NTPC Limited
(A Government of India Enterprise)
TOSHIBA JSW TURBINE & GENERATOR PRIVATE LIMITED CS-9573-110-2-FC-COA-5661, CS-9573-110-2-SC-COA-5662, CS-9573-110-2-TC-COA-5663 TOSHIBA CORPORATION, JAPAN
CONTRACTOR CONTRACT NO. SUB-CONTRACTOR OWNERS DOC. NO. 9573-110-PVM-U-018 SUB-CONTRACTORs REV. DDKV71215 DOC. NO. DRG. / DOC. TITLE PURPOSE
REVISION
02 01
REV. NO.
13/Sep/2012 25/July/2012
DATE
R. Y R. Y REVISED BY
Y. F S. M CHECKED BY
Y. F Y. F APPROVED BY
ISSUED BY - TOSHIBA
00
Y. F Y. F DATE S. M
7/June/2012
T ID T PROPERTY INCLUDING KNOW-HOW. IT SHALL NOT BE DISCLOSED TO ANY H MIS E A LI I N T As INTELLECTUAL FE N OR D RI ML C A I O TS N I OC T NO I I NN N FS TI HE O SN H A T B A A A THIRD PARTY, COPIED, REPRODUCED, USED FOR UNAUTHORIZED PURPOSES NOR MODIFIED WITHOUT PRIOR WRITTEN CONSENT OF TOSHIBA.
DD KV71215-d
1 20
The information in this material is confidential and contains Toshibas intellectual property including know-how. It shall not be disclosed to any third party, copied, reproduced, used for unauthorized purposes nor modified without prior written consent of Toshiba. Toshiba Corporation
DISTRIBUTION ISSUED BY
APPROVED BY
Y.Fuki Sep.13,2012
REVIEWED BY
Y.Fuki Sep.13,2012
PREPARED BY
NETSU-SETSU
R.Yasuki Sep.13.2012
DD KV71215-d
2 20
1. Design Specification 2. Calculation of Circulating Water flow rate 3. Thermal Calculation 3.1 L.P. Condenser 3.2 H.P. Condenser 4. Hydraulic Calculation 4.1 L.P. Condenser 4.2 H.P. Condenser 4.3 Total loss of Condenser 5. Hotwell Storage Capacity 6. Steam and Condensate flow
3 4 5 5 8 11 11 12 12 13 14
Appendix UNCORRECTED HEAT TRANSFER COEFFICIENTS INLET WATER TEMPERATURE CORRECTION FACTOR TUBE MATERIAL AND GAUGE CORRECTON FACTORS TEMPERATURE CORRECTION FOR FRICTION LOSS IN TUBES WATER BOX AND TUBE END LOSSES SINGLE PASS CONDENSER
*HEI STANDARD for STEAM SURFACE CONDENSERS 10th EDITION
DD KV71215-d
3 20
(L.P.) (H.P.)
Number of tubes (per shell) Location Condensing Zone Total Number of water passes Cooling water source Cleanliness factor Main Cooling Water (m3/min.) Thickness (mm) t=0.711 t=0.889 Number 22,764 2,528 25,292 One(1) Fresh Water Fc=0.90 (90%) 1,310 (78,600 m3/hr)
Applied Codes & Standards Heat Exchange Institute 10th (HEI 10th)
DD KV71215-d
4 20
Specific Flow Rate Enthalpy kg/h kcal/kg 659,579 564.1 67,223 590.2 1,614 750.4
d
Heat Duty D1
3.83162E+08
kcal/h Enthalpy of Condensate kcal/kg 46.1 46.1 46.1 46.1 46.1 46.1 Total kcal/h
b.Heat duty (H.P.Condenser) Heat Balance : 3GMG04302 (VWO, 3% m.u.,67mmHg) Main Turbine Exhaust BFP Turbine Exhaust Drain from Gland Steam Condenser Drain From LP No.1Heater Make-up Water L.P Condenser Drain
d
3.99730E+08
DD KV71215-d
5 20
22,764 2,528
Inner Diameter of Tubes di1 0.0240 m Inner Diameter of Tubes di2 0.0236 m
( Thickness 0.711 mm )
2528
0.0236 0.0240
1/1.4)
V1 1.92 m/s (2) Water velocity in Tubes V2 m/s V2 V1 di2 di1 0.0236 0.0240 1/1.4) ( Thickness 0.889 mm )
1.92 1.900m/s
1/1.4)
V2 1.90 m/s
DD KV71215-d
6 20
from Fig.1 V 1.92 m/s ( 6.299 ft/s ) U1 659.71 Btu/hft2F FW 1.079 from Fig.2 Inlet Water Temperature 33.0 FM 0.854
d
from Table.3 Tube Material (Stainless Steel), Thickness ( 0.711mm ) Correction Factor FC 0.9 Cleanliness Factor 90%
d
Ua 3220.7
1.079
0.854
2670.9 kcal/m2 h
, Diameter of Tubes
25.4mm ( 1.0 in )
from Table.3 Tube Material (Stainless Steel), Thickness ( 0.889mm ) Correction Factor FC 0.9 Cleanliness Factor 90%
d
Ub 3203.5
1.079
0.815 0.90
2535.3
kcal/m2 h
(3) Average Heat Transfer Coefficient Um Ua N1+ Ub N2 Um N1 + N2 2670.9 22764 22764 2535.3 2528 2528
DD KV71215-d
7 20
60
ts =
t1 =
33.0
t = 4.91
( ts t1 )( ts t2 )
ln
( ts t1 ) ( ts t2 )
ln
7.84 2.93
> Areq
DD KV71215-d
8 20
3.2H.P Condenser a.Water velocity in Tubes Thickness 0.711 mm Number of Tube N1 Thickness 0.889 mm Number of Tube N2 (1) Water velocity in Tubes V1 m/s V1 Q 4 60 d i1 N1 + d i2 2 N2(di2/di1)1/1.4) 1310 22764 + + 0.023622
2
2
22,764 2,528
Inner Diameter of Tubes di1 0.0240 m Inner Diameter of Tubes di2 0.0236 m
( Thickness 0.711 mm )
2528
0.0236 0.0240
1/1.4)
V1 1.92 m/s (2) Water velocity in Tubes V2 m/s V2 V1 di2 di1 0.0236 0.0240 1/1.4) ( Thickness 0.889 mm )
1.92 1.900m/s
1/1.4)
V2 1.90 m/s
DD KV71215-d
9 20
from Fig.1 V 1.92 m/s ( 6.299 ft/s ) U1 659.71 Btu/hft2F FW 1.101 from Fig.2 Inlet Water Temperature 37.91 FM 0.854
d
F ( 100.2
) Correction Factor
from Table.3 Tube Material (Stainless Steel), Thickness ( 0.711mm ) Correction Factor FC 0.9 Cleanliness Factor 90%
d
Ua 3220.7
1.101
0.854
2725.4 kcal/m2 h
, Diameter of Tubes
25.4mm ( 1.0 in )
from Table.3 Tube Material (Stainless Steel), Thickness ( 0.889mm ) Correction Factor FC 0.9 Cleanliness Factor 90%
d
Ub 3203.5
1.101
0.815 0.90
2587.0 kcal/m2 h
(3) Average Heat Transfer Coefficient Um Ua N1+ Ub N2 Um N1 + N2 2725.4 22764 22764 2587 2528 2528
2711.57
d
U m2711.6 kcal/m2 h
DD KV71215-d
10 20
ts =
t1 = 37.91
( ts t1 )( ts t2 )
t = 5.13
ln
( ts t1 ) ( ts t2 )
ln
8.18 3.05
> Areq
DD KV71215-d
11 20
7.94 (Vw) 1.92 6.30 (Vw) 33.0 / 37.91 91.4 / 100.24 (T1/T2) 23.98 0.94 (Di) 14.431 47.346 (Lt)
d
0.70 Curve (a) of Figure 8 0.98 Curve (b) of Figure 8 0.30 Curve (c) of Figure 8 1.98 (Re)
0.173 (R2 x Rt) 0.954 (R1: Figure 7) 0.165 (Rt x R2 x R1) 7.81
DD KV71215-d
12 20
7.94 (Vw) 1.92 6.30 (Vw) 37.91 / 43.04 100.24 / 109.47 (T1/T2) 23.98 0.94 (Di) 14.431 47.346 (Lt)
d
0.70 Curve (a) of Figure 8 0.98 Curve (b) of Figure 8 0.30 Curve (c) of Figure 8 1.98 (Re)
0.173 (R2 x Rt) 0.936 (R1: Figure 7) 0.162 (Rt x R2 x R1) 7.66
These value do not include loss of CW piping and inter-connecting piping between LP and HP Condenser.
DD KV71215-d
13 20
1741639 29.03
kg/h m 3/min
c.Required Hotwell Height : Hreq Size of Cond Lower Shell a b 13895 b 7960 a Size of Cond Lower Shell Hreq' Qreq ab 109 Height of LLWL - Bottom : HLLWL-B HLLWL-B Hreq Hreq' + HLLWL-B 87.08 138957960 109
787.3 mm
200 mm 987.3 mm
d.Actual Hotwell Height : H (Height of NWL - Bottom) Height of NWL - LLWL : HNWL-LLWL HNWL-LLWL H HNWL-LLWL + HLLWL-B
DD KV71215-d
14 20
The condensate (generated in LP Condenser) passing through the perforated plates is reheated by the steam from HP Condenser. The condensate is led to HP Condenser through connection pipe between HP and LP Condenser. The Hotwell of LP Condenser has two different pressure zones. The pressure zone (Reheating Section) has the same pressure as HP Condenser.
Condenser is designed for exhaust steam from steam turbine, BFP drive turbine, LP bypass system, heater drains and vents, boiler separator drains during start up, low load and abnormal conditions and other miscellaneous drains.
DD KV71215-d
15 20
DD KV71215-d
16 20
DD KV71215-d
17 20
DD KV71215-d
18 20
DD KV71215-d
19 20
DD KV71215-d
20 20
Initial Issue
11,12
Corrected value.
Jun.07.2012
Y.Fuki
Revised as marked
Jul.25.2012 Written in
Revised as marked
page 1.