Vous êtes sur la page 1sur 44

P632

Transformer Differential Protection Device


Version -304 -403/404 -606 ff

Supporting Documents
P632/EN IN/A54 (AFSV.11.09640 EN)
This document does not replace the Technical Manual

Warning
When electrical equipment is in operation dangerous voltage will be present in certain parts of the equipment. Failure to observe warning notices, incorrect use or improper use may endanger personnel and equipment and cause personal injury or physical damage. Before working in the terminal strip area, the device must be isolated. Where stranded conductors are used, wire end ferrules must be employed. Proper and safe operation of this device depends on appropriate shipping and handling, proper storage, installation and commissioning, and on careful operation, maintenance and servicing. For this reason only qualified personnel may work on or operate this device. For this reason only qualified personnel familiar with the content of the Safety Guide (SFTY/4LM/B11 or later version) may work on or operate this device. Any modifications to this device must be in accordance with the manual. If any other modification is made without the express permission of AREVA T&D, it will invalidate the warranty, and may render the product unsafe.

Qualified Personnel
are individuals who are familiar with the installation, commissioning and operation of the device and of the system to which it is being connected; are able to perform switching operations in accordance with safety engineering standards and are authorized to energize and de-energize equipment and to isolate, ground and label it; are trained in the care and use of safety apparatus in accordance with safety engineering standards; are trained in emergency procedures (first aid).

Note
The operating manual for this device gives instructions for its installation, commissioning and operation. However, the manual cannot cover all conceivable circumstances or include detailed information on all topics. In the event of questions or specific problems, do not take any action without proper authorization. Contact the appropriate AREVA technical sales office and request the necessary information. Any agreements, commitments, and legal relationships and any obligations on the part of AREVA, including settlement of warranties, result solely from the applicable purchase contract, which is not affected by the contents of the operating manual.

P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN

P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN

Stckprfbescheinigung P632
Routine Test Certificate P632

AREVA Energietechnik GmbH ist ein DQS zertifiziertes Unternehmen. Fertigung und Prfung der Schutzeinrichtungen erfllen die Anforderungen von DIN EN ISO 9001.
AREVA Energietechnik GmbH has been awarded the DQS certificate by the internationally recognized, independent and impartial association for the certification of quality assurance systems, DQS (Deutsche Gesellschaft zur Zertifizierung von Qualittssicherungssystemen), thereby certifying that ALSTOM has introduced and uses a state-of-the-art quality assurance system that complies with all requirements stated in EN ISO 9001 that apply to its products and services.

Stckprfung
Routine Test

Alle Prfungen nach IEC 255-6 und DIN EN 60255-6.


All tests according to IEC 255-6 and EN 60255-6.

Die folgenden berprfungen waren Gegenstand der Stckprfung bei Referenzbedingungen:


The following tests have been carried out as part of the routine test under reference conditions:

1 bereinstimmung der Schutzeinrichtung mit Bestckungs- und Anschluplan


Conformity of the protection device with components list, location diagram and terminal connection diagram

2 Isolationsprfung
Insulation test

3 Stromversorgung im Bereich 0,8 UH,nom UH,nom 1,1 UH,nom


Power supply within the range 0.8 VA,nom VA,nom 1.1 VA,nom

4 Prfung der Genauigkeit der Einstellwerte


Accuracy of the setting values

5 Ansprech- und Kommandozeiten fr alle wesentlichen Funktionen


Operate and command times for all essential functions

6 Funktionsprfung aller binren Signaleingnge und Kontakte


Functional testing of all binary signal inputs and contacts

7 100 % kontrollierter Wrmedauerlauf


100 % controlled thermal endurance test

P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN

P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN

Modifications After Going to Press

P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN

P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN

Contents

1 2 3 3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8 3.9 3.10 4 4.1 4.2 4.3 5 5.1 5.2 5.3

Order Information Modifications Dimensional Drawings Surface-Mounting Case 40 T Flush-Mounting Case 40 T Flush-Mounting Case 84 T PE Terminal Panel Cutout for Case 40 T Panel Cutout for Case 84 T Case 40 T, Flush-Mounted Case 84 T, Flush-Mounted Combining 40 T Cases to Form a 19 Mounting Rack Fitting a 19 Mounting Rack into a Cabinet Location Diagrams Case 40 T, Pin-terminal Connection Case 84 T, Ring-terminal Connection Ethernet Module Terminal Connection Diagrams Case 40 T, Pin-terminal Connection Case 84 T, Ring-terminal Connection Ethernet Module

10 11 12 12 13 15 17 18 20 22 24 26 27 28 28 29 30 31 31 37 43

P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN

1 Order Information

1 Order Information
MiCOM P632
Name Two Winding Transformer Diff. Prot. Basic device: Basic device 40TE, pin-terminal connection, Basic device 84TE, ring-terminal connection, basic complement with 4 binary inputs and 8 output relays Mounting option and display: Surface-mounted, local control panel with text display Flush-mounted, local control panel with text display Processor extension and Current transformer: With DSP-Coprocessor, Inom = 1 A / 5 A (T11...T13 / T21...23) Inom = 1 A / 5 A (T11...T14 / T21...24) Voltage transformer: Vnom = 50 ... 130 V (1-pole) Additional binary I/O options: Without With 1 binary module (add. 6 binary inputs and 8 output relays) Power supply and additional outputs: VA,nom = 24 VDC VA,nom = 48 ... 250 VDC / 100 ... 230 VAC VA,nom = 24 VDC and 6 output relays, 4 with thyristor VA,nom = 48 ... 250 VDC / 100 ... 230 VAC and 6 output relays, 4 with thyristor VA,nom = 24 VDC and 6 output relays VA,nom = 48 ... 250 VDC / 100 ... 230 VAC and 6 output relays Further add. options: Without With analogue module With binary module (add. 24 binary inputs) 0 2 4 8 9 3 4 6 7 0 1
2) 2)

Order number P6323 8 9 0 1 -304 -4xx -403 -404 -606 -46x -9x x -95 x -8xx

3 4 8 9 1

Switching threshold on binary inputs: >18 V (standard variant) >90 V (60...70% of VA,nom = 125...150 V) >73 V (67% of VA,nom = 110 V)
8) 8) 8) 8)

(Without order extension no.) -461 -462 -463 -464 -90 0 -91 -92

>155 V (60...70% of VA,nom = 220...250 V)

>146 V (67% of VA,nom = 220 V) With communication / information interface: Only IRIG-B input for clock synchronization Protocol IEC 60870-5-103 Protocol can be switched between: IEC 60870-5-101/-103, Modbus, DNP3, Courier and IRIG-B input for clock synchronization and 2nd interface (RS485, IEC 60870-5-103) For connection to wire, RS485, isolated For connection to plastic fibre, FSMA connector For connection to glass fibre, ST connector Protocol UCA2 For connection to 10 MHz Ethernet, glass fibre ST and wire RJ45 and 2nd interface (RS485, IEC 60870-5-103) For connection to 100 MHz Ethernet, glass fibre SC and wire RJ45 and 2nd interface (RS485, IEC 60870-5-103) Language: English (German) German (English) French (English) Polish (English) Spanish (English)
4) 4) 7) 4) 4)

1 2 4 -93 5 6

(Without order extension no.) (On request) (On request) (On request) (On request) (On request) -800 -801 -802 -803 -804 -805

Px40 English (English)


4) 4) 4)

Russian (English) 2) Switching via parameter, default setting is underlined! 4) Second included language in brackets

7) Hardware option, supports cyrillic letters instead of special West. Europe characters 8) Standard variant recommended, if higher pickup threshold not explicitly required by the application

10

P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN

2 Modifications

2 Modifications The following area is reserved for documentation of design version modifications of this device, e.g. add-ons, by the factory or the user. It contains information on modification date and modifying person.

Modification

Name

Date

P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN

11

3 Dimensional Drawings

3 Dimensional Drawings 3.1 Surface-Mounted Case 40 T

Dimensional drawing for surface-mounted case 40 T (dimensions in mm)

12

P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN

3 Dimensional Drawings
(continued)

3.2 Flush-Mounted Case 40 T

Dimensional drawing for flush-mounted case 40 T, flush-mount method 1 (without angle brackets and frame)

(dimensions in mm)

P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN

13

3 Dimensional Drawings
(continued)

Dimensional drawing for flush-mounted case 40 T, flush-mount method 2 (using the angle brackets and frame)

(dimensions in mm)

14

P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN

3 Dimensional Drawings
(continued)

3.3 Flush-Mounted Case 84 T

Dimensional drawing for flush-mounted case 84 T, flush-mount method 1 (without angle brackets and frame)

(dimensions in mm)

P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN

15

3 Dimensional Drawings
(continued)

Dimensional drawing for flush-mounted case 84 T, flush-mount method 2 (using the angle brackets and frame)

(dimensions in mm)

16

P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN

3 Dimensional Drawings
(continued)

3.4 Protective Conductor Terminal (PCT) / Case Grounding / Protective Earth Terminal

19Y5220A_EN

Mounting the PCT / Mounting set for case grounding PCT: Protective Conductor Terminal, formerly "Protective Earth Terminal" The clamp bracket is marked with a PCT symbol:

P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN

17

3 Dimensional Drawings
(continued)

3.5 Panel Cutout for Case 40 T

Dimensional drawing of panel cutout for case 40 T, flush-mount method 1 (without angle brackets and frame) (dimensions in mm)

18

P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN

3 Dimensional Drawings
(continued)

Dimensional drawing of panel cutout for case 40 T, flush-mount method 2 (using the angle brackets and frame) (dimensions in mm)

P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN

19

3 Dimensional Drawings
(continued)

3.6 Panel Cutout for Case 84 T

Dimensional drawing of panel cutout for case 84 T, flush-mount method 1 (without angle brackets and frame) (dimensions in mm)

20

P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN

3 Dimensional Drawings
(continued)

10

Dimensional drawing of panel cutout for case 84 T, flush-mount method 2 (using the angle brackets and frame) (dimensions in mm)

P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN

21

3 Dimensional Drawings
(continued)

3.7 Case 40 T, Flush-Mounted

11

Installation of case 40 T for flush-mounting, flush-mount method 1 (without angle brackets and frame) Protective Conductor Terminal (PCT) / Case Grounding / Protective Earth Terminal: See Chapter 3.4

22

P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN

3 Dimensional Drawings
(continued)

12

Installation of case 40 T for flush-mounting, flush-mount method 2 (using the angle brackets and frame) Protective Conductor Terminal (PCT) / Case Grounding / Protective Earth Terminal: See Chapter 3.4

P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN

23

3 Dimensional Drawings
(continued)

3.8 Case 84 T, Flush-Mounted

13

Installation of case 84 T for flush-mounting, flush-mount method 1 (without angle brackets and frame) Protective Conductor Terminal (PCT) / Case Grounding / Protective Earth Terminal: See Chapter 3.4

24

P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN

3 Dimensional Drawings
(continued)

14

Installation of case 84 T for flush-mounting, flush-mount method 2 (using the angle brackets and frame) Protective Conductor Terminal (PCT) / Case Grounding / Protective Earth Terminal: See Chapter 3.4

P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN

25

3 Dimensional Drawings
(continued)

3.9 Combining 40 T Cases to Form a 19 Mounting Rack

15

Combining 40 T flush-mounting cases to form a 19 mounting rack Protective Conductor Terminal (PCT) / Case Grounding / Protective Earth Terminal: See Chapter 3.4

26

P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN

3 Dimensional Drawings
(continued)

3.10 Fitting a 19 Mounting Rack into a Cabinet

16

Fitting a 19 mounting rack Protective Conductor Terminal (PCT) / Case Grounding / Protective Earth Terminal: See Chapter 3.4

P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN

27

4 Location Diagrams

4 Location Diagrams 4.1 Case 40 T, Pin-terminal Connection

17

Location diagram P632 in case 40 T, pin-terminal connection Location diagram of the Ethernet module see Chapter 4.3

28

P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN

4 Location Diagrams
(Fortsetzung)

4.2 Case 84 T, Ring-terminal Connection

18

Location diagram P632 in case 84 T, ring-terminal connection Location diagram of the Ethernet module see Chapter 4.3

P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN

29

4 Location Diagrams
(continued)

4.3 Ethernet Module

01

02

-X7 * A * 01

Type

-X12 02 : Alternative module (see order information) Type Designation

-X13 *

-X8 *

-X10

Slot

Item

Communication module

02

-U17; -U18; -U20; -U25; -U26

Px3x_Ethernet_01A_EN

19

Location diagram of the Ethernet module applicable to: Case 40 T, pin-terminal connection Case 84 T, ring-terminal connection

30

P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN

5 Terminal Connection Diagrams

5 Terminal Connection Diagrams 5.1 Case 40 T, Pin-terminal Connection

20

Terminal connection diagram P632 in case 40 T, pin-terminal connection, diagram P632.403, part 1 of 6

P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN

31

5 Terminal Connection Diagrams


(continued)

21

Terminal connection diagram P632 in case 40 T, pin-terminal connection, diagram P632.403, part 2 of 6

32

P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN

5 Terminal Connection Diagrams


(continued)

22

Terminal connection diagram P632 in case 40 T, pin-terminal connection, diagram P632.403, part 3 of 6

P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN

33

5 Terminal Connection Diagrams


(continued)

23

Terminal connection diagram P632 in case 40 T, pin-terminal connection, diagram P632.403, part 4 of 6

34

P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN

5 Terminal Connection Diagrams


(continued)

24

Terminal connection diagram P632 in case 40 T, pin-terminal connection, diagram P632.403, part 5 of 6

P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN

35

5 Terminal Connection Diagrams


(continued)

25

Terminal connection diagram P632 in case 40 T, pin-terminal connection, diagram P632.403, part 6 of 6 Terminal connection diagram of the Ethernet module see chapter 5.3

36

P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN

5 Terminal Connection Diagrams


(continued)

5.2 Case 84 T, Ring-terminal Connection

26

Terminal connection diagram P632 in case 84 T, ring-terminal connection, diagram P632.404, part 1 of 6

P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN

37

5 Terminal Connection Diagrams


(continued)

27

Terminal connection diagram P632 in case 84 T, ring-terminal connection, diagram P632.404, part 2 of 6

38

P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN

5 Terminal Connection Diagrams


(continued)

28

Terminal connection diagram P632 in case 84 T, ring-terminal connection, diagram P632.404, part 3 of 6

P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN

39

5 Terminal Connection Diagrams


(continued)

29

Terminal connection diagram P632 in case 84 T, ring-terminal connection, diagram P632.404, part 4 of 6

40

P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN

5 Terminal Connection Diagrams


(continued)

30

Terminal connection diagram P632 in case 84 T, ring-terminal connection, diagram P632.404, part 5 of 6

P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN

41

5 Terminal Connection Diagrams


(continued)

31

Terminal connection diagram P632 in case 84 T, ring-terminal connection, diagram P632.404, part 6 of 6 Terminal connection diagram of the Ethernet module see chapter 5.3

42

P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN

5 Terminal Connection Diagrams


(continued)

5.3 Ethernet Module

LOCATION ITEM DESIGN. CONNECTOR MEANING

+ -X7

ITEM REFER.
STATUS

REFER.

Comm. fiber interface Ethernet (10 Base - FL)

RX
ST

X/Y

-U17

LOCATION ITEM DESIGN. CONNECTOR MEANING

+ -X8

ITEM REFER.
STATUS

REFER.

Comm. fiber interface Ethernet (10 Base - FL)

TX
ST

X/Y

-U18

LOCATION ITEM DESIGN. CONNECTOR MEANING

+ -X13

ITEM REFER.
STATUS

REFER.

Comm. fiber interface Ethernet (100 Base - FX)

RX TX
SC

X/Y

-U26

LOCATION ITEM DESIGN. CONNECTOR MEANING

+ -X12

ITEM REFER.
STATUS

REFER.

Comm. interface Ethernet (10 Base T / 100 Base TX)

X // Y
RJ45

-U25

LOCATION ITEM DESIGN. CONNECTOR MEANING Comm. interface Channel 2

+ -X10

ITEM REFER.
STATUS

REFER.

*
1 2 3 4 5 + +

X // Y

D2[R] -U20 D1[T]

RS 485

: Alternative module (see order inform.)

Px3x_Ethernet_02A_EN

32

Terminal connection diagram of the Ethernet module applicable to: Case 40 T, pin-terminal connection, diagram P632.403 Case 84 T, ring-terminal connection, diagram P632.404

P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN

43

Publication: P632-304-403/404-606 // P632/EN IN/A54 // AFSV.11.09640 EN