 ACSR/TW Potomac
138 kV 397.5 kcm 26/7 ACSR Ibis
795 kcm 26/7 ACSR Drake
795 kcm 37 AAC Arbutus
1557.4 kcm 36/7 ACSR/TW Potomac
161 kV 795 kcm 26/7 ACSR Drake
795 kcm 37 AAC Arbutus
954 kcm 54/7 ACSR Cardinal
1272 kcm 45/7 ACSR Bittern
1272 kcm 61 AAC Narcissus
1557.4 kcm 36/7 ACSR/TW Potomac
230 kV 954 kcm 54/7 ACSR Cardinal
1272 kcm 45/7 ACSR Bittern
1272 kcm 61 AAC Narcissus
1557.4 kcm 36/7 ACSR/TW Potomac
1949.6 kcm 42/7 ACSR/TW Athabaska
345 kV 954 kcm 54/7 ACSR Cardinal
1272 kcm 45/7 AAC Bittern
1557.4 kcm 36/7 ACSR/TW Potomac
1949.6 kcm 42/7 ACSR/TW Athabaska
500 kV 1272 kcm 45/7 ACSR Bittern
1557.4 kcm 36/7 ACSR Potomac
1949.6 kcm 42/7 ACSR/TW Athabaska

Transmission
Construction Standard
E 2008 by PacifiCorp. All rights reserved. Conductor—Standard
Conductors
Engineer (C. Wright):
2 Jun 09 TD 102
Standards Manager (G. Lyons): Page 1 of 2
TD 102

This page is left blank intentionally.

Transmission
Construction Standard
Conductor—Standard E 2008 by PacifiCorp. All rights reserved.
Conductors
TD 102 Engineer (C. Wright):
2 Jun 09
Page 2 of 2 Standards Manager (G. Lyons):