Alarm Alarm Colour Code of Pin Root Cause Name Definition BTS Alarm Cable No

Verification To check the alarm switch OFF the MAINS MCB from PIU & also switch OFF the DG. To remove the alarm reduces the lubricant oil pressure level below the specified level.

DG LLOP

Major

Light Green & Black/Green.

Alarm occurs when 12- lubricant oil 30 pressuregoes below specified level.

To check the alarm use a matchbox or lighter. Alarm occurs when there Take amatchbox/lighter is either smoke/fire near the Smoke & Fire Orange/Black 18- inside the Fire/Smoke Critical Sensor. &Orange/Green. 36 shelterbecause of any short circuit or of To remove the alarm any inflammable object. reset the Smoke & Fire Sensor. Colour Code of Alarm Pin BTS Alarm Root Cause Definition No Cable

Alarm Name

Verification

High Critical Temperature

To check the alarm increase the temperature of AC Alarm occurs when the (Air Conditioner) temperature inside the more than specified Orange/Red shelter goes above the value or simply switch 17&Orange/Light specified value. It OFF the AC. 35 Grey. happens when AC(Air Conditioner) stops To remove the alarm working switch ON the AC & set the ACs temperature on desired value.

To check the alarm, Alarm occurs when the door of the open the shelter door. Door Red/Black & 16Minor shelter will be open which is Open Red/Blue 34 sensed by door sensor. To remove the alarm, close the door properly.

Low Critical Light Blue & Fuel Black/Blue

Alarm occurs when DG fuel 13- level goes down to the low 31 level or minimum desired level.

To check the alarm see if the desired fuel level of DG set is 30% or not. To remove the alarm just fill up the diesel tank of DG set.

Mains Failure

Green & MInor Green/White

To check the alarm first switch off the Mains MCB 7- Alarm occurs when there is from PIU. 25 no AC powersupply on site To remove the alarm turn on the Mains MCB.

AC Fail(AC1/AC-2)

Major

Light Grey& LightGrey/Black

To check the alarm switch OFF the AC or set the AC temperature more than Alarm occurs when 15specific value. AC(Air Conditioner) 33 stops working. To remove the alarm switch on the AC or repair/replace the AC.

Rectifier Module Failure

To check the alarm first remove the rectifier from the SMPS(in Alarm occurs when one some cases) or switch OFF the Blue & 8- or more than one MCB of rectifier from SMPS. Major Blue/White 26 rectifier modules To remove the alarm switch ON present in SMPS fails. the MCB of the rectifier module or insert the new rectifier module.

To check the alarm set the output load voltage less than 48v.Switch OFF Alarm occurs when the load is the DG,also switch OFF on battery bank & itsoutput the MAINS MCB. Low voltage is at or less than Violet & 9To remove the alarm Battery Critical 47v.Or if battery bankis not White/Violet 27 switch ON the MAINS MCB Voltage charging due to some reason or switch ON the DG if AC & its output load voltage goes is not available.Set the down to 47v. battery load voltage on more than 48v(i.e, between 50v to 51v).

Load on Major Battery

To check the alarm switch OFF the MAINS MCB from PIU & also switch OFF the Alarm occurs when DG (if it is inauto mode). Grey & 10- there is no power White/Grey 28 supply & DG is also To remove the alarm not working. switch ON the MAINS MCB of PIU or switch ON the DG set. Alarm occurs when there is no ACpower supply at the site. To check the alarm switch OFF the MAINS MCB from PIU & also switch ON the DG (if it is not in auto mode). To remove the alarm switch ON the MAINS MCB of PIU or switch OF the

Load on Pink & Minor 11-29 DG Black/Red

DG set, if the AC connection is not taken yet.

Alarm occurs whenever DG DG White & 14- set does no start Fail to Critical Black/White 32 after autocranking & remains Start latched on to the DG set.

To check the alarm switch OFF the MAINS MCB from PIU & see if the DG set is not in auto mode To remove the alarm start the DG set in manual mode.