SALE BUILDING

NOESIS PROJECT CONSULTANTS

Energy Consumption Analysis Summary Power consumed using Conventional method (in kWh) 28512.00 1926180.00 607395.96 1188000.00 3750088

Sl.no.

Description

Power consumed incorporating energy saving methods (in kWh)

A B C D * *

External Lighting load Lift load Common area Load Ventilation Load Total Total Savings in power / Annum (in Kwh) = Energy Consumed / Annum in the absence of energy savings method (in Kwh) = Total Energy Consumption / Annum (in Kwh) with energy saving method= Total savings in power because of power saving methods

21384.00 1444635.00 323924.27 1009800.00 2799743 950345 14599196

* *

13648851 25.34%

SALE BUILDING

NOESIS PROJECT CONSULTANTS

Energy Saving Analysis


The energy consumption analysis and data sheets are as per the Energy Conservation Building Codes 2007 / Bureau of Energy Efficiency. * * 1 2 Demand load for total of the Sale Buildings (1 to 10) : 6435.00KW Following are the methods proposed for the project achieving the same. All lifts on VFD drives which results in 25% saving in consumption. All Ventilation fans are controlled with CO sensor which results in 15% saving in consumption. All internal common area are proposed to work on high energy efficient lamps(CFL) as specified in bureau of energy efficiency, which again results in saving in general consumption.

25% of the external lighting is proposed on solar. These are set of lighting which are placed at critical junctions and which would be lit round the night. Otherwise the other 75% lighting is on timer circuits to achieve the max. savings.

Also total lighting to be proposed on 25% stages operation with automatic switch on and timer based. Also presence and photo sensors are proposed at critical junctions.

SALE BUILDING

NOESIS PROJECT CONSULTANTS

Assuming total external lighting

12.00 kw Operated amount of light at different stages Total load with conventional lights Power consumed in Conventional type of lighting Total load with 25% of solar lights

Annexure-A Power consumed with 25% of lighting on solar power

Sl.no.

Working hours

Number of hours

1 2 3

6p.m to 9p.m 9p.m to 12p.m 12p.m to 6a.m

3 3 6

100% 60% 30%

12 7.2 3.6

36 21.6 21.6 79.2 2376 28512

9 5.4 2.70

27 16.2 16.2 59.4 1782 21384

Energy consumption/day(in Kwh) Energy consumption/month(in Kwh) Energy consumption/Year(in Kwh) Total Power savings /Annum in (Kwh)) * Total Power savings /Annum in (Percentage)

7128.00 25.00 %

SALE BUILDING

NOESIS PROJECT CONSULTANTS

B Sl.no.

Total Lift load (Non Conventional type) Working hours Number of hours

435.00 kw % of load at different intervals Total load with conventional type 435 130.5 435 65.25 Power consumed Total load with in Conventional 25% energy type saving methods 1740 913.5 2175 522 5350.5 160515 1926180 481545.00 326.25 97.88 326.25 48.94

Annexure - B Power consumed in energy saving method

1 2 3 4

6a.m to 10a.m 10a.m to 5p.m 5p.m to 10p.m 10p.m to 6a.m

4 7 5 8

100% 30% 100% 15%

1305 685.125 1631.25 391.5 4012.875 120386.25 1444635

Energy consumption/day(in Kwh) Energy consumption/month(in Kwh) Energy consumption/Year(in Kwh) Total Power savings /Annum in (Kwh)) * Total Power savings /Annum in (Percentage)

25.00 %

SALE BUILDING

NOESIS PROJECT CONSULTANTS

Assuming Common area lighting load

154.79 kw Total load with % of load at conventional light different intervals fixtures Power consumed Total load with using power saving Conventional CFL light fixtures type 773.95 541.765 371.496 82.55 41.27 16.51

Annexure-C Power consumed using power saving CFL light fixtures

Sl.no.

Working hours

Number of hours

1 2 3

6p.m to 11p.m 11p.m to 6a.m 6a.m to 6p.m

5 7 12

100% 50% 20%

154.79 77.395 30.958

412.75 288.92 198.1188168

Energy consumption/day(in Kwh) Energy consumption/month(in Kwh) Energy consumption/Year(in Kwh) Total Power savings /Annum in (Kwh)) * Total Power savings /Annum in (Percentage)

1687.211 50616.33 607395.96 283471.69 46.67 %

899.79 26993.68879 323924.2655

SALE BUILDING

NOESIS PROJECT CONSULTANTS

Assuming Ventilation load

528.00 kw % of load at different intervals Total load with conventional type Power consumed Total load with using 15% energy Conventional saving methods type

Annexure-D Power consumed using power saving CFL light fixtures

Sl.no.

Working hours

Number of hours

1 2

8a.m to 10a.m & 7p.m to 9p.m 10a.m to 7p.m

4 9

100% 25%

528 132

2112 1188 3300 99000 1188000 178200.00

448.80 112.20

1795.20 1009.80 2805.00 84150 1009800

Energy consumption/day(in Kwh) Energy consumption/month(in Kwh) Energy consumption/Year(in Kwh) Total Power savings /Annum in (Kwh)) * Total Power savings /Annum in (Percentage)

15.00 %

SALE BUILDING

NOESIS PROJECT CONSULTANTS

Energy Consumption Analysis


Sl.no. Description Total Load (kW) Apartment load (80% for 2 hours, 40% for 4 hours, 15% for 10 hours, 10% for 8 hours) 5125.50 2 External lighting (100% for 3 hours + 60% for 2 hours + 30% for 7hours) 12 3 Pumps, STP & WTP (80% for 4 hours + 50% for 8 hours+30% for 12 hours) 180.2 4 Common area lighting (100% for 5 hours + 50% for 7 hours + 20% for 12 hours) 154.79 5 Lifts (100% for 9 hours + 30% for 7 hours + 15% for 8 hours) 435.00 6 Ventilation (100% for 4 hours + 25% for 9hours) 528.00 Load (kW) No. of hours 8 to 10AM & 6:30 to 8:30PM (40%) 2 2050.20 9 to 12PM (60%) 3 7.2 8AM to 4 PM (50%) 4 90.1 11PM to 6AM (50%) 5 77.395 10AM to 5PM (30%) 9 130.5 10AM to 7PM (25%) 4 132 9 3,300.00 40,553.32 7 7 8 3 4 Load (kW) No. of hours 10AM to 6:30PM & 8:30PM to 11:30PM (15%) 768.83 12PM to 6AM (30%) 3.6 6 PM to 6AM (30%) 54.06 6AM to 6PM(20%) 30.958 10PM to 6AM (15%) 65.25 8 5,350.50 12 1,687.21 12 1,946.16 6 79.20 Load (kW) No. of hours 11:30 PM to 6AM (10%) 10 512.55 8 28,190.25 Load (kW) No. of hours Total kWh

6 to 8AM (80%) 4100.40 6 to 9PM (100%) 12 6 to 8AM & 4pM to 6PM (80%) 144.16 6 to 11PM (100%) 154.79 6 to 10AM & 5 to 10 PM (100%) 435 8 to 10AM & 7 to 9 PM (100%) 528

Total No. of units consumed per day Considering 30 days in a month, total energy consumed 1216599.63 units Total energy consumed per annum 14599195.6 units