BBP_comparison_e_v1.2.

xls

PTD EA13/Fu

17.09.2007

Product Manufacturer Country Internet Name Measuring technique Measuring principle

7 SS52 Siemens D www.siprotec.com Distributed bus bar/Breaker failure Protection SIPROTEC 7 SS52 low impedance measurement; fully numeric; stabilized differential current measuring principle, realtime processing, check zone, 3 self adapting algorithms (Fourier, 1 of 1, 2 of 2), 50/60 Hz, 20 Samples/cyc, single phase measurement (phase segregated), separate earth fault characteristic, BU synchronized by CU each ms 3 of 3 tripping criterium, (even/odd samples+ check zone); overcurrent criterion, add. criteria by separate relay/ BI release < 15 ms (I > 4 Iset), < 25 ms (I < 4 Iset), independent of configuration Ts > 2 ms (stability;) Ts > 3 ms (tripping) basically not limited, matching via software NC(89B) AND NO(89A) decentralized, 1 CU with BUs in star configuration (2 fiber-optic cables)

REB 500 (sys) ABB S/CH www.abb.com Numerical busbars and circuit-breaker failure protection low impedance measurement; fully numeric; stabilized differential current principle; phasor processing;

P740 Areva T&D/(former Alstom) F www.areva-td.com Numerical bus bar Protection low impedance measurement; fully numeric; realtime processing (like 7SS52!) saturation detector; stabilized differential current principle; check zone, ground fault characteristic; 2.4kHz sampling rate BU synchronized by CU each ms

DRS-BB VA TECH A www.sat-automation.com Distributed digital busbar protection DRS-BB low impedance measurement; fully numeric; stabilized differential current principle; check zone; 16.7/50/60 Hz; Measurement preprocessing in BU; saturation detector, BU synchronized by CU each ms; single phase measurement; FFT algorithm for earth fault characteristic diff. current discrim zone (CU slave unit) & diff. current check-zone (CU master unit) & fast overcurrent criterion (BU) 15 ms at I> 4 Iset; < 22 ms at 1.1 Iset (50/60Hz) or < 25 ms at 1.1 Iset (16.7Hz), fast trip relays Ts > 1 ms (stability;) Ts > 3 ms (tripping) basically not limited, matching via software NC(89B) AND 2x NO(89A)

SEL-487B Schweitzer USA www.selinc.com Bus bar and Breaker Failure Protection, Automation and Control system low impedance measurement; fully numeric; stabilized differential current principle; check zone optional; 50/60 Hz; Saturation detector 2nd characteristic for external faults; direction measuring by phase comparison with ref. feeder);

Tripping criteria

differential current, current direction comparison, differential current, check zone; overcurrent overcurrent criterion, check zone criterion; add. criteria by separate relay/ BI release 20...30 ms (I > 5 Iset) (according to data sheet; "formerly longer"); dependent on no. of bays (?) Ts > 2 ms n.a. NO/NC, adjustment required decentralized, 1 or more CU with BUs in star configuration (2 fiber-optic cables); up to 18 BU on one CU, quadruple bus plus transfer bus 32 59 (in groups of 9) CU 19", 6 HE BU: 1/2 19" U . 1/3 19" (central. arrangement) typ. 15 ms (data sheet), resp.12-18 ms

differential current AND (direction element OR fault detec. Logic); check zone, overcurrent, undervoltage < 20 ms (50 Hz) / < 16.7 ms (60 Hz) "subcycle tripping" (including high speed output contact closure) Ts > 2 ms 10:1 NC(89B) AND/OR NO(89A)

Tripping time

Current transformer saturation CT conditions, ratio Isolator auxiliary contacts (NC=89B; NO=89A) Topology

Ts > 2 ms 40:1 (sep. CT calculation required) n.a. decentralized, 1 CU with BUs in star configuration (2 fiber-optic cables)

decentralized, CU and BUs on an optical double- centralized ring

System performance

Busbars Bus zones Feeders

up to 12 12 48, (incl. couplers), groups of 8 5 disconnectors CU 7SS522: 19", 6 HE BU 7SS525: 1/3 19" of 6 HE (flush mounting) BU 7SS523: 1/2 19" of 6 HE (flush/cubicle mounting) Weidmller modul blocks (SIPROTEC V3-relays) dedicated PCB, double Eurosize

triple bus+? 8 (formerly 16!) 28 (in groups of 4;) (2 CUs linkable?) CU P741: 19 " (80 T), 4 HE BU P742: 8 " (40 T), 4 HE BU P743: 12 " (60 T), 4 HE

Construction

Components, mechanics (WxHxD)

no limit in topology (not limited for standard topologies), limited to 16 (24) zones 16 80, 6 disconnectors CU: 19", 9 HE, BU (LBB): 1/4 19", 6 HE, BU (CBB): 1/2 19", 6HE Phoenix-Contact

n.a. ("for multiple BB") 2 (1 unit) or 6 (3 units) 6 (1 unit)/18 (3 units) 19", 16"/9 U, 9"

Terminals Technology

PHOENIX Combicon? dedicated PCB, double Eurosize MiCOM series; presumable system I/Os; same displays with CU and BU inflexible; Expansion causes new configuration by manufacturer 4 X J (1/5A selectable)

Screw type terminals Standard Main board+to 4 interface boards

Modularity, flexibility Quantity structure hardware Analog inputs

easy to extend later on, no precautions, few type of components as spare parts 3+1 x J (1A, 5A)

inflexible; Expansion causes new configuration by manufacturer 4 xJ (1/5A selectable) 4 xU (opt.)

CU: double Eurosize PCB, system " MRB" BU: system " DRS-Light"; add. comm.-board DSR-SR Expansions by a new configuration by means of "graph theory" 1A / 5A

Basic equipment with 4 I/O boards, expandable 18 x J (1A, 5A) not adjustable; 3 x U

Binary inputs

CU: 12 BI; 16 DO BU 7 SS523: 20 BI; 12 DO BU 7 SS525: 10 BI, 11 DO BI, DO partly routed CU: LCD of 4 x20; 34 LED; 24 keys BU: LCD of 4 x16; 18 LEDs; 12 keys (7 SS523)

CU: 12/24 BI; 7 CR, 2 AR BU: 16 BI; 8 CR, 8 AR BI threshold by FW adjustable; 2s root

CU: 8 BI, 8 DO BU P742: 16 BI, 8 DO BU P743: 24 BI, 21 DO no roots

Display, keys

Power supply

Functionality

Busbar protection 87 BB (/) P/(87 BB/N)/(87 CZ) Breaker failure (50 BF) Voltage protection (27/59) Supervision Disturbance recording

CU: LCD of 2 x16; 12 LEDs, 7 keys BU P742: LCD of 2 x16; 12 LEDs, 7 keys BU P743: LCD of 2 x16; 12 LEDs, 7 keys CU: 3 ranges (48-60 VDC, 110-125 VDC, 220-250 CU and BU: 1 range (48-250 VDC); Redundancy 3 ranges (24-54 VDC, 48-125 VDC/30-100 VAC, CU:4 ranges (24 V, 48-60 VDC, 110-125 VDC, VDC) possible 110-250 VDC/100-240 VAC) 220-250 VDC) BU: 1 range (48-250 VDC) BU: 2 ranges (20-72 VDC, 80-350 VDC or AC rms 50/60Hz) x/x/x x/x/x/x/x x/x/x

BU: LCD, 4 x18; 6 keys; 3 LEDs; detachable CU: LCD, 4 x18; 6 keys, 3 LEDs

CU: 8 (16, 24, 32) BI; 6 (12, 18) BO (15x1NO), 3 AR BU (LBB): 15 BI, 3 CR (2x1NO, 1x2NO), 1 AR BU (CBB): 23 BI, 8 CR (4x1NO, 4x2NO), 1 AR 6 isolators possible, add. BI via CAN bus CU: LCD 2 rows; 10 LEDs, 6 keys BU: LCD 2 rows; 10 LEDS, 6 keys

Basic equipment: 7 BI; 8 DO (5NO, 3ChO) 4 x I/0, each: 18 BI (partly rooted); 2 DO (2NO); 6 DO high speed (2NO)

LCD 128 x128 pixels (3"x3"); 6 keys; 18 LEDs; 8 function keys/LEDs; 3 ranges (18-60 VDC, 38-140 VDC, 85-300 VDC/85-264 VAC)

x/-/ x

2 stages; very short reset time 2ms (unbalancing) -/-

2 stages (opt.) x

2 stages -/-

2 stages; reset time <15 ms -/-

ct circuits, internal trip circuits 1 kHz; max. 5 s; 8 records 3xJ (feeder) and Idiff/Istab (zones)

x max. 2.4 kHz; max. 1.5 s (2.4 kHz)/6 s (0.6 kHz) 4xJ, 4xU (feeder)

open CTs (delta algorithm?) 1.2 kHz; 20x10.5s s (BU), 8x1.2 s (CU), 8 analog, 32 digital channels (CU), 4 analog, 32 digital channels (BU) Test function (simulation of the BI)

ct circuits (3 different principles), internal trip circuits BU (feeder) 4 records a' 75 cycles; CU max. 10 s (zones)

2 stages (definite time elements) internal; external 2 stages (27/59) negative sequence system, zero-sequence system CT fault 24 s/cyc; 15 cyc; 20 records (no Idiff/Istab)

Automation Other

coupler with 1 or 2 CTs

Test generator (simulation of the BI and DO)

coupler with 1 or 2 CTs

programmable control functions (with SELogic) 6 parameter sets Coupler needs 2 CT cores/ bays

Back-up protection 50/51 (/P); 67P 50/51 (/N); 67N Other functions

50/51P, 2-stage 50/51N, 2-stage

REB 500sys: Distance protection REL316 or transformer diff RET316 integrated

50/51P, 2-stage 50/51N, 2-stage

End fault protection Overcurrent release Sensitive characteristic (e.g. earthfault)

End fault protection Overcurrent release Pole discrepancy supervision Ground fault Diff. protection (effectiveness doubtful (BEWAG)!)

Ordering form

order by order code, "loose relay"

HW order by order code, configuration and tests done plant specific

End fault protection CB control, CFC 4 parameter sets CT supervision by zero-sequence system Trip circuit supervision with CFC (how?) Test mode with I/O stimulation Sensitive earthfault characteristic HW order by order code, configuration and tests done plant specific

50/51P, 2-stage def.time OR inverse time with highset; 50/51N, 2-stage def.time OR inveret time with highset; End fault protection Overcurrent release optional electrical lockout

50P 1-stage; 51P 1-stage without/with disk emulation

Station battery monitoring/PQ (analog input) end fault protection (SELogic)

order by order code and single-line diagram

HW order by order code

DBN ZIV E www.ziv.es DBN bus bar of differential Protection terminal low impedance measurement; fully numeric; stabilized differential current principle; check zone optional; 50/60 Hz; Saturation detector

RED 521 ABB S /CH www.abb.com General differential protection fully numeric; stabilized differential current principle; 50/60 Hz

REB 670 ABB S / CH www.abb.com Busbar differential protection IED fully numeric; stabilized differential current principle; 50/60 Hz

GRB100 Toshiba TM T & D J www.tmt-d.com Numerical centralized bus bar protection relay low impedance measurement; fully numeric; stabilized difference current principle; saturation detector; 50/60Hz; checking zone and undervoltage (opt)

B-PRO nxtphase CAN www.nxtphase.com bus protection relay (three phase or single phase) low impedance measurement; fully numeric; stabilized difference current principle; saturation detector;

B90 GE CAN www.Geindustrial.com/multilin Bus differential relay low impedance measurement; fully numeric; stabilized difference current principle; saturation detector; additional direction criterion at saturation (2 out-of 2), 64 s/C;

B30 GE CAN www.Geindustrial.com/multilin Bus differential relay low impedance measurement; fully numeric; stabilized difference current principle; saturation detector; additional direction criterion at saturation (2 out-of 2), 64 s/C;

differential current , undervoltage

differential current

differential current

differential current, check zone, undervoltage criterion

differential current , undervoltage, overcurrent

differential current AND direction element (dynamically controlled by saturation detector)

differential current AND direction element (dynamically controlled by saturation detector)

12-18 ms

12-19 ms

less than resp. typ. 1 period?

8-20 ms typical

typ. 16 ms

typ. 16 ms

? ? ? decentralized, 1 CU with BUs in star configuration (2 fiber-optic cables)

2 ms 10:1 89B ( AND 89A, adjusted) centralized, 1 (3-ph) or 3 equipments (1-ph)

2 ms 10:1 89B ( AND 89A, adjusted) centralized, 1 (3-ph) or 3 equipments (1-ph)

n.a.

n.a. adaptable

Ts > 2 ms 32:1; range 1...50000 A n.a. centralized, 3 equipments "IED" (each singlephase), additional equipment for BFP or I/O expansion, connection via optical doubleended ring 3-BB, transfer bus 4 8, 16, 24 19" , 180 mm (3 U), 250 mm

Ts > 2 ms

n.a.

n.a.

4-BB 4 28 (14+14); plus 4 x voltage measurement CU: 19", 4 HE BU: 19", 2 HE

1-BB or 2-BB 1 or 2 3-phase up to 6 feeders 1-phase up to 18 feeders (3 equipments) CU: 19", 6 HE No drawout of current inputs

1-BB or 2-BB 1 or 2 3-phase up to 8 feeders 1-phase up to 24 feeders (3 equipments) CU: 1/1 resp. 1/2 19", 6 HE

centralized (in the past also decentralized!), 1 centralized, 1 equipment (3-ph) or 3 CU with Bus in star configuration (2 fiber-optic equipments (1-ph) cables) only up to 8 m 2 feeders per BU 2-BB +transfer bus 1 1 to 4 32 in groups of 8 CU: 3/4 19", 6 HE, 310 mm BU: 1/2 19", 6 HE, 310 mm 1 (+1 transformer) 6 or 18 19", 133 mm (3U), 305 mm

centralized

1 or 2 (2 xB30) 1 6 o.Spg. 5 m/. Spg. 19" , 180 mm (3 U), 250 mm

Screw type terminals

see IED 670 System data

n.a. System family GR, double Eurosize boards Universal relay (UR) platform, Universal relay (UR) platform,

Boards (uP, AIM, BIM, BOM) of REx 5xx-System see IED 670 System data

Expansions by manufacturer DBP-B: 3 x J? (1 A, 5A) DBP A: 3 x U? CU: 7/14 BI, 7/14 DO BU: 8/16 BI, 2 CR (2NO)+4 CR ??, 8/16 AR

Functionality by ordering size fixed (9 or 18 X J) 1A/5A adjustable 18 x J 16 (3-ph) / 32-48 (1-ph) BI 24 DO not marshallable

see IED 670 System data 1A or 5A 12/24 x J see IED 670 System data

Expandable CU: 0/6/12 x U BU 2 x3 x J (1 A, 5A) not switch-selectable CU: 5 BI; 13 DO BU GRB100 B100: 2 x13 BI; 2 x6 DO BU GRB100 B200: 2 x13 BI; 2 x10 DO BI and DO partly rooted CU: LCD 4x40; 8 LED; 19 keys; 3 test jacks BU: 1 LED 3 ranges (48 VDC, 110-125 VDC, 220-250 VDC), no 60 VDC

no 18 current, 3 tension (three-phAe) 54 current, 9 tension (single-phAe) 9 or 27 BI;

6 plug-in slots, numerous I/O boards (U, I, BI, DO, DO fast) 3 x8 J (1A/5A) resp. 3 x7 J/1 x3 U per equipment up to 96 BI, up to 48 DO

6 plug-in slots, numerous I/O boards (U, I, BI, DO, DO fast); practically only 3 I/O 18 J (1A/5A) bzw. 15 J/3 U up to 96 BI, up to 48 DO

CU: 13 LEDs, display, 20 keys BU: 5 LEDs, 1 key 3 ranges (24-48 VDC, 110-125 VDC, 220-250 VDC), no 60 VDC

attached operating panel 3 LED, 4 x16 LCD, 6 keys 2 ranges (110-125 VDC, 220-250 VDC), no 60 VDC

see IED 670 System data

14 or 42 there strappable

LCD 2x20; 14 LED fixed, 48 LED marshallable, 16 function keys marshallable, 22 keys 2 ranges (24-48 VDC, 125-250 VDC/AC), no 60 VDC !

LCD 2x20; 14 LED fixed, 48 LED marshallable, 16 function keys marshallable, 22 keys 2 ranges (24-48 VDC, 125-250 VDC/AC), no 60 VDC !

2 ranges (24-60 VDC, 90-250 VDC)

x/-/x

x/-/-

x/-/x

x/-/x

1 characteristic

1 stage 27

2 stages (opt.)

2 stages (opt.) Undervoltage 1-stage (opt.)

2-stage, int. and ext., very simple, no. BI small over/undervoltage, 2-stage

x/x/x 1 characteristic, 2-folded 87 BB/N with separate B90 2 stages (opt.) Undervoltage, 1-stage

x / x / x (!) 1 characteristic, 2-fold folded

Undervoltage, 2-stage

CT fault

open CT, Idiff, Checkzone powerful (see IED 670 System data)

CT fault Isolator (vague description) 400,800 ms; 3 records at 800 ms each, 32 analog and digital signals, no Idiff/Istab no in earlier catalog sheets the system was introduced as a decentralized system! CT dimensioning in accordance with high impedance rule

Voltage transducer (ANSI 60 loss of potential) 96 s/cyc, max. 15 records, 2s

CT fault, ext. trip circuits up to 64 s/cyc

CT fault, ext. trip circuits up to 64 s/cyc

3 parameter sets

time synchro by BI CIM: comm.board with ABB-AIS (opt. transducer)

no autoreclosure (79) for BB faults 6 parameter sets separate sensisitive characteristic (as with 7SS52!) 50/51 4 stages (opt.)

using FlexLogic 2 inputs for transformer protection; Frequency protection (81 O/U), neg. sequence overcurr. (46/50/51/67); sensitive definite time elements (50 LS, > 0.1A) 50P,51P,67P, 50 N, 51 N, 67N 50, 51, 1-stage

using FlexLogic Check zone by ext. parallel connection of separate CTs and use of a current input, not stabilized!

50

50, 51, 2-stage

Undervoltage release

endfault protection checkzone

End fault protection

HW order by order code

Order by order code

Order by order code

HW order by order code; FW n.a.

by order code, "normally ordered as engineered product"

by order code, "normally ordered as engineered product"

Remote communication

IEC60870-5-103, DIGSI-protocol via modem, IEC61850

IEC61850-8-1, IEC60870-5-103, LON

Internal protocol "Courier"/k-Bus; convertable into IEC60870-5-103 IEC61850-8-1

Local operation/ program Configuration

DIGSI4 (engl/ge/fr/sp/it/rus) Program REBWIN especially for REB 500; CU centralised resp. decentralised controllable also by BU RS232/RS485/Ethernet universal software, freely graphically configurable, Configuration only by ABB possible integrated in DIGSI, easily changeable by user all voltage levels, all types of system groundings

Application range

MiCOM S1; (engl/fr/ge/span) centralized or dezentralized RS232 protocol "Courier" Configuration only by Alstom staff possible; tool "TOPOLOGY "; intensive individual test required all voltage levels, all types of system groundings all voltage levels; high-impedancely earthed

IEC60870-5-103, DrsWin-protocol via modem or 4 x RS232 (ASCII, specific); DNP3.0 telnet-server IEC61850-8-1 1 x Ethernet (FTP, telnet) no IEC61850 interface Inter equipment communication by means of SEL "Mirrored bit" Drs-Win4 (engl/ge/fr), BU RS485 SEL-5601 Analytic Assistant for analysis, PC CU RS232, communication on ASCII base Plant image generated by means of "graph AcSelerator SEL-5030 for configuration (ASCII, theory", generation and modification with tabular); isolator replica with an individual logic maintenance software ELTAS (only internal CU) all voltage levels, all types of system groundings n.a.

Highlights

security by 3-of-3 trip decision, incl. check zone, add. OC release, short tripping times, low aux contact requirements, modular and flexible system, comfortably operated by DIGSI KEMA (particularly algorithms)

additional tripping criterion "current direction"; redundant power supply;

Certification Price (list)

Redundancy by optical double-ring and 3-of-3 trip decision (discrim.zone&check-zone&OC release); comfortable and simple fully graphical operation software DrsWin functionality and algorithms by KEMA; EMC by Austrian research centers ARSENAL n.a.

Price flexible zone assignment (e.g. as check zone)

n.a. from USD 6500 (basic unit)

very project dependent, no list prices; range 7SS52 -20% ... +100% (mostly 20%) Introduction Market share References Advantage 1997 high-end : 40-60 % (country dependent) 1000 Systems worldwide well accepted, user friendly system, extensive basic functionality, experiences since 1989 with 7SS50 1995

Position in the market

February 2003 <5% 150 (Sept2006); not accepted at RWE no-one; P470 is "a good copy of the 7 SS52" to large portions; BI voltage programmable

March 2000 high-end : <5 % (country dependent) 78 (6/2005); (incl.11x16.7Hz)

2003 ? some cheap (at least for small plants), CFC, compact construction

Position vs 7 SS52

Disadvantage

High-end: 40-60 % (country dependent) worldwide high market acceptance, comparable with 7SS5; many additional functions; integrated distance/transformer diff protection (REB500sys), additional tripping criterion "current direction" (Spec argument!) Many specs ares influenced by ABB, no integrated slower tripping times; closed system with a high voltage protection, no integrated distance manufacturer relationship (configuration, protection commissioning, expansion "only by ABB"); isolator aux contacts require adjustment Undervoltage as additional tripping criterion by separate voltage relay (by zone); Redundant power supply as the one and only redundant component is senseless as it has similar reliability. Check zone should be integrated because of faulty There is not a single bus fault known that would isolator image risk; have demanded for an additional direction criterion in 7SS52. Why are several parameter sets required reasons, example?

few references; bus sectionalizer requires BU

few references; no IEC 61850 interface

Argumentation, comment

missing acceptance is inexplicable (only because of few references?) Areva tries to increase their market share by price dumping!

centralized, medium amount of I/O, "low level" operation and uncomfortable configuration, no renowned references, no IEC interface, needs adjusted isolator aux contacts; no integrated isolator replica pricewise attractive, if function sufficient and no references/experiences are required "ext. Fault detection logic" uses dI/dT criterion! Isolator logic "Not open= closed" same as SIEMENS!

no IEC interface

Lon bus

IEC 60870-5-103 IEC 61850-8-1 LON, SPA (ABB spec.)

IEC 60870-5-103

IEC60870 5-104, ModBus-RTU-TCP/IP, DNP, MMS/UCA2, also redundant, IEC61850

IEC60870 5-104, ModBus-RTU-TCP/IP, DNP, MMS/UCA2, also redundant, IEC61850

Operating program Zivercom; engl/spa/port

operating panel

PCM 600 IED Manager, local HMI

RSM 100 operating program, centralized, RS232 (front) or RS485 (rear) only examples listed

Keyboard / display or operating program EnerVista UR PC; application orientated, by logic design and FlexLogic implementation, normally by GE all voltage levels, all types of system groundings

Keyboard / display or operating program EnerVista UR PC;

plant specific by manufacturers

preconfigured configurations on order

3-ph for small buses, generators, T connections, motors, "meshed corners" 1-ph for larger buses Integrated isolator replica for 2-BB; external bistable relays required/ recommended

3-ph for small buses, generators, T connections, n.a. motors, "meshed corners" 1-ph for larger buses Integrated isolator replica for 2-BB actually no-one, plain equipment

High and extra-high voltage

very flexible as an UR component; fast DO;

KEMA test?

n.a. n.a.

approx. 2002 < 5% some in Brazil Attempt on market share increase by an aggressive pricing policy

2006

2002 -- 2003?

Hardware (UR) since 2000, B90 since 07/2002; Algorithm of the small B30

Hardware (UR) since 2000

cheap for small plants

cheap for small to midsize plants (=80%), compact construction

6 plug-in slots, numerous I/O boards (U, I, BI, DO, DO fast) of the UR family; extensive FlexLogik ("CFC")

few references; no IEC interface; only 4 zones, 1- centralized construction step BFP no additional functions (e.g. BFP) not expandable

only 2 zones, centralized construction

only 4 zones, weak disturbance recording, centralized construction, few announciations,

only 1 zone

pricewise attractive, if functionality is sufficient and no references/ experiences are required

ABB arguments: no check zone required "because of stability against CT interruption", not as Siemens, "against faulty isolator replica"! Related to high impedance schemes! "Setting below Imaxload possible, as CT interruption is detected and protection is blocked in time"

Checkzone is available (to satisfy specifications!) difficult, too little information about price, Could become a quite strong rival for 7SS52 and references etc. REB500 because of functionality and/or price! Takes advantage of universal IED 670 platform! Note: 1A/5A not adjustable! 4 ranges for binary inputs!?

difficult, too little information about price, references etc. Actually a n-leg differential protection for 1BB/1.5 CB plants Quantity structure very similar to the SEL487B basic equipment

only 4 zones, (incl. CZ); incommodious configuration (CFC like;) centralized; no IEC60870-5-103; very complicated CT calculation and setting instruction for characteristic difficult, too little information about price, references etc. Actually a n-leg differential protection based on the B30 Current direction criterion is no advantage but necessity! Direction criterion is for stability at saturation and external fault. 7SS doesnt need additional criteria as the fast 1-of-1-algo is faster than saturation.

only 1 zone

difficult, too little information about price, references etc. Actually a n-leg differential protection for 1BB/1.5 CB plants Current direction criterion is no advantage but necessity! Direction criterion is for stability at saturation and external fault. 7SS doesnt need additional criteria as the fast 1-of-1-algo is faster than saturation.