Outdoor Air Ventilation Calculations

14761 Biscayne Blvd. Bay #316 North Miami Beach, FL Calculations per Florida Mechanical Building Code - 20010 Edition Mechanical Ventilation Chapter 4, Section 403, Table 403.3 Mixed use space: Requirements From Table 403.3
CFM Outdoor Air Persons #/mft Exhaust CFM/ft

Category # person CFM/ft Coffee Shop 7.5 0.18 Offices 5 0.06 Play Floor (Day Care) 10 0.18 Toilet Rooms (rate per w.c. or urinal, typ use) Storage Areas 0.12 Ventilation Calculations: Space Coffee Shop Offices Play Floor W.C. & Urinals Storage Areas Total Ventilation Required Outdoor Air flow Calculations

70 5 25 50

S.F. 752 80 1233 3 183

Persons 52.64 1 36.99 per unit n/a

Ventilation CFM 394.8 5 739.8 150 27.45 1317.05

Vbz = (Rp Rz) + (Ra Az) Equation 4-3 Rp = CFM reqd per person Rz = # people in Zone Ra = outdoor air flow reqd per/area Az = net occupiable floor area
Coffee Shop Area Rp = 7.5 Rz = 52.64 Ra = 0.18 Az = 752 CFM 530.16 Storage Areas Rp = 0 Rz = 0 Ra = 0.12 Az = 183 CFM 21.96 Office area Rp = 5 Rz = 1 Ra = 0.06 Az = 80 CFM 9.8 Toilets Exhaust per 50 # fixtures 3 Exhst CFM 150 CFM 150 Play Room Rp = 10 Rz = 36.99 Ra = 0.18 Az = 1233 CFM 591.84

Total CFM Outside Air Required /Equation 4-3

1,303.76