Académique Documents
Professionnel Documents
Culture Documents
The total amp load that the NEC allows a conductor to carry and be considered to meet the minimum safety standards after de-ration calculations are performed as required. NOTE: The breaker must be sized no larger in amp size than the ampacity rating of a conductor after de-ration calculations have been performed to find the maximum ampacity of that conductor.
Ambient Temperature
The normal temperature range that surrounds the area of an electrical conductor in which that conductor is to be used.
Residential Service Entrance and Feeder Conductor Ampacity Ratings Also this NEC Article 310.15.B.2.A and / or NEC Table 310.16 correction factor [ at bottom of the page ] does not apply to the residential service entrance and feeder conductor ampacity ratings allowed in NEC Table 310.15.B.6This service entrance and feeder conductor chart is exempt from both the ambient temperature and the number of conductors in a raceway requirement. NEC Table 310.15.B.6 naturally limits the number of conductors to no more than three when the conductors are a single phase residential service. There is also a rule pertaining to this chart that states that any feeder being served by a service entrance conductor supplying it allows the feeder also being served to be sized no larger than the service entrance conductor serving that feeder. There are times when you may find 4 feeders in a conduit being served by a service entrance that is sized by this NEC Table 310.15.B.6that is also
controlled in size by this same chart NEC Table 310.15.B.6 by that feeder not being required to be larger than the service entrance conductors supplying it power. This feeder also would be exempt from the de-ration factors required by NEC Article 310.15.B.2.A and / or NEC Table 310.16 correction factor [ at bottom of the page ]. Special Note: Any conduit shorter than 24requires no de-rating calculation in considering the number of conductors installed in a raceway. NEC Article 310.15.B.2. Exception 3 Special Note: When counting current carrying conductors you do not need to count equipment grounding conductors in your de-ration of ampacity due to the number of conductors in a raceway at all, they are not current carrying conductors. NEC Article310.15.B.5 Special Note: When counting current carrying conductors you do not need to count in your de-ration of the ampacity of a conductor, any white neutral conductors, that are carrying only the unbalanced load of two hot conductors of the same two pole circuit and installed in the same raceway. { example would be a { multi-wire circuit } that is two circuits using the same common white wire to a receptacle box when that receptacle is 240 volt rated like for dual 120 volt branch circuit that has been split into two 120 volt branch circuits from one 240 volt circuit that has two hot conductors, one insulated white neutral conductor and one equipment grounding conductor. Another example that would use a neutral conductor is a dryer or electric range that uses both 240 volts and 120 volts in the same multiwire branch circuit. NEC Article310.15.B.4.A.A 120 VOLT BRANCH CIRCUIT SERVING RECEPTACLES DOES NOT APPLY TO THIS RULE FOR NEUTRALS. A 120 VOLT RECEPTACLE DOES NOT HAVE A NEUTRAL CONDUCTOR IN ITS BRACH CIRCUIT DESIGN. Special Note: You must count the white grounded leg serving a single ungrounded [hot]conductor of a 120 volt branch circuit { this white conductor would not be a true neutral conductor } for your conduit fill calculations { example white conductor of a 120 volt receptacle }. This is true only if the grounded leg is not used as a neutral designed to carry the unbalanced load while serving between two ungrounded [hot] conductors of a 240 two pole circuit {this conductor would be a true neutral conductor}. NEC Article 310.15.B.2and 310.15.B.4.A Special Note: On 4 wire 3 phase wye-connected systems the neutral must be counted as a current carrying conductor. NEC Article 310.15.B.4.B&C Conductor Ampacity = ampacity x correction factor for ambient temperature x correction factor for number of conductors in a conduit over 3 conductors = adjusted Conductor ampacity recognized as the ampacity of that conductor by the NEC.
ampacity de-ration calculation due to the number of conductors contained in that raceway as required in NEC Table 310.15.B.2.A 40amps X 41% = 16.4 amps after ambient temperature de-ration then multiplied by 45% required due to the 26 current carrying conductors in that same raceway which would then have a final de-rated ampacity of that 8 awg copper conductor of 7.38 amps. This 7 amps of ampacity of this 8 awg copper conductor would then be considered the true adjusted ampacity rating of that 8 awg copper conductor. The NEC requires that you must have a minimum ampacity of 15 amps for any conductor used in a wiring system of 120 volts or more. NEC Table 210.3 That conductor must also be capable to carry the load apply requiring the ampacity to equal the load it carries NEC Table 210.19.A.1 and NEC Table 210.24 This 8 awg conductor as described above in its installation would not be allowed to be used because it not only is not rated at in ampacity of at least 15 amp but it also would not carry the load expected of it. Same Example: [ Numeric Form ] 8 awg TW ampacity = 40 amps X 41 % {ambient temp} = 16.4 amps 16.4 amps X 45 % {26 conductors} = 7.38 amps capacity of a 8 awg TW conductor after the correction factors are reduced. Example Results: Therefore that 8 awg TW has a total ampacity of 7.38 amps found in a Florida attic with ambient temperature of 130 degrees F., and found with 26 other current carrying conductors, in the same conduit. In NEC Table 310.16 column for 60 degree C the ampacity rating says that this conductor is rated at 40 amps for TW insulated conductors. The calculated answer is smaller the original ampacity rating found in NEC Table 310.16 column for 60 degree C , therefore you must use the smallest ampacity rating which would be your calculated de-rated ampacity rating. Remember that only 15 amp or larger rated conductors after de-ration calculation are allowed to serve 120 volts or more in any type of structure. NEC Article 210.3 and NEC Table 210.19.A.1 and NEC Table 210.24 Also remember that 20 amp rated conductors after de-ration calculation are required serving any receptacle installed in a bath room, kitchen, dining, nook, pantry, or laundry. NEC Article 210.11 Motors conductors must also consider ampacity deration calculations. NEC Table 310.15.B.2.A and NEC Table 310.16 and NEC Article 430.22 and NEC Article 430.24 Actually to my knowledge the table for residential service entrance type conductors as per NEC Table 310.15.B.6 is the only ampacity that does not require ampacity de-ration calculations. Special Note: If you are not required to calculate for de-rations as required for temperature or number of conductors in a raceway because you have no de-ration to calculate and if you are using a higher temperature rated conductor such as THHN which is rated 90 degrees centigrade NEC Table 310.16 or THW which is rated at 75 degrees centigrade NEC Table 310.16, and the conductor is smaller than 1 awg, regardless, you must use the 60 degree column as the ampacity rating as required in NEC Article 110.14.C.1.A.1If the conductor is a 1 awg or larger conductor then you must use the 75 degree column as the ampacity rating NEC Article 110.14.C.2. There is an exception that may apply if you are using no connectors except your breaker connection and if you breaker connection is rated at 75 degrees then you may use the 75 degree column if your conductor is also rated at 75 degrees such as THW OR THWN etc. If you are required to calculate an ampacity de-ration calculation for either ambient temperature or more than 3 current carrying conductors in a raceway, you may start your calculation by using the ampacity rating found in NEC Table 310.16 column for 90 degree C if the conductors insulation is originally rated for 90 degrees. You may also start your de-rating calculations by using the ampacity rating found in NEC Table 310.16 column for 75 degree C if the conductorinsulation is originally rated for 75 degrees. You must then finish your de-rating calculation for the ampacity rating according to NEC Articles 110.14.C after you have completed your ampacity de-ration calculation, you must then compare that calculation de-rated ampacity answer that you calculated using the original temperature
degree rated ampacity in your calculation, with the either the 60 degree column ampacity rating, if the conductor is smaller than 1 awg or with the 75 degree column ampacity rating. If the conductor is 1 awg or larger. NEC Article 110.14.C.1 & 2 You must use the worst scenario [lowest amps in the comparison, comparing your de-rated ampacity answer to the ampacity rating dictated by NEC Article 110.14.C.1 & 2 ] The lowest ampacity rating must be chosen concerning the ampacity rating of that conductor after comparing the de-rated ampacity you found after learning your de-rating calculation answer to the ampacity rating found in the column found in NEC Table 310.16 column for 60 degree C that NEC Article 110.14 requires, if smaller than 1 awg = 60 degree column or if 1 awg or larger = 75 degree column. NEC Article 110.14.C.1 & 2 This NEC Article 210.14.C.1 & 2 requirement of a lower ampacity rating than found in NEC Table 310.16 i s because the terminal ends and wire nuts that are listed and approved on the market in the electrical industry are only rated at 60 degrees centigrade if smaller than 1 awg or 75 degree column if larger than 1 awg conductors as per NEC Article 110.14.C.1 & 2. There can be times when the ampacity de-ration calculations answer is higher in ampacity when starting with the original insulation temperature rating of the conductor than the ampacity of the column in NEC Table 310.16 dictated by NEC Article 110.14.C 1 & 2.
ampacity ratings found in NEC Table 310.16but only after any de-rating calculations required due to ambient temperature or more than 3 current carrying conductors in a raceway has been calculated. When calculating the ampacity of 14, 12, or 10 awg conductors you must first perform the ampacity de-ration calculation as per ambient temperature found at the bottom of the Chart found in NEC Table 310.16 and then as per more than 3 conductors in a raceway found in NEC Table 310.15.B.2.A.
Operate continuously under full load without being damaged Provide the load with a suitable voltage (and avoid excessive voltage drops) Withstand the worst short circuits currents flowing through the cable
Cable sizing methods do differ across international standards (e.g. IEC, NEC, BS, etc) and some standards emphasise certain things over others. However the general principles that underpin all cable sizing calculation do not change. When sizing a cable, the following general process is typically followed:
Gather data about the cable, its installation conditions, the load that it will carry, etc Determine the minimum cable size based on ampacity (continuous current carrying capacity) Determine the minimum cable size based on voltage drop considerations Determine the minimum cable size based on short circuit temperature rise Select the cable based on the highest of the sizes calculated in the steps above
2. Data Gathering
The first step is to collate the relevant information that is required to perform the sizing calculation. Typically, you will need to obtain the following data: (1) Basic cable data - the basic characteristics of the cable's physical construction, which includes:
Conductor material - e.g. copper or aluminium Insulation or cable type - e.g. PVC, XLPE, EPR (for IEC cables), TW, THHW, XHH, etc (for NEC cables) Number of cores - single core or multicore (e.g. 2C, 3C or 4C)
(2) Load data - the characteristics of the load that the cable will supply, which includes:
Number of phases, e.g. three phase or single phase System / source voltage Full load current (A) - or calculate this if the load is defined in terms of power (kW) Full load power factor (pu) Distance / length of cable run from source to load - this length should be as close as possible to the actual route of the cable and include enough contingency for vertical drops / rises and termination of the cable tails
(3) Cable installation - how the cable will be installed, which includes:
Installation method - e.g. cable tray / ladder, in conduit / raceways, against a wall, in air, directly buried, etc Ambient or soil temperature at the installation site Cable grouping, i.e. the number of other cables that are bunched together or installed in the same area Cable spacing, i.e. whether cables are installed touching or spaced Soil thermal resistivity (for underground cables) For single core three-phase cables, are the cables installed in trefoil or laid flat?
When the proposed installation conditions differ from the base conditions, derating (or correction) factors can be applied to the base ampacities to obtain the actual installed current ratings. International standards and cable manufacturers will provide derating factors for a range of installation conditions, for example ambient / soil temperature, grouping or bunching of cables, soil thermal resistivity, etc. The installed current rating is calculated by multiplying the base current rating with each of the derating factors, i.e. Ic = Ib . kd where Ic is the installed / derated ampacity of the cable (A) Ib is the base cable ampacity (A) kd are the product of all the derating factors For example, suppose a cable had an ambient temperature derating factor of kamb = 0.94 and a grouping derating factor of kg = 0.85, then the overall derating factor kd = 0.94x0.85 = 0.799. For a cable with a base ampacity of 42A, the installed / derated ampacity would be Ic = 0.799x42 = 33.6A.
Current flow through the cable - the higher the current flow, the higher the voltage drop Impedance of the conductor - the larger the impedance, the higher the voltage drop
The impedance of the cable is a function of the cable size (cross-sectional area) and the length of the cable. Most cable manufacturers will quote a cable's resistance and reactance in Ohms/km or Ohms/ft. For AC systems, the method of calculating voltage drops based on load power factor is commonly used. Full load currents are normally used, but if the load has high startup currents (e.g. motors), then voltage drops based on starting current (and power factor if applicable) should also be calculated. For a three phase system:
Where V is the three phase or single phase voltage drop (V) I is the nominal full load or starting current as applicable (A) Rc is the ac resistance of the cable (Ohms/km or Ohms/ft) Xc is the ac reactance of the cable (Ohms/km or Ohms/ft) \cos\phi is the load power factor (pu) L is the length of the cable (m or ft) When sizing cables for voltage drop, a maximum voltage drop is specified, and then the smallest cable size that meets the voltage drop constraint is selected. For example, suppose a 5% maximum voltage drop is specified. 16mm2, 25mm2 and 35mm2 cables have calculated voltage drops of 6.4%, 4.6% and 3.2% respectively. The 25mm2 cable is selected as it is the smallest cable that fulfils the maximum voltage drop criteria of 5%. Maximum voltage drops are typically specified because load consumers (e.g. appliances) will have an input voltage tolerance range. This means that if the voltage at the appliance is lower than its rated minimum voltage, then the appliance may not operate correctly. In general, most electrical equipment will operate normally at a voltage as low as 80% nominal voltage. For example, if the nominal voltage is 230VAC, then most appliances will run at >184VAC. Cables are typically sized for a more conservative maximum voltage drop, in the range of 5 to 10% at full load.
Where A is the minimum cross-sectional area of the cable (mm2) i is the prospective short circuit current (A) t is the duration of the short circuit (s) k is a short circuit temperature rise constant The temperature rise constant is calculated based on the material properties of the conductor and the initial and final conductor temperatures. IEC 60364-5-54 calculates it as follows:
For aluminium cables: Where \thetai and \thetaf are the initial and final conductor temperatures respectively. As a rough guide, the following temperatures are common for the different insulation materials: Max Operating Temperature o C 75 90 90 Limiting Temperature o C 160 250 250
Material