Caterpillar Generator Data Page 1 of 10
GENERATOR DATA June 13, 2011
For Help Desk Phone Numbers Click
Selected Model
Engine: 3512 Generator Frame: 685 1g (KW): 1000.0. Line Voltage: 4160,
Fuel: Diese! Generator Arrangement: 7€262. 1g (KVA): 1250.0 Phase Voltage: 2402
Frequency: 60 — Excitation Typ 08 Rated Current: 173.5
Duty: STANDBY Connection: SERIES STAR EPG Status: Current
Spec Information
Generator Specification oujaiiads eemsichay
Frame: 685 Type: SR4B No, of Bearings: 1 as Una Coed tweety a
Winding Type: FORM WOUND Flywheel: 21.0 bos aso ye
is SERINE TAR Hina 01 ie ecais ne
Wires per Lead: | a ae Be
Syme Speed: 1800 Generator Piteh: 0.7777 te are a
Reactances Per Unit Ohms
SUBTRANSIENT - DIRECT AXIS X'y o.1a07 Lars
SUBTRANSIENT - QUADRATURE AXIS", osiss — aaorz
TRANSIENT - SATURATED X'g 02186 29855
SYNCHRONOUS - DIRECT AXIS Xy 32072 aa.gn2s
SYNCHRONOUS - QUADRATURE AXIS X, Lssis 21.8997
NEGATIVE SEQUENCE X, om 3.1765
ZERO SEQUENCE X, 0.1250 7308 |
Time Constants Seconds
OPEN CIRCUIT TRANSIENT - DIRECT AXIS Ty, 2.9310
SHORT CIRCUIT TRANSIENT - DIRECT AXIS T, 0.2643
OPEN CIRCUIT SUBSTRANSIENT - DIRECT AXIS Ty) 0.0099
SHORT CIRCUIT SUBSTRANSIENT - DIRECT AXIS T'y 0.0070
OPEN CIRCUIT SUBSTRANSIENT- QUADRATURE AXIS Ty, 0.0194
SHORT CIRCUIT SUBSTRANSIENT- QUADRATURE AXIST", 0.0143
EXCITER TIME CONSTANT T 0.1093
ARMATURE SHORT CIRCUIT 0.0387
Short Circuit Ratio: 038 J[__ Stator Resistance = 0.388 Ohms __ Field Resistance = 1.476 Ohms
Voltage Regulation Generator Excitation
Voltage level adustment: +/- 5.0% No Load Full Load, (rated) pf
Voltage regulation, steady state: #/- Series Parallel
Voltage regulation with 3% speed change: +/- 0.5% || Excitation voltage: 2.67 Volts. 13.95 Volts Volts
Waveform deviation line - fine, no load: less than 3.0% || Exeitation current 1.81 Amps 7.77 Amps Amps
‘Telephone influence factor: less than 50
hutp://tmiwebclassic.cat.com/tmi/servlevcat.edis.tmiweb.gui-TMIDirector?Action=buildtab.... 6/13/2011Caterpillar Generator Data Page 2 of 10
Selected Model
Engin Genset Rating (kW): 1000.0 Line Voltage: 4160
3512 Generator Frame: 685
Fuel: Diesel Generator Arrangement: 7C2624 _ Genset Rating (kVA): 1250.0 Phase Voltage: 2402
Frequeney: 60 Excitation Type: Permanent Magnet Pwr. Factor: 0.8 Rated Current: 173.5
Du Application: EPG Status: Current
Generator Mechanical Information
Center of Gravity
[Dimension XJE-871.2 mm]/-34.3 IN.
[Dimension ¥][0.0 mm _][0.01N.
[Dimension Z][0.0 mm __][0.01N.
"X" is measured from driven end of generator and parallel to rotor. Towards
engine fan is positive. See General information for details
+ "Y"is measured vertically from rotor center line. Up is positive
"2" is measured to left and right of rotor center line. To the right is positive
Generator WT = 2620 kg * Rotor WT= 992 kg * Stator WT= 1628 kg
5,776LB 2,187 LB 3,589 LB
Rotor Balance ~ 0.0508 mm deflection PTP
Overspeed Capa
ty = 150% of synchronous speed
Generator Torsional Data
JU = Coupling J2= Rotor
d Fan TOTAL J=J1 +42 +33
K1 = Shaft Stiffness between K2
J1+J2 Diameter 1) 2+ J3 (Diameter 2)
a KI Min Shaft Dia = J2 K2— Min Shaft Dia? 3
232LBIN.S M34 MLBINJrad —62IN.IB9SLBINS 266MLBIN/ad —-261N, 3,3 LBINS?
262INms 162MNmMad —157Smm Nm 30MNaviad 660mm —-9373Nms
Total J
216.3 LIN?
AMIN ms
hup://tmiwebelassic.cat.com/tmi/servlet/cat.edis.tmiweb.gui. TMIDirector? Actior
nuildtab.,, 6/13/2011Caterpillar Generator Data
Selected Model
Engine: 3512 Generator Frame: 685 Genset Rating (kW): 1000.0 Line Voltage: 4160
: Diesel Generator Arrangement: 7C2624 Genset Rating (kVA): 1250.0 Phase Voltage: 2402
Frequency: 60 Excitation Type: Permanent Magnet Pwr. Factor: 0.8 Rated Current: 173.5,
Duty: STANDBY Connection: SERIES STAR Application: EPG Status: Current
Generator Cooling Requirements -
Temperature - Insulation Data
Cooling Requirements: ‘Temperature Data: (Ambient 40°C)
Heat Dissipated: 53.7 kW Stator Ris 30.0 °C
Air Flow; 0.0 m¥min Rotor Ri 130.0%
Insulati
n Class: H
Insulation Reg. as shipped: 100.0 MQ minimum at 40.9C
‘Thermal Limits of Generator
Frequency: 60 Hz
Line to Line Voltage: 4160 Volts
BBR 80/40 944.0 KVA
FBR -105/40 L380 kVA
HBR - 125/40 1250.0kVA
F PR- 130/40 1250.0kVA
hutp://Amiwebelassic.cat.com/tmi/servle'
tmiweb.gui. TMIDirector?Action=buildtab... 6/13/2011
Page 3 of 10