Vous êtes sur la page 1sur 1

A Normal

Process: OK Alm: OK Ack: Ack

Alarm Occurs

Re-Alarm Process RTN Alarm Clears Operator Acks Alarm or Auto Ack

B UnackAlarm
Process: Alarm Alm: Alarm Ack: Unack

Operator Resets Alarm

C AckAlarm
Process: Alarm Alm: Alarm Ack: Ack

Operator Acks Alarm

Alarm Occurs

Process RTN Process RTN Alarm Clears

D RTN Unack
Process RTN Process: OK Alm: OK Ack: Unack Operator Resets Alarm Operator Acks Alarm

F Latch Ack
Process: OK Alm: Alarm Ack: Ack

E Latch Unack
Process: OK Alm: Alarm Ack: Unack

Shelv e

Un-shelv e

Designed Suppression

Designed Un-suppression

Remov e f rom Serv ice

Return to Serv ice

G Shelved
Process: N/A Alm: N/A

H Suppressed By Design
Process: N/A Alm: N/A

I Out Of Service
Process: N/A Alm: N/A

Note 1: States G, H, and I can connect to any alarm state in the diagram. Note 2: The dotted line indicates an infrequently implemented option.

Figure 5 Alarm State Transition Diagram

ISA 18.02 2009 CDV 04/2009

28