Date : 21/06/2012
Project references : Panait
Page: 2 / 5
The manufacturer will have to guarantee and provide the documents establishing : * The conformity of material with specifications as well as norms and construction codes NORMS AND CONSTRUCTION CODES. * The performances of material, in particular : - heating and cooling output - air flow - available pressure - filters efficiency - fans curves * Inspection and test A factory inspection with test will be planned by the prime contractor before shipment of material * Documents to be enclosed with the submission * Technical specifications as per enclosed annex * Pressure and output level spectrum -> At the AHU intake -> At the AHU discharge -> Radiated by the AHU * The resistance of paint coating in relation to the scale RE
Date : 21/06/2012
Project references : Panait
Page: 3 / 5
1 Air Handling Unit
Make : CIAT or equivalent Flow : SUPPLY 10`600 m/h / EXTRACT : 10`600 m/h Mounting : In line / Internal Mineral wool standard insulation : 25 mm Altitude : 250 m Reference temperature : 20 C EXTRACT : Position 00 1 Fan type LP (forward curved blades) Hinged doors with locking devicefor hexagonal screws Air flow: 10`600 m/h 2.9444 m/s Duct available pressure: 25 mmWG 245 Pa Motor Voltage: 230V/400V/3ph 50Hz Antivibratil chassis on springs mountsand internal flexible sleeve Packing box for motor electrical supply 1 horizontal economizer mixing box Internal damper boxes Opposed dampers with gaskets on the thin plates extremities Cog wheel drive Control to be motorized ACOUSTIC OUTPUT SPECTRUM Frequencies (Hz) / Levels per octave band (dB Lin) 63 125 250 500 1000 2000 4000 Radiated 67 69 48 40 30 33 28 Ducted air inlet 79 78 75 73 72 70 66 Ducted discharge 79 78 75 73 72 70 66 Tolerance on the global spectrum : +/- 3dBTolerance on the octave spectrum :+/-5dB
SUPPLY
Total dB (A) 54 77 77
1 filtration section Efficiency G4:90% With pressure valves Cooling coil Cooling capacity:35.6 kW Refrigerant fluid:Water inlet t / outlet t:7 C / 12 C air inlet t / rh %:28.2 C / 48 %(RH) Calculation air flow: 10`600 m/h 2.9444 m/s Fluid pressure drop :17`470 Pa Standard droplet eliminator Slide mounting Removable panel to acceed to the droplet separator and condensates tray Galva./steel drain pan for condensates recovery 1 spraying humidifier HC Efficiency:80.00 % air inlet t / rh %: 20 C / 50 %(RH)
C:\DOCUMENTS AND SETTINGS\MIHAIL GEORGESCU\DESKTOP\STEFAN.GIW - 001 Climgiw 5.04.11 - P 01/2001
Date : 21/06/2012
Project references : Panait
Page: 4 / 5
Heating coil Heating capacity:50.2 kW Heating fluid:Water inlet t / outlet t:90 C / 70 C air inlet t / rh %:9 C / 95 %(RH) Calculation air flow: 10`600 m/h 2.9444 m/s Slide mounting Removable panel for antifrost thermostat mounting 1 Fan type LP (forward curved blades) Hinged doors with locking devicefor hexagonal screws Air flow: 10`600 m/h 2.9444 m/s Duct available pressure: 25 mmWG 245 Pa Motor Voltage: 230V/400V/3ph 50Hz Antivibratil chassis on springs mountsand internal flexible sleeve Packing box for motor electrical supply
ACOUSTIC OUTPUT SPECTRUM Frequencies (Hz) / Levels per octave band (dB Lin) 63 125 250 500 1000 2000 4000 Radiated 70 72 51 43 33 36 31 Ducted air inlet 78 77 74 72 69 65 53 Ducted discharge 82 81 78 76 75 73 69 Tolerance on the global spectrum : +/- 3dBTolerance on the octave spectrum :+/-5dB
Total dB (A) 57 74 80
Date : 21/06/2012
Project references : Panait
Page: 5 / 5
1 Air Handling Unit
Length : 6`140 mm
Height : 1`320 mm