PROFIBUS Design and Good Practices

Agenda PROFIBUS Family Communication Medias Topologies Cable length Devices Rules Installation Rules

Introduction PROFIBUS-DP PROFIBUS-PA Installations and Best practise

Troubleshooting Training

PROFIBUS Family
3

Agenda PROFIBUS Family Communication Medias Topologies Cable length Devices Rules Installation Rules Troubleshooting Training
2 3 4 5 6 7 8 31 3 4 2 1 1

DCS

ERP MES Ethernet backbone

PROFIBUS PA

PROFIBUS DP PROFIBUS PA
6 7 8 31

PA coupler PA link
Author / Title of the presentation

PROFIBUS-DP/PA
Specification by 13 industrial firms and 5 university institutes 1988 German DIN Standard 19245 1996 European Fieldbus Standard EN 50170 2000 International Standard IEC 61158

Agenda PROFIBUS Family Communication Medias Topologies Cable length Devices Rules Installation Rules Troubleshooting Training

Profile PROFIBUS-DP (high speed)

IEC 61158 communication RS485 physic or fiber optic max. 12 MBaud IEC 61158 communication

Profile PROFIBUS-PA current supply over bus IEC 61158-2 physic 31,25 KBaud

PROFIBUS - Transmission Technologies


Controller

Agenda PROFIBUS Family


PROFIBUS DP
> 10km FO RS485 Fiber optic RS485

Per PROFIBUS DP Master system max. 125 DP slaves OLMs (Optical Link Module) for wide distances with high EMC stability Electrical networks can be extended by means of repeaters (segments)
max. 32 DP slaves per
Coupler RS485iS

Communication Medias Topologies Cable length Devices Rules Installation Rules Troubleshooting Training

Repeater 1,200 m

segment

RS485iS DP/PA 1.900 m Non-Ex 1.000 m 1.000 m

RS485iS couplers for intrinsically safe PROFIBUS DP in EX areas PROFIBUS PA for direct connection of field devices with power supply via bus

PROFIBUS PA (MBP IS)

PROFIBUS - Functional levels


Functional Levels DP-V2 extension: Peer Slave Communication (Publisher / Subscriber) Isochron Mode (Equidistance) Clock Synchronization & Time Stamps HARTon DP PROFIdrive Redundancy

Agenda PROFIBUS Family Communication Medias Topologies Cable length Devices Rules Installation Rules Troubleshooting Training

Cyclic Data Exchange between PLC and Slave Devices GSD Configuration Diagnosis

> 90%
Time

DP-V0

field decice

DP-V1 extension: Acyclic Data Exchange between PC or PLC and Slave Devices Integration within Engineering: EDD and FDT Portable PLC Software Function Blocks (IEC 61131-3) Fail-Safe Communication (PROFIsafe) Alarms

PROFIBUS - Master - Slave


Master (class 1)
Central control Cyclical data exchange with the slaves Acyclical data exchange with the slaves Active with a high priority

Agenda PROFIBUS Family Communication Medias Topologies Cable length Devices Rules Installation Rules Troubleshooting Training

Master (class 2)
Engineering tool for commissioning and parameter settings of the slaves Acyclical data exchange with the slaves Active with a low priority

SPS

Master (class 1)

Master (class 2)

PROFIBUS Bus slaves (passive)

PROFIBUS DP/PA - Deterministic communication

Deterministic communication according Master/Slave principle:


Agenda PROFIBUS Family Communication Medias Topologies Cable length Devices Rules Installation Rules Troubleshooting Training

Parameterized time behaviour of the bus and defined reaction times of the slaves are permanently guaranteed!
Master class 1 Master class 2
cyclic
acyclic acyclic

cyclic

1 t

2
PROFIBUS DP

Read measured values, write manipulated variables

Read/write parameters and measured values of a slave

PROFIBUS PA

Slave 1

Slave 2

Configuration of the bus (GSD file)

Agenda PROFIBUS Family Communication Medias Topologies Cable length Devices Rules Installation Rules Troubleshooting Training

Bus master (Class 1 Master) needs the technical data of the attached field device.
The GSD file describes the general and device specific communication characteristic of a PROFIBUS device: sheet
Supported transmission rates Length of the transferred I/O data Type of the field device (compact slave, modular slave)
ion urat nfig s - Co Bu

PROFIBUS Configurator

SPS

PROFIBUS

Agenda PROFIBUS Family Communication Medias Topologies Cable length Devices Rules Installation Rules

Introduction PROFIBUS-DP PROFIBUS-PA Installations and Best practise

Troubleshooting Training

PROFIBUS Family - Principle


11

Agenda PROFIBUS Family Communication Medias Topologies Cable length Devices Rules Installation Rules Troubleshooting Training

To create hierarchy in the network, PROFIBUS defines 2 types of stations: active (masters) and passive (slaves).

master
0 1 0 1 0

commands
0 1 0 1 0

slave

responses

network

At least 1 master is mandatory. PROFIBUS networks allow multiple masters. In total 127 stations can be addressed (masters + slaves).

Communication Medias
12

PROFIBUS Supports 3 transmission media


Agenda PROFIBUS Family Communication Medias Topologies Cable length Devices Rules Installation Rules Troubleshooting Training
Coupler Coupler

RS 485 2-wire CU-cable for general purposes

Fiber Optic Highest EMC protection and wide distances

MBP-IS 2-wire CU-cable with the option for power over the bus and Ex-protection

Fiber optic cable

Total Overview of the Technology


13

Agenda

Identification Systems Identification Systems

PA Devices PA Devices

V2.0 and V3.0 V2.0 and V3.0

Encoder Encoder

SEMI SEMI

Topologies Cable length Devices Rules Installation Rules Troubleshooting Training


Comm. App. Profiles I

Common Application Profiles (optional): Common Application Profiles (optional):

PROFIsafe, Time Stamp, Redundancy, etc. PROFIsafe, Time Stamp, Redundancy, etc.
IEC 61158/61784
Descriptions (GSD, EDD) Descriptions (GSD, EDD) Tools (DTM, Configurators) Tools (DTM, Configurators)

PROFIBUS DP
Fiber Fiber Optics: Optics:
Glass Multi Mode Glass Multi Mode Glass Single Mode Glass Single Mode PCF // Plastic Fiber PCF Plastic Fiber

FDL + DPV0...V2

Physical Layer

RS 485 RS 485 RS 485-IS RS 485-IS

NRZ NRZ Intrinsic Safety Intrinsic Safety

MBP MBP MBP-LP MBP-LP MBP-IS MBP-IS

Manchester Bus Powered Manchester Bus Powered Low Power Low Power Intrinsic Safety Intrinsic Safety

Integration Technologies

App. Profiles II

PROFIdrive PROFIdrive

RIO for PA RIO for PA

Communication Medias

Weighing & Dosage Weighing & Dosage

PROFIBUS Family

PROFIBUS DP Topologies - General


14

PROFIBUS communicates over a two wire bus structure.


Agenda PROFIBUS Family Communication Medias Topologies Cable length Devices Rules Installation Rules Troubleshooting Training
T

listen, taking over and answering

sending listen

0 1 0 1 0

1 43

117
T

5
listen listen

Devices are addressed through a network address (0..126). Devices are coupled in parallel to the bus. Devices can be hot swapped and position does not matter. Each segment is terminated at both end with an active termination Spurs should be avoided as length is very limited

PROFIBUS DP Topologies - Repeaters


15

Single Repeaters
Agenda PROFIBUS Family

PROFIBUS Hubs

Topologies Cable length Devices Rules Installation Rules Troubleshooting Training

Segment 1

Communication Medias

Stations

Backbone

Segment 2

Stations Segment 1 Segment 2

Benefit: Isolate part of your network from EMC/Noise

PROFIBUS DP Topologies Fiber Optic


16

Classic Topology
Agenda PROFIBUS Family Communication Medias
Coupler

Ring Topology

Fiber optic cable


Coupler

Topologies Cable length Devices Rules Installation Rules Troubleshooting Training


Coupler Coupler Coupler Coupler

Fiber optic cable

Benefits: Long distances and EMC/Noise isolation

PROFIBUS DP Topologies - Wireless


17

Connect your slaves through wireless couplers


Agenda PROFIBUS Family Communication Medias Topologies Cable length Devices Rules Installation Rules Troubleshooting Training
Wireless gateway Wireless gateway

Wireless gateway

Wireless gateway

Segment

Wireless DP Device

Wireless PN Device

PROFIBUS DP Topologies - Redundancy


18

Agenda PROFIBUS Family Communication Medias Topologies Cable length Devices Rules Installation Rules Troubleshooting Training
RS 485 RS 485
glasvezel coupler glasvezel coupler

RS 485

RS 485
coupler

RS 485
coupler

RS 485

RS 485

1.0

Transmission speed (baudrate)


19

Agenda PROFIBUS Family Communication Medias Topologies Cable length Devices Rules Installation Rules Troubleshooting Training

PROFIBUS offers the user the possibility to choose from 10 transmission speeds (RS 485).
9,6 19,2 45,45 93,75 9,6 19,2 45,45 93,75 187,5 500 1500 3000 6000 12000 kbps 187,5 500 1500 3000 6000 12000 kbps

Remarks: The transmission speed determines the maximum cable length and vice versa. The transmission speed has to be set identically at all the masters on the same bus. Most slaves detect the baudrate automatically. Because of economic and technical reasons some products do not support all transmission speeds. Some older products do not support 45,45 kbps.

2.1

PROFIBUS DP Cable Length


20

Baudrate vs Cable Length


Agenda PROFIBUS Family Communication Medias Topologies Cable length Devices Rules Installation Rules Troubleshooting Training
Baudrate (kbit/s) Segment length (m) Segment length (feet) 9.6 19.2 45.45 93.75 187.5 500 1500 3000 6000 12000

1200

1200

1200

1200

1000

400

200

100

100

100

3940

3940

3940

3940

3280

1310

656

328

328

328

3 baudrate transitions in which the cable 3 baudrate transitions in which the cable length reduces with more than 50 %. length reduces with more than 50 %.

These lengths are defined for 1 segment with 32 bus loads!

2.1

Device Rules - Network


21

PROFIBUS Address Map


Agenda PROFIBUS Family Communication Medias Topologies Cable length Devices Rules Installation Rules Troubleshooting Training

0 1..2 3..125 126 127

Service-, diagnosis- and programming tool Masters (class 1) Slaves (total 123 or 124) Address for: Set Slave Address Broadcast address

Most configuration tools block address 0 and 126 for slaves. Address 126 is a default address for slaves with software address settings. Address 127 is a broadcast address (only visible with a busmonitor). Maximum 124 DP slaves per bus!!!!!!!

2.0

Device Rules - DP Segments


22

Maximum 32 loads per RS485 segments


Agenda PROFIBUS Family Communication Medias Topologies Cable length Devices Rules Installation Rules Troubleshooting Training

Max 30 Stations

Max 31 Stations

Segment 1

Segment 2

Devices that generate new segments:


Repeaters Fiber Optic Couplers Wireless gateways

After these devices, PROFIBUS segment rules are the same.

Agenda PROFIBUS Family Communication Medias Topologies Cable length Devices Rules Installation Rules

Introduction PROFIBUS-DP PROFIBUS-PA Installations and Best practise

Troubleshooting Training

PROFIBUS-PA Network layout


Layer Model (ISO Standard since 1983)

Agenda PROFIBUS Family Communication Medias


PROFIBUS DP

Controller (Master)

7
Remote IO

Application Presentation Session Transport Network Data Link

DPV0 .. 2

Topologies Cable length Devices Rules Installation Rules Troubleshooting Training


IEC 61158-2 Manchester Bus Powered (MPB)
I IB + 9mA IB IB - 9mA t 1 0 1 1

6 5 4 3 2 1

Link

FDL Physical MBP

Gert

PROFIBUS PA

PROFIBUS PA Topologies - Overview


25

Agenda PROFIBUS Family Communication Medias Topologies Cable length Devices Rules Installation Rules Troubleshooting Training
24 V

+
DCS/PLC

PROFIBUS DP
Junction Box

DP/PA-Link

Segment PROFIBUS PA

PROFIBUS PA Topologies - Redundancy


26

Coupler Redundancy
Agenda PROFIBUS Family Communication Medias Topologies Cable length Devices Rules Installation Rules Troubleshooting Training
Bus termination Automatic bus termination
PROFIBUS DP

Coupler-Redundancy
M

DP/PA-coupler, redundant (M = master)

IM 153, redundant

AFS

Active Field Splitter PROFIBUS PA

PA Ring Redundancy
PROFIBUS DP

Coupler-Redundancy
M

DP/PA-coupler, redundant (M = Master) AFD

Media redundancy based on a ring topology


AFD Active Field Distributor

IM 153, redundant

PROFIBUS PA AFD AFD

Higher availability with Redundancy

Agenda PROFIBUS Family Communication Medias Topologies Cable length Devices Rules Installation Rules Troubleshooting Training
Short-circuit or wire break on trunk line

DP/PA Link
M

Field Device Coupler, redundant (M = master)

PROFIBUS PA

PA Junction Box

Junction Box

Automatic bus termination

Automatic Termination
Automatic bus termination enables unique online changeability
Agenda PROFIBUS Family Communication Medias Topologies
Bus termination Automatic bus termination

FF Link

Add new devices Enhance line Enhance ring

Cable length Devices Rules Installation Rules Troubleshooting Training

PROFIBUS PA

AFD

AFD

AFD

AFD

AFD

There is no need to reserve spare ports of the AFDs !

Agenda PROFIBUS Family Communication Medias Topologies Cable length Devices Rules Installation Rules

Introduction PROFIBUS-DP PROFIBUS-PA Installations and Best practise

Troubleshooting Training

Installation rules
30

Grounding & Shielding


Agenda PROFIBUS Family Communication Medias Topologies Cable length Devices Rules Installation Rules Troubleshooting Training

PROFIBUS is digital communication, not 4-20mA Ground at both end Ungrounded shield has no effect

Installation rules
31

Power Lines
Agenda PROFIBUS Family Communication Medias Topologies Cable length Devices Rules Installation Rules Troubleshooting Training

Digital communication is sensitive to power lines Watch out for cable runs in trays Respect distances for air separation

Power line too close

Power line are removed

Installation rules
32

Some examples with Power Lines


Agenda PROFIBUS Family Communication Medias Topologies Cable length Devices Rules Installation Rules Troubleshooting Training

Installation rules
33

Proper wiring and component selection


Agenda PROFIBUS Family Communication Medias Topologies Cable length Devices Rules Installation Rules Troubleshooting Training

Wiring and cable termination is critical Wrong component selection leads to bad installation Take environment in account (humidity, sunlight)

Troubleshooting
34

Recognizing bad installations


Agenda PROFIBUS Family Communication Medias Topologies Cable length Devices Rules Installation Rules Troubleshooting Training

You cannot use the multimeter, this is digital comm. Specific tools are required

Cable Tester

Oscilloscope Analyzer

Find wiring errors such as short circuit Identify missing termination and EMC Capture error messages and find the source of your system shutdown Cost and time saving by using the right tools!

Troubleshooting - Oscilloscope
35

Good signal
Agenda PROFIBUS Family Communication Medias Topologies Cable length Devices Rules Installation Rules Troubleshooting Training

Missing termination

Troubleshooting - Analyzer
36

Capture all PROFIBUS messages


Agenda PROFIBUS Family Communication Medias Topologies Cable length Devices Rules Installation Rules Troubleshooting Training

Useful for random errors Shows underlying conditions Device diagnostic

Training
37

Certified Training by PROFIBUS International


Agenda PROFIBUS Family Communication Medias Topologies Cable length Devices Rules Installation Rules Troubleshooting Training

Benefits
Avoid basic errors that cost time and money Quality assurance for design and commissioning Faster project delivery Better installation, longer operation

Various courses available


PROFIBUS Certified Engineer PROFIBUS Certified PA Module PROFIBUS Certified Installer PROFINET Certified Engineer

Certified by

38

The end Thank you for listening