STANDARD IQ/IQT REMOTE CONTROL CIRCUITRY (120VAC)


NOTE: ACTUATOR REMOTE CONTROL SIGNALS MAY BE INTERNALLY OR EXTERNALLY SUPPLIED.
REMOTE # FIT LINK '#' AS SHOWN AND CONNECT TERMINALCONTROL CONTACTS TO INTERNAL SUPPLY ON 5.

THE INFRA RED SETTING TOOL ENABLES ALL CONFIGURABLE ACTUATOR SETTINGS TO BE MADE. BEFORE PUTTING THE ACTUATOR INTO SERVICE, IT MUST BE INSTALLED AND COMMISSIONED IN ACCORDANCE WITH PUBLICATION E170E (IQ) or E175E (IQT) INSTALLATION AND MAINTENANCE INSTRUCTIONS. UNLESS SPECIFIED WITH ORDER, THE ACTUATOR IS DESPATCHED WITH DEFAULT SETTINGS AS LISTED IN PUBLICATION E170E (IQ) or E175E (IQT). FOR IQ/IQT CONTROL AND MONITORING FACILITIES, REFER TO PUBLICATION E120E.

INTERNALLY SUPPLIED:

EXTERNALLY SUPPLIED: CONNECT CONTROL CONTACTS TO EXTERNAL SUPPLY LIVE/+VE. CONNECT SUPPLY ZERO/-VE AS FOLLOWS:TO TERMINAL 36 & 31 FOR SUPPLIES UP TO 60VAC or DC TO TERMINAL 40 & 32 FOR SUPPLIES UP TO 120VAC
FOR CONTROL FORMS D & E, LINK '#' MUST BE FITTED. CONNECT ZERO/-VE AS INDICATED ABOVE.
HU TD OW N

INT E (ZE RNA RO L S UP ) PL Y CO MM CO ON NT FO 60V RO R AC LS U REM OR P T OTE CO DC O M CO MON NT FO 120 RO R V A LS 6 REM C O 0V TO TE CL OS E

CUSTOMER CONNECTION FOR REMOTE CONTROL

INT E 120 RNA V A L SU CL P IVE PLY

MA INT AIN

FORM A

36

40

33

34

35

OP E

25

OPEN/CLOSE PUSH TO RUN CONTROL (LOCAL CONTROL REMAINS SELF MAINTAINED)

Close

Open To external supply or terminal 5 (see 'Note:' above)

FORM B
OPEN/CLOSE MAINTAINED CONTROL WITH MID TRAVEL REVERSAL

36

40

33

34

35

25

Close

Open To external supply or terminal 5 (see Note:' above)

FORM C
OPEN/STOP/CLOSE MAINTAINED CONTROL

36

40

33

34

35

25
To external supply or terminal 5 (see 'Note:' above)

Close

Open

Stop

FORM D
TWO WIRE CONTROL, ENERGISE TO OPEN DE-ENERGIZE TO CLOSE. (CONFIGURE FOR OPEN PRIORITY) CUSTOMER TO LINK 5 - 33

36

40

33

34

35

25

Close

Open To external supply or terminal 5 (see 'Note:' above)

FORM E

36

40

33

34

35

25

TWO WIRE CONTROL, ENERGISE TO CLOSE DE-ENERGIZE TO OPEN (CONFIGURE FOR CLOSE PRIORITY) CUSTOMER TO LINK 5 - 35 4 31 32

Open

Close To external supply or terminal 5 (see 'Note:' above)

FORM F

33

34

35

5
ESD switch (stayput)

25

EMERGENCY SHUT-DOWN CIRCUIT. THE ESD CIRCUIT CAN BE ADDED TO ANY OF THE CONTROL CIRCUITS SHOWN ABOVE. AN ESD SIGNAL APPLIED TO THE ACTUATOR WILL OVERRIDE ANY EXISTING OPEN OR CLOSE CONTROL SIGNAL. THE DEFAULT ESD CONFIGURATION IS "STAY PUT", DERIVED FROM A N/O CONTACT (SIGNAL APPLIED). FOR OTHER CONFIGURABLE ESD SETTING OPTIONS, REFER TO PUBLICATION E170E (IQ) or E175E (IQT) INSTALLATION AND MAINTENANCE INSTRUCTIONS.

To external supply or terminal 5 (see 'Note:' above)

www.

.com BATH, BA1 3JQ

ROTORK CONTROLS LTD ROTORK CONTROLS INC ROCHESTER ENGLAND NY 14624, USA

EM ER GE NC YS

This is an Associative Document that needs to be read in conjunction with the appropriate Rotork Wiring Diagram.

Document No

Issue No

RWS301 2