A Case Study By Hitesh Bavarva Planning Engineer Top Energy Ltd. INTRODUCTION o Objectives: Investigate the Effect of 1. A 4 x 840 kVAr Switched Capacitor Bank at Zone Substation 2. Feeder Capacitors for Voltage Support Purposes 3. A Power Factor Correction Capacitor at Low Voltage Level 4. Network Loading on the 317Hz Ripple Signal Level and Its Amplification on the Distribution Network. o Tool: DIgSILENT PowerFactory Software Capacitor Bank Facts - For Power Factor Correction - For Reactive Power Support - Can be used at any voltage level - Do not Generate Harmonics - Provide Network loop for local and general resonance Harmonics Nagnification. - !nfluence the magnitude of Harmonics currents and voltages. Typical Shunt Capacitor Arrangement Russell Capacitors And Controller Installed Capacitor Capacitor Controller Capacitors in Workshop Ripple Injection Plant - Nainly used for peak load control street light relay control. - !njects 317Hz audio frequency signals. - L-C series circuit creates low pass filter for 317Hz frequency. - Ripple !njection level at ZS bus bars : 2-7v (L-N) with reference to Low voltage system. - !njection duration: Approx. 7 Secf telegram - Ripple Relay voltage : Nin 1v (L-N). Typical Ripple Injection Plant Arrangement Ripple Injection Plant at Kaikohe Substation Resonance in the Network Resonance in the Network (Contd.) Series Resonant Minimum Z Minimum V Maximum I Figure: 2 Figure: 1 Figure: 3 Parallel Resonant Maximum Z Maximum V Minimum I Figure: 4 Top Energy Network Model - D!gS!LENT PowerFactory Nodels : 33kv and 11kv Network. - Ripple !njection Static Converter : Ward Equivalent voltage Source - Distribution Transformers and Lv Network are not included - Functionality Used: Harmonic Load flow and Frequency Sweep 840VAr Switched Capacitor Banks Ripple Injection Plant W P A 0 1 1 _ 1 W P A 0 1 1 _ 3 200kVAr Fixed Capacitor Banks 3 x 210kVAr switched pf Correction Unit at 440V Effect of ZS Capacitors on Network Impedance 8.559 8.523 14.096 WPA011_3 8.559 41.29 9.743 WPA011_1 Close Bus Open Bus Open Bus With Capacitors Without Capacitors Impedance for 317Hz Signal Name Without Capacitors With Capacitors Figure: 1 Without Capacitors With Capacitors Figure: 2 Effect of Feeder Capacitors on Network Impedance 7.223 21.491 8.56 WAP011_3 7.223 21.491 8.56 WAP011_1 Close Bus Close Bus Close Bus With ChinaClay pf Capacitors Without Fdr Capacitors With ZS Capacitors Impedance for 317Hz Signal Name With ZS capacitors With ZS capacitors + With pf Correction Capacitors Figure: 2 With ZS capacitors + Without Feeder Capacitors Figure: 1 With ZS capacitors Waipapa 11kV Bus- Signal Levels 0.00 2.00 4.00 6.00 8.00 10.00 12.00 14.00 16.00 WPA011_1 WPA011_3 11kV Bus V o l t a g e
( L - N ) w/o WPA caps w/o WPA caps + China Caps with WPA caps + Open Bus with WPA + China Caps + Open Bus with WPA caps + No Fdr caps + Open Bus with WPA caps + Close Bus with WPA + China Caps + Close Bus with WPA caps + No Fdr Caps + Close Bus Signal Levels at Waipapa 11kV Bus Effect of Network Load on Network Impedance 5.307 8.52 WAP011_3 53.14 41.28 WAP011_1 Open Bus Open Bus Average Load Maximum Load Impedance for 317Hz Signal Name Max. Load Avg. Load Effect of Network Load on Signal Levels Waipapa 11kV Bus- Signal Level (Max Vs Avg Load) 0.00 2.00 4.00 6.00 8.00 10.00 12.00 14.00 16.00 18.00 WPA011_1 WPA011_3 V o l t a g e
( L - N ) w/o WPA caps w/o WPA caps + Avg Load with WPA caps + Open Bus with WPA caps + Open Bus + Avg Load with WPA caps + Close Bus with WPA caps + Close Bus + Avg Load Ripple Signal Amplification on the Feeder 4 steps, 100Amps Voltage Regulator 22/11kV Transformer 200kVAr Fixed Capacitor Bank Rangiahua Feeder- Kaikohe Substation Conclusions - Network impedance and Ripple Signal level depends on: Network configuration Network Loading. - Parallel Resonance occurs close to the injected ripple injection frequency (317Hz). - Addition of + x 8+0kvar capacitors will change the Network impedance significantly. - Feeder and power factor correction capacitors decrease the signal level on the Network but the ripple signal amplifies across them. - Ripple signal amplification occurs on the distribution feeder. - Ripple signal amplification can cause adverse effects on customer equipment. - !nstallation of new Shunt capacitors should be investigated where ripple signals are used for load control purposes. Future Work DigSilent Model should include Distribution Transformers and LV Network. The Model should also include all the spur lines in the Network. The Signal levels should be verified by taking field results. Thank You Questions are Welcomed.