Item 20.0T Packaged AC unit 30.0T Packaged AC unit

Unit set set

Quantity 2 3

Description N/A

1.1

SPLIT SYSTEM AIR-CONDITIONING UNITS 1.1.1 Quality Assurance

c)

20.0T AC outdoor unit

set

Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100. Paint finish shall be suitable for hot and humid climates. Unit shall be capable and suitable of working at outdoor ambient temperature of 50 deg. C.Sound-power-level, decibels reference, 10 to the minus 12 power watt, at the fan operating speed selected to meet the specified capacity. Sound level shall not exceed 40dBa at low speed and 48dBa at high speed. Sound-power-level data or values for these units shall be obtained in accordance with the test procedures specified in ANSI S12.23. Sound-power values apply to units provided with factory-fabricated cabinet enclosures and standard grilles. Values obtained for the standard cabinet models will be acceptable for concealed models without separate tests provided there is no variation between models as to the coil configuration, blowers, motor speeds, or relative arrangement of parts. Each unit shall be fastened securely to the building structure. Wall or Ceiling Mounted, Evaporator Fan Components Cabinet: Enameled steel with removable panels on front and ends, and discharge drain pans with drain connection. Refrigerant Coil: Copper tube, with mechanically bonded aluminum fins, complying with ARI 210/240, and with thermal-expansion valve. Fan and Motor: Centrifugal fan, directly driven by multispeed, electric motor with integral overload protection; resiliently mounted. Filters: 25 mm thick, permanent, washable, cleanable type in aluminum frames. Air-Cooled, Compressor-Condenser Components Casing: Steel, finished with baked enamel, with removable panels for access to controls, weep holes for water drainage, and mounting holes in base. Provide brass service valves, fittings, and gage ports on exterior of casing.

d)

16.0T AC outdoor unit

set

e)

14.0T AC outdoor unit

set

1.1.2

f)

12.0T AC outdoor unit

set

1.1.3

g)

10.0T AC outdoor unit

set

Compressor: Hermetically sealed with crankcase heater and mounted on vibration isolation. Compressor motor

shall have thermal- and current-sensitive overload devices, start capacitor, relay, and contactor. h) 9.0T AC outdoor unit set 1 Compressor Type: Reciprocating or Scroll. Two-speed compressor motor with manual-reset highpressure switch and automatic-reset low-pressure switch.

Refrigerant Coil: Copper tube, with mechanically bonded aluminum fins, complying with ARI 210/240, and with liquid subcooler. Fan: Aluminum-propeller type, directly connected to motor. Motor: Permanently lubricated, with integral thermaloverload protection. Mounting Base: Polyethylene. 1.1.4 Accessories

i)

2.0T Cassette type AC indoor unit

set

76

Thermostat: DDC wall type. Refer to specification section 15900, clause 2.5A Automatic-reset timer to prevent rapid cycling of compressor.

j)

1.5T AC wall mounted indoor unit

set

Refrigerant Line Kits: Soft-annealed copper suction and liquid lines factory cleaned, dried, pressurized, and sealed; factory-insulated suction line with flared fittings at both ends.

k)

l)

750mm x 750mm AC Duct including insulation & fixing accessories Supply & Return air nozzles including fixing in the ducts

200

pc

32

1.1.5

Manual-Volume Dampers General: Factory fabricated with required hardware and accessories. Stiffen damper blades for stability. Include locking device to hold single-blade dampers in a fixed position without vibration. Close duct penetrations for damper components to seal duct consistent with pressure class. Pressure Classifications of 500 Pa or Higher: End bearings or other seals for ducts with axles full length of damper blades and bearings at both ends of operating shaft.

m)

Manual-Volume Damper

pc

32

Low-Leakage Volume Dampers: Multiple- or singleblade, parallel- or opposed-blade design as indicated, low-leakage rating, with linkage outside air stream, and suitable for horizontal or vertical applications.

Steel Frames: Hat-shaped, galvanized, sheet steel channels, minimum of 1.6 mm thick, with mitered and welded corners; frames with flanges where indicated for attaching to walls; and flangeless frames where indicated for installing in ducts. Aluminum Frames to be installed where aluminum ducts are installed: Hat-shaped, 1.6 mm thick, extruded-aluminum channels; frames with flanges where indicated for attaching to walls; and flangeless frames where indicated for installing in ducts. Roll-Formed Steel Blades: 1.6 mm thick, galvanized, sheet steel. Roll-Formed Aluminum Blades: 2.5 mm thick aluminum sheet. Blade Axles: Galvanized steel. Tie Bars and Brackets: Aluminum where aluminum ducts are installed. Tie Bars and Brackets: Galvanized steel.

Jackshaft: 25 mm diameter, galvanized steel pipe rotating within a pipe-bearing assembly mounted on supports at each mullion and at each end of multipledamper assemblies. Length and Number of Mountings: Appropriate to connect linkage of each damper of a multipledamper assembly.

Damper Hardware: Zinc-plated, die-cast core with dial and handle made of 2.4 mm thick zinc-plated steel, and a 19 mm hexagon locking nut. Include center hole to suit damper operating-rod size. Include elevated platform for insulated duct mounting. AMCA 500D

1.1.6
n) Fire Damper pc 5

Fire Dampers General: Labeled to UL 555. Fire Rating: One and one-half and three hours. Frame: SMACNA Type B with blades out of air stream; fabricated with roll-formed, 0.85 mm thick galvanized steel; with mitered and interlocking corners. Mounting Sleeve: Factory- or field-installed galvanized, sheet steel. Minimum Thickness: 1.3 mm or 3.5 mm thick as indicated, and length to suit application. Exceptions: Omit sleeve where damper frame width permits direct attachment of perimeter mounting angles on each side of wall or floor, and

thickness of damper frame complies with sleeve requirements. Mounting Orientation: indicated. Vertical or horizontal as

Blades: Roll-formed, interlocking, 0.85 mm thick, galvanized, sheet steel. In place of interlocking blades, use full-length, 0.85 mm thick, galvanized steel blade connectors. Horizontal Dampers: Include a blade lock and stainless-steel negator closure spring. Fusible Link: Replaceable, 74deg. C rated. Flexible Connectors General: Flame-retarded or noncombustible fabrics, coatings, and adhesives complying with UL 181, Class 1. Extra-Wide Metal-Edged Connectors for use with extra heavy equipment and large ducts: Factory fabricated with a strip of fabric 146 mm wide attached to two strips of 70 mm wide, 0.7 mm thick, galvanized, sheet steel. High-Corrosive-Environment System Flexible Connectors: Glass fabric coated with a chemicalresistant coating. Minimum Weight: 474 g/sq. m. Tensile Strength: 79 N/mm in the warp, and 60 N/mm in the filling.

1.1.7

o) Flexible Connecter m 70

p) e) f) g) h) i) j) k)

l)

16.0T AC outdoor unit 14.0T AC outdoor unit 12.0T AC outdoor unit 10.0T AC outdoor unit 9.0T AC outdoor unit 2.0T Cassette type AC indoor unit 1.5T AC wall mounted indoor unit 750mm x 750mm AC Duct including insulation & fixing accessories Supply & Return air nozzles including fixing in the ducts