The coupling electrode (6) capacitively picks up the voltage, which is then transmitted to the meas-
uring point (8). Overvoltage arresters (10) are installed to protect the system. A balancing capacitor
(11) limits the voltage respectively the current at the measuring point.
Delivery content
1. complete system
consists of:
3 pcs capacitive insulator
3 pcs. connection cable
1 pcs. capacitive voltage ledge *
optional 1 pcs. voltage indication instrument
2. subsystem 1 ( in case measuring points exist )
3 pcs. capacitive insulator
3 pcs. connection cable
3 pcs. overvoltage arrester
3pcs. adapter
optional 1 pcs. voltage indication instrument
KVDS110703ae
1) Capacitive Insulator
The capacitive insulator serves as a voltage detector in a Voltage Detection System.
Together with the balancing capacitor, the capacitive insulator constitutes a
capacitative voltage divider.
The capacitive insulator is designed in a similar way as the common insulators.
Both types are exchangeable.
rated voltage 10 kV order-No. 38.10.01
rated voltage 20 kV order-No. 38.11.01
2) Connecting Cables
The connection cable between the insulator and the capacitive voltage
ledge is a screened cable. The screened cable is connected to the insulator
with a M6 screw terminal and to the capacitive voltage ledge with a flat
plug 6.3 x 0.8 mm. The screen of the cable is earthed.
Technical data
Conditions for the port: HR – System
rated frequency: 50 Hz
Operatingvoltage measuring point: 70 to 90 V AC
KVDS110703be