Académique Documents
Professionnel Documents
Culture Documents
28
ANSI/ISA-S5.1-1984 (R 1992)
ANSI/ISA-S5.1-1984 (R 1992)
29
DIAPHRAGM SEAL
* It is not mandatory to show a common housing. ** These diamonds are approximately half the size of the larger ones. *** For specific logic symbols, see ANI/ISA Standard S5.2.
30
ANSI/ISA-S5.1-1984 (R 1992)
GENERAL SYMBOL 5 6
ANGLE 7
BUTTERFLY 8
ROTARY VALVE
THREE-WAY 9 10
FOUR-WAY 11
GLOBE 12
DIAPHRAGM
DAMPER OR LOUVER
Further information may be added adjacent to the body symbol either by note or code number.
ANSI/ISA-S5.1-1984 (R 1992)
31
32
ANSI/ISA-S5.1-1984 (R 1992)
ANSI/ISA-S5.1-1984 (R 1992)
33
34
ANSI/ISA-S5.1-1984 (R 1992)
6.6 Symbols for self-actuated regulators, valves, and other devices (contd.)
ANSI/ISA-S5.1-1984 (R 1992)
35
6.6 Symbols for self-actuated regulators, valves, and other devices (contd.)
36
ANSI/ISA-S5.1-1984 (R 1992)
6.7 Symbols for actuator action in event of actuator power failure (shown typically for diaphragm-actuated control valve).
ANSI/ISA-S5.1-1984 (R 1992)
37
38
ANSI/ISA-S5.1-1984 (R 1992)
ANSI/ISA-S5.1-1984 (R 1992)
39
40
ANSI/ISA-S5.1-1984 (R 1992)
ANSI/ISA-S5.1-1984 (R 1992)
41
42
ANSI/ISA-S5.1-1984 (R 1992)
ANSI/ISA-S5.1-1984 (R 1992)
43
44
ANSI/ISA-S5.1-1984 (R 1992)
ANSI/ISA-S5.1-1984 (R 1992)
45
46
ANSI/ISA-S5.1-1984 (R 1992)
ANSI/ISA-S5.1-1984 (R 1992)
47
48
ANSI/ISA-S5.1-1984 (R 1992)
ANSI/ISA-S5.1-1984 (R 1992)
49
50
ANSI/ISA-S5.1-1984 (R 1992)
ANSI/ISA-S5.1-1984 (R 1992)
51
52
ANSI/ISA-S5.1-1984 (R 1992)
ANSI/ISA-S5.1-1984 (R 1992)
53
54
ANSI/ISA-S5.1-1984 (R 1992)
ANSI/ISA-S5.1-1984 (R 1992)
55
FLOW RECORDER WITH PRESSURE PEN CONNECTED TO TAP OF DIFFERENTIAL-PRESSURETYPE FLOW RECORDER 5 LI UU 300
FC FIK 403
T A N K
LIT
T A N K
LT
FT
COMPLEX COMBUSTION CONTROL SYSTEM, UU-300, ADJUSTING SET-POINT OF FLOW CONTROL SYSTEM
PREFERRED METHOD TO BE USED IF INTERLOCK IS UNDEFINED OR COMPLEX. I-1 MAY BE SUBSTITUTED FOR I TO REFER TO INTERLOCK DETAIL NO. 1, TO BE DRAWN ELSEWHERE. THE OUTPUTS OF TSL-301 AND PSH-501 MAY ENTER THE INTERLOCK BOX SEPARATELY IN
OPTIONAL METHOD MAY BE USED IF RELAY EXISTS AND ONE DESIRES TO SHOW IT
FLOW CONTROL LOOP THAT MAY BE BLOCKED BY INTERLOCK ACTUATED BY EITHER LOW TEMPERATURE OR HIGH PRESSURE
FY I FIC 404
56
ANSI/ISA-S5.1-1984 (R 1992)
ANSI/ISA-S5.1-1984 (R 1992)
57
58
ANSI/ISA-S5.1-1984 (R 1992)
PR-507 PEN 2
PR 508
ALTERNATIVE 1
INTERRELATED INSTRUMENTS WHOSE SYMBOLS ARE SCATTERED ON DIAGRAM. (A MULTIPOINT INSTRUMENT, SUCH AS A DATA LOGGER, THAT IS DESIGNATED WITH POINT NUMBERS ON A DIAGRAM IS NOT EXPECTED TO HAVE THE SYMBOLS FOR THE VARIOUS POINTS TIED OR REFERENCED TOGETHER). PEN ASSIGNMENTS NEED NOT BE SHOWN ON A DIAGRAM IF IT IS THE USER'S PREFERENCE TO SHOW THEM IN AN INDEX. 29 LSL 602 STOP LSL 603 START STANDBY
LSHL 604
STANDBY ON-OFF
LSHL 605
LEAD-LAG
ANSI/ISA-S5.1-1984 (R 1992)
59
ZSL 303
FQT 411
ZSL 801
ZSL 303
YC 1
FQT 411
ZSL 801
ALTERNATIVE 1
ALTERNATIVE 2
PROGRAMMABLE CONTROLLER SCHEME. ALTERNATIVE 2 ALLOWS MORE DEFINITION OF WHICH SIGNALS ARE ACCESSIBLE TO THE OPERATOR 32 1:1 FI 410 33
AIC 103 SP INDIVIDUAL INSTRUMENTS WITH INTEGRAL FUNCTION BLOCKS: SQUARE ROOT EXTRACTION, 1:1 FEED BOOST, FEED FORWARD BIAS ON CONTROLLER OUTPUT, SETPOINT OUTPUT SIGNAL
60
ANSI/ISA-S5.1-1984 (R 1992)
ANSI/ISA-S5.1-1984 (R 1992)
61
PC
VAC UU M
LC
FC
FC
LC
H O T O IL
Simplified symbolism and abbreviated identification used to define the principal points of measurement and control interest. * SEE SECTION 4.4 FOR DISCUSSION
62
ANSI/ISA-S5.1-1984 (R 1992)
PT
PC
F/D
I-Y AC AT
VACUU M
F f(t) f(t) LC LT
Q H OT OIL
LT
LC
B X AC AT
Functionally oriented symbolism and abbreviated identification used to develop control concepts without concern for specific hardware.
ANSI/ISA-S5.1-1984 (R 1992)
63
64
ANSI/ISA-S5.1-1984 (R 1992)
Index
Term -A-
Para. No.
Accessible definition .............................. 3 graphic symbols ................... 6.3 Actuator actuator action...................... 6.7 graphic symbols ................... 6.5 identification ......................... 5.1 Air Supply identification ......................... 6.2 Alarm definition............................... 3 examples .............................. 6.9 identification ......................... 5.1 Analysis examples .............................. 6.8 identification ......................... 5.1 Assignable definition............................... 3 Auto-Manual Station (Control Station) definition............................... 3 identification ......................... 5.1 Auxiliary Location graphic symbol ..................... 6.3 Averaging graphic symbol ..................... 5.4 -BBalloon, Bubble definition............................... 3 graphic symbol ..................... 6.3 Behind-the-Panel definition............................... 3 graphic symbol ..................... 6.3 Bias graphic symbol ..................... 5.4
Term Para. No. Binary definition............................... 3 graphic symbol ..................... 6.2 Board (Panel) definition............................... 3 identification ......................... 6.3 Burner, Combustion example................................6.8 identification ......................... 5.1 -CComplex Combinations example................................6.11 Computer Function graphic symbol ..................... 6.3 Computing Device definition............................... 3 example................................6.9 function................................. 5.4 identification ......................... 5.1 Conceptual Diagrams example................................6.12 Conductivity (see Analysis) example................................6.8 Configurable definition............................... 3 Controller definition............................... 3 Control example................................6.9 identification ......................... 5.1 Control Station (Auto-Manual Station) definition............................... 3 example................................6.9 identification ......................... 5.1 Control Valve definition............................... 3
ANSI/ISA-S5.1-1984 (R 1992)
65