The trend of cross-linked polyethylene insulated cables into power cables field is quite prevalent in the
world as the substitutes of paper insulated cables, which had played the leading role in electric power
transmission stage. Thus, nowadays after making its impact on its use in the medium voltage cable
category, the stage seems to be turning in favour of XLPE cables in the high voltage and extra high
voltage range. Especially in the higher voltage area, the monopoly of paper insulated cables, such as
oil filled cable, gas filled and compressed type of cables, is gradually collapsing into the co-existence
with XLPE cables, which have great advantages and economical reasons such as higher permissible
temperature level, ease of jointing and maintenance techniques and omission of equivalent inherent to
the pressurized cable.
Electrical performance of XLPE is excellent. Di-electric breakdown strength and volume resistivity are
high and both Di-electric loss (tan ) and dielectric constant () are low. Thermal resistivity is low.
XLPE insulated cables can operate continuously at a temperature of 90C, because they have excellent
heat ageing characteristics. This leads to large power transmission capacity. XLPE cables are lighter in
weight, they are easy to handle and install and jointing and termination is also easy. They are of dry
type because no oil impregnation is involved.
The insulation material for XLPE cables is low-density (LD) polyethylene. PE has for a long time had
a wide use as cable insulating and sheath materials owing to its excellent electrical and mechanical
properties, its lightness, low temperature flexibility and good resistance to moisture, chemicals, ozone
etc. as well as its comparatively low price.
However, Low Density Polyethylene has properties which limit its use as cable insulation. Being a
thermoplastic, its softening temperature is 105 - 115C. Another disadvantage is its tendency to stress
cracking when in contact with certain surface-active agents.
By means of a process reminiscent of the vulcanization of rubber, PE molecules can be cross-linked, thus
greatly improving the thermal and mechanical properties of the material, while its electrical properties
are retained largely unchanged. This product, cross-linked polyethylene (XLPE), is therefore no longer
a thermoplastic. It assumes elastic, rubber-like consistency, a property that retains during further rise
of temperature. The tendency to stress cracking entirely disappears and the material also acquires very
good resistance to ageing in hot air.
CROSS-LINKED POLYETHYLENE
PE is made up of long molecular chains. By cross-linking, these chains a network of strong bonds is
created and PE is converted into cross-linked polyethylene, XLPE.
THERMAL PROPERTIES
Owing to the cross-linking, XLPE is a very heat-resistant material. It cannot melt like polyethylene but
decomposes and carbonizes if exposed for long periods to temperature above 300C.
The permissible conductor temperature during short-circuit for 1 second has therefore been put at 250C
and under continuous load, conductors with XLPE insulation may have a temperature of 90C. These
temperature are specified by International standards. In emergency conditions and for limited period,
XLPE can withstand 130C.
XLPE, like PE, retains its low temperature flexibility down to -40C which implies great advantages during
laying of cables.
ELECTRICAL PROPERTIES
The good electrical properties of PE remain largely unchanged during cross-linking process. XLPE
therefore, like PE, has a very small and insignificant temperature dependant loss factor (tan ) and
dielectric constant () As a result the dielectric loss of XLPE cables are small in comparison with those
of PVC and paper insulated cables. XLPE cables are specially adapted for long cable routes and high
voltages, in both cases where dielectric losses are of great significant.
MECHANICAL PROPERTIES
Polyethylene has good mechanical properties. It is interesting that at normal temperature PE can resist
local stress better than PVC. In this respect XLPE has the same advantageous properties as PE and certain
grades, such as filled XLPE insulation also resist abrasion much better than polyethylene.
CHEMICAL PROPERTIES
Owing to the cross-linking of molecules XLPE better resistance than PE to most chemical such as ordinary
acids, bases and oil.
ENVIRONMENTAL POLLUTION AND CABLES
From the environmental aspect, both PVC and oil-impregnated paper-insulated cables have distinct
disadvantages. When PVC cables burn they give off corrosive gases, and a leaking oil filled cable may
cause severe damage to environment.
XLPE admittedly burns, but the products of combustion carbon dioxide and water do not cause damage.
Filled XLPE used for low voltage cables can also be made resistant to flame propagation and the compound
does not produce halogen.
CROSS-LINKING PROCESS
Cross-linking is done by agent Di-Cumyl Peroxide (DCP). Cross-linking takes place in the CCV Tube under
heated and pressurized Nitrogen where DCP decomposes into two radicals, which react with Polyethylene,
thereby causing cross-linking.
Peroxide is already mixed at the material suppliers plant with proper balance of anti-oxidant and
peroxide to ensure the required thermal stability and optimum curing level. Therefore, no mixing is done
during production. This prevents problems which might occur due to the unbalance mixing of material
during production stage. Un-packing and handling of the material is also done in similar super clean
environment.
The mixing ratio is about 1 to 1.5 PHR with very small amount of anti-oxidant. The cross-link residue is
gas, which defuses out of the insulation gradually. Other residuals are Acetophone and Cumyl-alcohol
which are in very low ratio. Research, in this regard, has proven that these materials have very good
effect on insulation such as:
a) It improves the breaking strength when inclusion occurs in XLPE material.
b) It slows water tree growth in the XLPE material under service.
National Cables Industry employs in-line dry curing for all its CCV lines along with state-of-the-art
Triple Cross-Head extrusion where the Conductor Screen, Insulation and Insulation Screen are extruded
simultaneously by means of a Triple Cross Head which has the following advantages:
Reduce micro voids and moisture content in insulation and ensures enhanced and stable breakdown
strength and uniform insulation structure.
Ensures extremely accurate layer thickness.
Ensures high purity in the frontier limit between the semi-conductive layers and the insulation.
Provides optimal fusion of the individual layers without contamination.
Ensures a firm bond and smooth interface between each layer improving electrical properties.
Prevents unforeseen damage to the conductor or insulation screen during manufacturing
process.
The above are optimized by the use of an X-Ray unit located immediately after the cross-head which
provides a transparent view of all three layers. This arrangement also facilitates recording the trend
every 4 seconds. The unit continuously scans 360C geometry of the cable and displays the maximum,
minimum and eccentricity of all three layers separately. Any deviation between the specified values and
the measured values are recorded and adjusted automatically.
Also incorporated in the CCV line is the Twin-Rot system, one of the latest in manufacturing technology,
which ensures superior control of eccentricity and eliminates the possibility of Pear Drop since the cable
rotates during manufacture.
QUALITY ASPECT
It is the policy of National Cables Industry to supply customers with products meeting fully their stated
needs. The products perform their required functions safely, consistently and reliably of their intended
use. They fully meet the specifications which they are designed to meet whether Customer, Country or
International.
NCI sources its raw materials from reputed suppliers from all over the world. The most important
cable constituents such as XLPE material, conductor and insulation shielding material are procured from
the worlds leading suppliers of cable components. Right from the beginning, all incoming material and
cable constituents are analyzed and tested to ensure their quality and compliance with specifications
before being used. During manufacture, again complete tests are performed on physical, mechanical and
electrical properties of insulation and sheath material.
NCI products are also type tested at International agencies. Several of the products are type tested and
certified from KEMA, Netherlands, IPH, Berlin, Germany and CPRI, India. Type tests are also performed
in-house on a pre-defined regular basis to ensure and guarantee the quality of the manufactured
products.
Testing facilities are equipped with up-to-date most modern and advanced laboratories. The laboratories
are equipped with facilities for complete testing of its products both for incoming raw materials as well
as finished goods as per International Standards. Test fields include routine test field with large shielded
enclosures for carrying out the routine high voltage tests,Partial discharge measurement up to 250kV at
a noise level of below 2 pC, measurement of (tan ) ,capacitance and 900kV impulse generator.
CCV Line
MV Test Field
The table below shows some typical properties of XLPE material, PVC, EP Rubber and Impregnated Paper
XLPE
PVC
EP
Rubber
Impregnated
Paper
Unfilled
Filled
2.30
3.5
0.0005
0.0005
0.07
0.003
0.003
1016
1014
1012
1016
1013
90
90
70
85
65
250
250
160
250
150
15
15
15
Elongation at rupture, %
500
300
250
300
Flexibility
20 C
-10 C
Good
Good
Good
Good
Excellent
Poor
Excellent
Excellent
Abrasion resistance
Good
Excellent
Good
Poor
Good
Excellent
Poor
Excellent
Good
Oil resistance at 70 C
Good
Good
Good
Poor
Fire resistance
Poor
Moderate
Excellent
Poor
Poor
100 C
Excellent
Excellent
Moderate
Good
Good
120 C
Good
Good
Poor
Moderate
Moderate
150 C
Moderate
Moderate
Poor
Poor
Ageing resistance at
CONDUCTORS
Conductors shall be stranded class 2 of plain annealed copper or aluminium and in accordance with
IEC 60228 and BS EN 60228 (earlier BS 6360).
CONDUCTOR SCREEN
Conductor screen shall be non-metallic and shall consist of an extruded semi-conductive compound
which may be applied on top of a semi-conductive tape at the manufacturers discretion. The extruded
semi-conducting compound shall be firmly bonded to the insulation.
XLPE INSULATION
Insulation shall be XLPE (cross-linked polyethylene). Thickness and test requirements shall comply with
IEC 60502-2 and IEC 60811 series.
INSULATION SCREEN
The insulation screen shall consist of a non-metallic semi-conducting layer in combination with a metallic
layer.
Non-metallic part: The non-metallic layer shall be extruded directly upon the insulation of each core and
shall consist of either a strippable or bonded semi-conducting compound.
Metallic part: Metallic layer shall consist of one or more tapes or a concentric layer of wires or a combination
of wire and tapes.
INNER COVERING/SEPARATION SHEATH
Inner covering may be extruded or lapped. When the underlying metallic layer and the armour are of
different materials, they shall be separated by an extruded sheath of PVC or Polyethylene or LSF as
applicable.
METALLIC ARMOUR
Armour shall be as per IEC 60502-2 of the following types:
a) Round Wire Armour
b) Double Tape Armour
Armour material shall be Galvanized Steel for three core cables and Aluminium for single core cables.
OUTER SHEATH
Outer sheath shall be extruded PVC type ST2 as per IEC 60502-2, Type 9 as per BS 7655. Special type of
PVC sheathing materials such as Fire Retardant PVC, anti-termite and anti-rodent PVC, Ultraviolet PVC,
Oil Resistant PVC, etc. are available on request. Also, other special sheathing materials such as LLDPE,
MDPE, HDPE, LSF etc are available.
PHASE IDENTIFICATION
For 3 core cables, Red, Yellow and Blue coloured strips shall be applied under the metallic screen throughout
the length of the cable for phase identification.
For single core cables no phase identification shall be provided.
COPPER CONDUCTORS
IEC 60502-2
1. Conductor
2. Conductor Screen
3. XLPE Insulation
Size
Diameter
of
Conductor
(Approx.)
Nominal
Insulation
Thickness
Diameter
Over
Insulation
(Approx.)
mm
5.9
6.9
8.1
9.7
11.4
12.9
14.3
16.0
18.4
20.4
23.2
26.7
30.4
mm
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.6
2.8
3.0
3.2
3.2
mm
12.5
13.5
14.7
16.3
18.0
19.5
20.9
22.6
25.2
27.6
30.8
34.7
38.4
mm
25
35
50
70
95
120
150
185
240
300
400
500
630
Uo/U (Um)=3.5/6(7.2)kV
Overall Diameter
(Approx.)
Weight of Cable
(Approx)
CUT
CUW
CUT
CUW
CUT
CUW
mm
1.8
1.8
1.6
1.6
1.7
1.7
1.8
1.8
1.9
2.0
2.1
2.2
2.3
mm
1.5
1.6
1.6
1.6
1.7
1.8
1.8
1.9
1.9
2.0
2.2
2.3
2.4
mm
18
19
21
22
24
26
27
29
32
34
38
42
46
mm
20
21
22
24
25
26
28
30
33
36
39
44
48
Kg/km
510
650
785
1010
1300
1550
1825
2200
2800
3400
4275
5375
6800
Kg/km
725
825
950
1175
1475
1750
2100
2400
3000
3600
4675
5800
7075
Flat
Spaced
Trefoil
ducts
Flat
Touching
ducts
Trefoil
Flat
Touching
Flat
Spaced
Ohm/km
mH/km
mH/km
F/km
kA
Amps
Amps
Amps
Amps
Amps
Amps
Amps
25
35
50
70
95
120
150
185
240
300
400
500
630
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
0.444
0.426
0.408
0.388
0.378
0.364
0.354
0.343
0.332
0.324
0.313
0.306
0.296
0.760
0.745
0.720
0.694
0.679
0.660
0.645
0.630
0.611
0.596
0.578
0.564
0.548
0.26
0.29
0.32
0.37
0.39
0.44
0.48
0.52
0.56
0.58
0.61
0.64
0.71
3.575
5.005
7.150
10.010
13.585
17.160
21.450
26.455
34.320
42.900
57.200
71.500
90.090
140
166
196
239
285
323
361
406
469
526
590
655
731
144
172
203
246
293
332
366
410
470
524
572
625
690
132
157
186
227
271
308
343
387
447
504
564
133
159
188
229
274
311
347
391
453
510
574
163
198
238
296
361
417
473
543
641
735
845
956
1095
167
203
243
303
369
426
481
550
647
739
837
935
196
238
286
356
434
500
559
637
745
846
938
1028
1158
635
712
640
720
1061
Trefoil
mm
Size
Conductor
Short Circuit
Current
for 1 second
In air
Capacitance
Buried
Direct
In
the
ground
In single -way
ducts
Flat
Inductance
Trefoil
Max DC
Resistance
@ 20C
Current ratings
V/A.
Km
0.825
0.615
0.472
0.347
0.269
0.225
0.194
0.167
0.141
0.125
0.110
0.099
0.09
Laying condition: Maximum conductor temperature 90C, Ambient temperature 30C. Underground temperature of soil 20C, Depth of laying - 0.8m.
Ground thermal resistivity 1.5 K.m/W, thermal resisitivity of earthenware ducts 1.2 K.m/W.
Note: Area of copper wire considered is 16 mm2 up to 120 mm2, 25 mm2 from 150 mm2 up to 300 mm2, 35 mm2 from 400 mm2 up to 630 mm2.
10
IEC 60502-2
1. Conductor
2. Conductor Screen
3. XLPE Insulation
Diameter of
Conductor
(Approx.)
Nominal
Insulation
Thickness
Diameter
Over Insulation
(Approx.)
mm
5.9
6.9
8.1
9.7
11.4
12.9
14.3
16.0
18.4
20.4
23.2
26.7
30.4
mm
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
mm
14.3
15.3
16.5
18.1
19.8
21.3
22.7
24.4
26.8
28.8
31.6
35.1
38.8
Overall Diameter
(Approx.)
Weight of Cable
(Approx)
CUT
CUW
CUT
CUW
CUT
CUW
mm
1.8
1..8
1.8
1.8
1.8
1.8
1.8
1.9
2.0
2.0
2.1
2.2
2.3
mm
1.8
1.8
1.8
1.8
1.8
1.8
1.9
1.9
2.0
2.1
2.2
2.3
2.4
mm
20
21
22
24
26
27
29
31
33
35
38
42
46
mm
22
23
24
26
27
29
30
32
35
37
40
44
48
Kg/km
600
700
850
1075
1350
1625
1900
2300
2900
3475
4325
5400
6825
Kg/km
775
875
990
1200
1500
1725
2100
2475
3100
3700
4650
5725
7100
In single -way
ducts
Flat
Conductor
Short Circuit
Current
for 1 second
Trefoil
Flat
Spaced
Trefoil
ducts
Flat
Touching
ducts
Trefoil
Flat
Touching
Flat
Spaced
In air
mm
Ohm/km
mH/km
mH/km
F/km
kA
Amps
Amps
Amps
Amps
Amps
Amps
Amps
25
35
50
70
95
120
150
185
240
300
400
500
630
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
0.460
0.440
0.420
0.401
0.383
0.376
0.364
0.354
0.341
0.329
0.318
0.308
0.299
0.770
0.751
0.726
0.700
0.681
0.666
0.650
0.635
0.615
0.593
0.580
0.565
0.549
0.21
0.23
0.25
0.29
0.31
0.34
0.37
0.40
0.45
0.49
0.55
0.60
0.68
3.575
5.005
7.150
10.010
13.585
17.160
21.450
26.455
34.320
42.900
57.200
71.500
90.090
140
166
196
239
285
323
361
406
469
526
590
655
731
144
172
203
246
293
332
366
410
470
524
572
625
690
132
157
186
227
271
308
343
387
447
504
564
133
159
188
229
274
311
347
391
453
510
571
163
198
238
296
361
417
473
543
641
735
845
956
1095
167
203
243
303
369
426
481
550
647
739
837
935
196
238
286
356
434
500
559
637
745
846
938
1028
1158
635
712
640
720
1061
Current ratings
Trefoil
Max DC
Resistance
@ 20C
Size
Inductance
Buried
Direct
In
the
ground
mm
25
35
50
70
95
120
150
185
240
300
400
500
630
Capacitance
Size
Uo/U (Um)=6/10(12)kV
V/A.
Km
0.829
0.618
0.474
0.349
0.270
0.228
0.196
0.169
0.143
0.126
0.111
0.100
0.091
Laying condition: Maximum conductor temperature 90C, Ambient temperature 30C. Underground temperature of soil 20C, Depth of laying - 0.8m.
Ground thermal resistivity 1.5 K.m/W, thermal resisitivity of earthenware ducts 1.2 K.m/W.
Note: Area of copper wire considered is 16 mm2 up to 120 mm2, 25 mm2 from 150 mm2 up to 300 mm2, 35 mm2 from 400 mm2 up to 630 mm2.
11
IEC 60502-2
1. Conductor
2. Conductor Screen
3. XLPE Insulation
Size
Diameter of
Conductor
(Approx.)
Nominal
Insulation
Thickness
Diameter
Over Insulation
(Approx.)
mm
5.9
6.9
8.1
9.7
11.4
12.9
14.3
16.0
18.4
20.4
23.2
26.7
30.4
mm
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
mm
16.5
17.5
18.7
20.3
22.0
23.5
24.9
26.6
29.0
31.0
33.8
37.3
41.0
mm
25
35
50
70
95
120
150
185
240
300
400
500
630
Uo/U (Um)=8.7/15(17.5)kV
Overall Diameter
(Approx.)
Weight of Cable
(Approx)
CUT
CUW
CUT
CUW
CUT
CUW
mm
1.8
1.8
1.8
1.8
1.8
1.9
1.9
2.0
2.0
2.1
2.2
2.3
2.4
mm
1.8
1.8
1.8
1.8
1.8
1.9
1.9
2.0
2.1
2.1
2.3
2.4
2.5
mm
22
23
25
26
28
30
31
33
35
38
41
44
49
mm
24
25
26
28
30
31
33
35
37
39
42
46
51
Kg/km
675
800
950
1175
1425
1750
2025
2425
3000
3650
4475
5575
7075
Kg/km
850
925
1075
1300
1575
1850
2225
2625
3225
3825
4800
5900
7375
In single -way
ducts
Capacitance
Conductor
Short Circuit
Current
for 1 second
Trefoil
Flat
Spaced
Trefoil
ducts
Flat
Touching
ducts
Trefoil
Flat
Touching
Flat
Spaced
mm
Ohm/km
mH/km
mH/km
F/km
kA
Amps
Amps
Amps
Amps
Amps
Amps
Amps
V/A.Km
25
35
50
70
95
120
150
185
240
300
400
500
630
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
0.470
0.758
0.21
0.402
0.672
0.29
0.352
0.605
0.43
0.307
0.621
0.470
0.758
0.780
0.19
0.415
0.690
0.27
0.366
0.621
0.39
0.318
0.554
0.477
0.780
0.19
0.17
0.435
0.706
0.25
0.377
0.641
0.35
0.327
0.570
0.53
0.352
0.17
0.435
0.456
0.732
0.23
0.389
0.656
0.32
0.340
0.585
0.48
0.830
0.273
0.456
0.732
140
166
196
239
285
323
361
406
469
526
590
655
731
144
172
203
246
293
332
366
410
470
524
572
625
690
132
157
186
227
271
308
343
387
447
504
564
133
159
188
229
274
311
347
391
453
510
571
635
640
720
163
198
238
296
361
417
473
543
641
735
845
956
1095
167
203
243
303
369
426
481
550
647
739
837
935
196
238
286
356
434
500
559
637
745
846
938
1028
1158
0.830
0.621
0.477
0.352
0.273
0.230
0.198
0.172
0.146
0.128
0.113
0.102
0.092
Size
Flat
In air
Trefoil
Max DC
Resistance
@ 20C
Inductance
Buried
Direct
In
the
ground
Current ratings
712
1061
Laying condition: Maximum conductor temperature 90C, Ambient temperature 30C. Underground temperature of soil 20C, Depth of laying - 0.8m.
Ground thermal resistivity 1.5 K.m/W, thermal resisitivity of earthenware ducts 1.2 K.m/W.
Note: Area of copper wire considered is 16 mm2 up to 120 mm2, 25 mm2 from 150 mm2 up to 300 mm2, 35 mm2 from 400 mm2 up to 630 mm2.
12
IEC 60502-2
6
.
1. Conductor
2. Conductor Screen
3. XLPE Insulation
Size
mm
25
35
50
70
95
120
150
185
240
300
400
500
630
Diameter of
Conductor
(Approx.)
Nominal
Insulation
Thickness
Diameter
Over
Insulation
(Approx.)
mm
5.9
6.9
8.1
9.7
11.4
12.9
14.3
16.0
18.4
20.4
23.2
26.7
30.4
mm
6.0
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
mm
19.5
19.5
20.7
22.3
24.0
25.5
26.9
28.6
31.0
33.0
35.8
39.3
43.0
Uo/U (Um)=12/20(24)kV
Overall Diameter
(Approx.)
Weight of Cable
(Approx)
CUT
CUW
CUT
CUW
CUT
CUW
mm
1.8
1.8
1.8
1.8
1.9
1.9
2.0
2.0
2.1
2.2
2.3
2.4
2.5
mm
1.8
1.8
1.8
1.9
1.9
2.0
2.0
2.1
2.1
2.2
2.3
2.4
2.5
mm
25
25
27
28
30
32
33
35
38
40
43
49
51
mm
27
27
28
30
31
33
35
37
39
41
44
49
53
Kg/km
800
875
1050
1275
1575
1850
2150
2550
3150
3775
4650
5800
7250
Kg/km
925
1000
1150
1400
1675
2000
2350
2750
3350
3975
4925
6100
7525
Capacitance
Conductor
Short Circuit
Current
for 1 second
Trefoil
Flat
Spaced
Trefoil
ducts
Flat
Touching
ducts
Trefoil
Flat
Touching
Flat
Spaced
In air
mm
Ohm/km
mH/km
mH/km
F/km
kA
Amps
Amps
Amps
Amps
Amps
Amps
Amps
25
35
50
70
95
120
150
185
240
300
400
500
630
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
0.497
0.468
0.448
0.426
0.414
0.399
0.388
0.375
0.361
0.350
0.336
0.326
0.315
0.792
0.763
0.738
0.712
0.696
0.677
0.662
0.646
0.626
0.610
0.590
0.575
0.558
0.14
0.16
0.18
0.20
0.21
0.23
0.25
0.27
0.30
0.33
0.37
0.40
0.45
3.575
5.005
7.150
10.010
13.585
17.160
21.450
26.455
34.320
42.900
57.200
71.500
90.090
140
166
196
239
285
323
361
406
469
526
590
655
731
144
172
203
246
293
332
366
410
470
524
572
625
690
132
157
186
227
271
308
343
387
447
504
564
133
159
188
229
274
311
347
391
453
510
571
163
198
238
296
361
417
473
543
641
735
845
956
1095
167
203
243
303
369
426
481
550
647
739
837
935
196
238
286
356
434
500
559
637
745
846
938
1028
1158
635
712
640
720
1061
Buried
Direct
In
the
ground
In single -way
ducts
Flat
Inductance
Trefoil
Max DC
Resistance
@ 20C
Size
Current ratings
V/A.
Km
0.835
0.623
0.480
0.354
0.276
0.232
0.201
0.173
0.147
0.130
0.115
0.103
0.094
Laying condition: Maximum conductor temperature 90C, Ambient temperature 30C. Underground temperature of soil 20C, Depth of laying -0.8m.
Ground thermal resistivity 1.5 K.m/W, thermal resisitivity of earthenware ducts 1.2 K.m/W.
Note: Area of copper wire considered is 16 mm2 up to 120 mm2, 25 mm2 from 150 mm2 up to 300 mm2, 35 mm2 from 400 mm2 up to 630 mm2.
13
IEC 60502-2
Overall Diameter
(Approx.)
Weight of Cable
(Approx)
CUT
CUW
CUT
CUW
CUT
CUW
mm
1.9
2.0
2
2.1
2.1
2.2
2.3
2.3
2.5
2.5
2.7
mm
2.0
2.0
2.1
2.1
2.2
2.2
2.3
2.4
2.5
2.6
2.7
mm
32
34
36
37
38
40
43
45
49
52
56
mm
33
35
37
38
40
42
44
47
50
54
57
Kg/km
1300
1575
1900
2150
2450
2900
3525
4150
5050
6150
7650
Kg/km
1500
1700
2000
2275
2675
3075
3700
4350
5400
6525
8000
In single -way
ducts
Trefoil
Flat
Spaced
Trefoil
ducts
Flat
Touching
ducts
Trefoil
Flat
Touching
Flat
Spaced
In air
Current ratings
Flat
Inductance
Buried
Direct
In
the
ground
mm
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
Diameter
Over
Insulation
(Approx.)
mm
25.7
27.3
29.0
30.5
31.9
33.6
36.0
38.0
40.8
44.3
48.0
Capacitance
Nominal
Insulation
Thickness
Trefoil
Size
mm
50
70
95
120
150
185
240
300
400
500
630
Diameter
of
Conductor
(Approx.)
mm
8.1
9.7
11.4
12.9
14.3
16.0
18.4
20.4
23.2
26.7
30.4
Max DC
Resistance
@ 20C
Size
Conductor
Short Circuit
Current
for 1 second
1. Conductor
2. Conductor Screen
3. XLPE Insulation
Uo/U (Um)=18/30(36)kV
mm
Ohm/km
mH/km
mH/km
F/km
kA
Amps
Amps
Amps
Amps
Amps
Amps
Amps
V/A.Km
50
0.387
0.482
0.755
0.14
7.150
196
203
186
188
238
243
286
0.486
70
0.268
0.457
0.728
0.16
10.010
239
246
227
229
296
303
356
0.36
95
0.193
0.446
0.712
0.17
13.585
285
293
271
274
361
369
434
0.282
120
0.153
0.430
0.693
0.18
17.160
323
332
308
311
417
426
500
0.238
150
0.124
0.417
0.677
0.19
21.450
361
366
343
347
473
481
559
0.206
185
0.0991
0.404
0.661
0.21
26.455
406
410
387
391
543
550
637
0.179
240
0.0754
0.388
0.641
0.23
34.320
469
470
447
453
641
647
745
0.152
300
0.0601
0.375
0.624
0.25
42.900
526
524
504
510
735
739
846
0.135
400
0.0470
0.360
0.604
0.27
57.200
590
572
564
571
845
837
938
0.119
500
0.0366
0.349
0.589
0.30
71.500
655
625
635
640
956
935
1028
0.108
630
0.0283
0.388
0.570
0.33
90.090
731
690
712
720
1095
1061
1158
0.098
Laying condition: Maximum conductor temperature 90C, Ambient temperature 30C. Underground temperature of soil 20C, Depth of laying - 0.8m.
Ground thermal resistivity 1.5 K.m/W, thermal resisitivity of earthenware ducts 1.2 K.m/W.
Note: Area of copper wire considered is 16 mm2 up to 120 mm2, 25 mm2 from 150 mm2 up to 300 mm2, 35 mm2 from 400 mm2 up to 630 mm2.
14
IEC 60502-2
1.
2.
3.
4.
Size
mm
25
35
50
70
95
120
150
185
240
300
400
500
630
Conductor
Conductor Screen
XLPE Insulation
Insulation Screen (Non-metallic)
Diameter of
Conductor
(Approx.)
Nominal
Insulation
Thickness
Diameter
Over
Insulation
(Approx.)
mm
5.9
6.9
8.1
9.7
11.4
12.9
14.3
16.0
18.4
20.4
23.2
26.7
30.4
mm
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.6
2.8
3.0
3.2
3.2
mm
12.5
13.5
14.7
16.3
18.0
19.5
20.9
22.6
25.2
27.6
30.8
34.7
38.4
Uo/U (Um)=3.5/6(7.2)kV
7 6 5 4 3 2 1
Nominal
Outer Sheath
Thickness
Overall
Diameter
(Approx.)
Weight of Cable
(Approx)
CUT/CUW
CUT
CUW
CUT
CUW
CUT
CUW
mm
1.6
1.6
1.6
1.6
1.6
1.6
1.6/2.0
2.0
2.0
2.0
2.0/2.5
2.5
2.5
mm
1.8
1.8
1.8
1.8
1.9
1.9
2.0
2.0
2.1
2.2
2.3
2.5
2.6
mm
1.8
1.8
1.8
1.8
1.9
1.9
2.0
2.0
2.2
2.2
2.4
2.5
2.6
mm
24
25
27
28
30
32
33
36
39
41
45
50
54
mm
26
27
28
30
32
33
35
37
40
43
48
52
56
Kg/km
875
1000
1150
1400
1750
1975
2300
2750
3450
4175
5100
6500
8050
Kg/km
1075
1175
1350
1600
1950
2200
2675
3100
3800
4475
5725
6900
8475
Amps
133
158
186
226
268
303
335
375
425
471
522
578
632
555
604
Amps
162
196
234
291
353
406
460
524
611
692
788
873
975
Amps
165
199
238
294
355
407
454
513
589
657
733
786
Amps
189
228
271
334
401
455
501
559
633
697
764
815
882
858
Amps
131
155
183
223
265
301
334
376
430
478
534
Flat
Spaced
Amps
142
168
197
238
280
313
340
374
416
451
488
509
542
Flat
Touching
Amps
137
164
193
234
278
315
349
391
446
495
551
593
646
In air
Trefoil
Flat
Touching
ducts
kA
3.575
5.005
7.150
10.010
13.585
17.160
21.450
26.455
34.320
42.900
57.200
71.500
90.090
Trefoil
ducts
0.26
0.29
0.32
0.37
0.39
0.44
0.48
0.52
0.56
0.58
0.61
0.64
0.71
Flat
Spaced
F/km
0.785
0.760
0.735
0.708
0.792
0.673
0.658
0.642
0.623
0.608
0.589
0.576
0.558
Buried
Direct
In
the
ground
mH/km
Flat
Trefoil
mH/km
0.473
0.461
0.440
0.418
0.406
0.392
0.380
0.369
0.356
0.346
0.334
0.327
0.315
In single -way
ducts
Trefoil
Ohm/km
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
Conductor
Short Circuit
Current
for 1 second
25
35
50
70
95
120
150
185
240
300
400
500
630
Inductance
Capacitance
mm
Max DC
Resistance
@ 20C
Size
Current ratings
V/A.Km
0.831
0.622
0.478
0.352
0.274
0.231
0.199
0.172
0.146
0.129
0.114
0.103
0.094
Laying condition: Maximum conductor temperature 90C, Ambient temperature 30C. Underground temperature of soil 20C, Depth of laying - 0.8m.
Ground thermal resistivity 1.5 K.m/W, thermal resisitivity of earthenware ducts 1.2 K.m/W.
Note: Area of copper wire considered is 16 mm2 up to 120 mm2, 25 mm2 from 150 mm2 up to 300 mm2, 35 mm2 from 400 mm2 up to 630 mm2.
15
IEC 60502-2
7 6 5 4 3 2 1
1. Conductor
5. Insulation Screen (Metallic)
2. Conductor Screen
6. Bedding
3. XLPE Insulation
7. Aluminium Wire Armour
4. Insulation Screen (Non-metallic)
8. Outer Sheath
Size
mm
25
35
50
70
95
120
150
185
240
300
400
500
630
Diameter of
Conductor
(Approx.)
Nominal
Insulation
Thickness
Diameter
Over
Insulation
(Approx.)
mm
5.9
6.9
8.1
9.7
11.4
12.9
14.3
16.0
18.4
20.4
23.2
26.7
30.4
mm
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
mm
14.3
15.3
16.5
18.1
19.8
21.3
22.7
24.4
26.8
28.8
31.6
35.1
38.8
Nominal
Diameter of
Aluminium Wire
Nominal
Outer Sheath
Thickness
Overall Diameter
(Approx.)
Weight of Cable
(Approx)
CUT/CUW
CUT
CUW
CUT
CUW
CUT
CUW
mm
1.6
1.6
1.6
1.6
1.6
1.6/2.0
2.0
2.0
2.0
2.0
2.0/2.5
2.5
2.5
mm
1.8
1.8
1.8
1.9
1.9
2.0
2
2.1
2.2
2.2
2.4
2.5
2.6
mm
1.8
1.8
1.9
1.9
2.0
2.0
2.1
2.1
2.2
2.3
2.4
2.5
2.7
mm
26
27
28
30
32
33
36
37
40
42
45
50
54
mm
27
28
30
31
33
35
37
39
41
44
48
52
57
Kg/km
950
1075
1275
1500
1850
2150
2575
2925
3625
4250
5175
6525
8050
Kg/km
1200
1325
1500
1750
2050
2450
2825
3225
3925
4575
5775
6950
8575
Flat
Spaced
Trefoil
ducts
Flat
Touching
ducts
Trefoil
Flat
Touching
Flat
Spaced
Ohm/km
mH/km
mH/km
F/km
kA
Amps
Amps
Amps
Amps
Amps
Amps
Amps
25
35
50
70
95
120
150
185
240
300
400
500
630
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
0.488
0.472
0.450
0.428
0.416
0.401
0.390
0.378
0.363
0.351
0.338
0.328
0.317
0.790
0.765
0.739
0.713
0.697
0.678
0.663
0.647
0.627
0.611
0.591
0.576
0.560
0.21
0.23
0.25
0.29
0.31
0.34
0.37
0.40
0.45
0.49
0.55
0.60
0.68
3.575
5.005
7.150
10.010
13.585
17.160
21.450
26.455
34.320
42.900
57.200
71.500
90.090
137
164
193
234
278
315
349
391
446
495
551
593
646
142
168
197
238
280
313
340
374
416
451
488
509
542
131
155
183
223
265
301
334
376
430
478
534
133
158
186
226
268
303
335
375
425
471
522
162
196
234
291
353
406
460
524
611
692
788
873
975
165
199
238
294
355
407
454
513
589
657
733
786
189
228
271
334
401
455
501
559
633
697
764
815
882
578
632
555
604
858
Trefoil
mm
Size
Conductor
Short Circuit
Current
for 1 second
In air
Capacitance
Buried
Direct
In
the
ground
In single -way
ducts
Flat
Inductance
Trefoil
Max DC
Resistance
@ 20C
Current ratings
V/A.
Km
0.833
0.624
0.48
0.354
0.276
0.233
0.201
0.174
0.147
0.130
0.115
0.103
0.094
Laying condition: Maximum conductor temperature 90C, Ambient temperature 30C. Underground temperature of soil 20C, Depth of laying - 0.8m.
Ground thermal resistivity 1.5 K.m/W, thermal resisitivity of earthenware ducts 1.2 K.m/W.
Note: Area of copper wire considered is 16 mm2 up to 120 mm2, 25 mm2 from 150 mm2 up to 300 mm2, 35 mm2 from 400 mm2 up to 630 mm2.
16
IEC 60502-2
1.
2.
3.
4.
Conductor
Conductor Screen
XLPE Insulation
Insulation Screen (Non-metallic)
7 6 5 4 3 2 1
Size
Diameter of
Conductor
(Approx.)
Nominal
Insulation
Thickness
Diameter
Over
Insulation
(Approx.)
mm
25
35
50
70
95
120
150
185
240
300
400
500
630
mm
5.9
6.9
8.1
9.7
11.4
12.9
14.3
16.0
18.4
20.4
23.2
26.7
30.4
mm
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
mm
16.5
17.5
18.7
20.3
22.0
23.5
24.9
26.6
29.0
31.0
33.8
37.3
41.0
Nominal
Diameter of
Aluminium Wire
Nominal Outer
Sheath Thickness
Overall Diameter
(Approx.)
Weight of Cable
(Approx)
CUT/CUW
CUT
CUW
CUT
CUW
CUT
CUW
mm
1.6
1.6
1.6
1.6
2.0
2.0
2.0
2.0
2.0
2.0/2.5
2.5
2.5
2.5
mm
1.8
1.9
1.9
1.9
2.0
2.1
2.1
2.2
2.3
2.3
2.5
2.6
2.7
mm
1.9
1.9
1.9
2.0
2.1
2.1
2.2
2.2
2.3
2.4
2.5
2.6
2.7
mm
28
29
30
32
35
36
38
40
42
44
49
52
57
mm
30
31
32
34
36
38
40
41
44
47
50
54
59
Kg/km
1100
1250
1375
1650
2050
2350
2675
3150
3800
4450
5575
6725
8300
Kg/km
1325
1475
1625
1875
2300
2600
3000
3450
4125
4975
6000
7200
8775
Amps
133
158
186
226
268
303
335
375
425
471
522
578
632
555
604
Amps
162
196
234
291
353
406
460
524
611
692
788
873
975
Amps
165
199
238
294
355
407
454
513
589
657
733
786
Amps
189
228
271
334
401
455
501
559
633
697
764
815
882
858
Amps
131
155
183
223
265
301
334
376
430
478
534
Flat
Spaced
Amps
142
168
197
238
280
313
340
374
416
451
488
509
542
Flat
Touching
Amps
137
164
193
234
278
315
349
391
446
495
551
593
646
In air
Trefoil
Flat
Touching
ducts
kA
3.575
5.005
7.150
10.010
13.585
17.160
21.450
26.455
34.320
42.900
57.200
71.500
90.090
Trefoil
ducts
0.17
0.19
0.21
0.23
0.25
0.27
0.29
0.32
0.35
0.39
0.43
0.48
0.53
Flat
Spaced
F/km
0.796
0.771
0.745
0.719
0.703
0.684
0.668
0.652
0.632
0.616
0.596
0.582
0.565
Buried
Direct
In
the
ground
mH/km
In single -way
ducts
Trefoil
Trefoil
mH/km
0.505
0.484
0.463
0.441
0.428
0.413
0.401
0.388
0.373
0.361
0.346
0.337
0.325
Conductor
Short Circuit
Current
for 1 second
Ohm/km
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
Capacitance
25
35
50
70
95
120
150
185
240
300
400
500
630
Inductance
Flat
mm
Max DC
Resistance
@ 20C
Size
Current ratings
V/A.Km
0.837
0.626
0.482
0.357
0.278
0.235
0.203
0.176
0.149
0.132
0.117
0.105
0.095
Laying condition: Maximum conductor temperature 90C, Ambient temperature 30C. Underground temperature of soil 20C, Depth of laying - 0.8m.
Ground thermal resistivity 1.5 K.m/W, thermal resisitivity of earthenware ducts 1.2 K.m/W.
Note: Area of copper wire considered is 16 mm2 up to 120 mm2, 25 mm2 from 150 mm2 up to 300 mm2, 35 mm2 from 400 mm2 up to 630 mm2.
17
IEC 60502-2
8
.
1.
2.
3.
4.
Conductor
Conductor Screen
XLPE Insulation
Insulation Screen (Non-metallic)
Size
Diameter of
Conductor
(Approx.)
Nominal
Insulation
Thickness
Diameter
Over
Insulation
(Approx.)
mm
25
35
50
70
95
120
150
185
240
300
400
500
630
mm
5.9
6.9
8.1
9.7
11.4
12.9
14.3
16.0
18.4
20.4
23.2
26.7
30.4
mm
6.0
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
mm
19.5
19.5
20.7
22.3
24.0
25.5
26.9
28.6
31.0
33.0
35.8
39.3
43.0
7 6 5 4 3 2 1
Nominal
Diameter of
Aluminium Wire
Nominal
Outer Sheath
Thickness
Overall Diameter
(Approx.)
Weight of Cable
(Approx)
CUT/CUW
CUT
CUW
CUT
CUW
CUT
CUW
mm
1.6
1.6
1.6
2.0
2.0
2.0
2.0
2.0
2.0/2.5
2.5
2.5
2.5
2.5
mm
1.9
1.9
2.0
2.0
2.1
2.1
2.2
2.2
2.3
2.4
2.5
2.6
2.8
mm
2.0
2.0
2.0
2.1
2.1
2.2
2.2
2.3
2.4
2.5
2.6
2.7
2.8
mm
31
31
33
35
37
38
40
42
44
48
51
55
59
mm
33
33
35
37
38
40
41
43
47
49
53
57
61
Kg/km
1300
1375
1550
1850
2200
2550
2900
3275
3975
4825
5725
7000
8550
Kg/km
1525
1600
1825
2100
2475
2800
3175
3650
4500
5175
6250
7500
9050
Amps
133
158
186
226
268
303
335
375
425
471
522
578
555
604
632
Amps
162
196
234
291
353
406
460
524
611
692
788
873
975
Amps
165
199
238
294
355
407
454
513
589
657
733
786
Amps
189
228
271
334
401
455
501
559
633
697
764
815
882
858
Amps
131
155
183
223
265
301
334
376
430
478
534
Flat
Spaced
Amps
142
168
197
238
280
313
340
374
416
451
488
509
542
Flat
Touching
Amps
137
164
193
234
278
315
349
391
446
495
551
593
646
In air
Trefoil
Flat
Touching
ducts
kA
3.575
5.005
7.150
10.010
13.585
17.160
21.450
26.455
34.320
42.900
57.200
71.500
90.090
Trefoil
ducts
0.14
0.16
0.18
0.20
0.21
0.23
0.25
0.27
0.30
0.33
0.37
0.40
0.45
Flat
Spaced
F/km
0.805
0.776
0.751
0.724
0.708
0.689
0.673
0.657
0.637
0.621
0.601
0.586
0.569
Buried
Direct
In
the
ground
mH/km
In single -way
ducts
Trefoil
Trefoil
mH/km
0.504
0.496
0.474
0.452
0.438
0.423
0.410
0.397
0.392
0.370
0.345
0.355
0.333
Conductor
Short Circuit
Current
for 1 second
Ohm/km
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
Capacitance
25
35
50
70
95
120
150
185
240
300
400
500
630
Inductance
Flat
mm
Max DC
Resistance
@ 20C
Size
Current ratings
V/A.Km
0.841
0.628
0.484
0.359
0.280
0.237
0.205
0.178
0.153
0.133
0.118
0.106
0.097
Laying condition: Maximum conductor temperature 90C, Ambient temperature 30C. Underground temperature of soil 20C, Depth of laying - 0.8m.
Ground thermal resistivity 1.5 K.m/W, thermal resisitivity of earthenware ducts 1.2 K.m/W.
Note: Area of copper wire considered is 16 mm2 up to 120 mm2, 25 mm2 from 150 mm2 up to 300 mm2, 35 mm2 from 400 mm2 up to 630 mm2.
18
IEC 60502-2
1.
2.
3.
4.
Size
Conductor
Conductor Screen
XLPE Insulation
Insulation Screen (Non-metallic)
Diameter of
Conductor
(Approx.)
Nominal
Insulation
Thickness
Diameter
Over
Insulation
(Approx.)
mm
8.1
9.7
11.4
12.9
14.3
16.0
18.4
20.4
23.2
26.7
30.4
mm
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
mm
25.7
27.3
29.0
30.5
31.9
33.6
36.0
38.0
40.8
44.3
48.0
mm
50
70
95
120
150
185
240
300
400
500
630
Uo/U (Um)=18/30(36) kV
7 6 5 4 3 2 1
Nominal
Diameter of
Aluminium Wire
Nominal
Outer Sheath
Thickness
Overall Diameter
(Approx.)
Weight of Cable
(Approx)
CUT/CUW
CUT
CUW
CUT
CUW
CUT
CUW
mm
2.0
2.0
2.0
2.0/2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
mm
2.2
2.2
2.3
2.3
2.4
2.5
2.5
2.6
2.7
2.8
2.9
mm
2.2
2.3
2.3
2.4
2.5
2.5
2.6
2.7
2.8
2.9
3.0
mm
39
40
42
44
47
49
51
53
57
61
65
mm
40
42
44
46
48
50
53
55
59
63
67
Kg/km
2025
2300
2675
2950
3500
3925
4600
5375
6350
7600
9100
Kg/km
2250
2575
2900
3225
3850
4300
5025
5725
6850
8100
9700
Trefoil
ducts
Flat
Touching
ducts
Trefoil
Flat
Touching
Flat
Spaced
Flat
Spaced
Ohm/km
mH/km
mH/km
F/km
kA
Amps
Amps
Amps
Amps
Amps
Amps
Amps
50
0.387
0.504
0.766
0.14
7.150
193
197
183
186
234
238
271
0.490
70
0.268
0.481
0.740
0.16
10.010
234
238
223
226
291
294
334
0.364
Conductor
Short Circuit
Current
for 1 second
mm
Size
Trefoil
In air
Capacitance
Buried
Direct
In
the
ground
In single -way
ducts
Flat
Inductance
Trefoil
Max DC
Resistance
@ 20C
Current ratings
V/A.Km
95
0.193
0.467
0.723
0.17
13.585
278
280
265
268
353
355
401
0.286
120
0.153
0.450
0.704
0.18
17.160
315
313
301
303
406
407
455
0.242
150
0.124
0.437
0.688
0.19
21.450
349
340
334
335
460
454
501
0.21
185
0.0991
0.424
0.672
0.21
26.455
391
374
376
375
524
513
559
0.182
240
0.0754
0.407
0.652
0.23
34.320
446
416
430
425
611
589
633
0.156
300
0.0601
0.394
0.635
0.25
42.900
495
451
478
471
692
657
697
0.138
400
0.0470
0.377
0.614
0.27
57.200
551
488
534
522
788
733
764
0.122
500
0.0366
0.366
0.599
0.30
71.500
593
509
578
555
873
786
815
0.111
630
0.0283
0.357
0.582
0.33
90.090
646
542
632
604
975
858
882
0.101
Laying condition: Maximum conductor temperature 90C, Ambient temperature 30C. Underground temperature of soil 20C, Depth of laying - 0.8m.
Ground thermal resistivity 1.5 K.m/W, thermal resisitivity of earthenware ducts 1.2 K.m/W.
Note: Area of copper wire considered is 16 mm2 up to 120 mm2, 25 mm2 from 150 mm2 up to 300 mm2, 35 mm2 from 400 mm2 up to 630 mm2.
19
IEC 60502-2
1.
2.
3.
4.
Size
mm
25
35
50
70
95
120
150
185
240
300
Conductor
Conductor Screen
XLPE Insulation
Insulation Screen (Non-metallic)
Diameter of
Conductor
(Approx.)
Nominal
Insulation
Thickness
Diameter
Over Insulation
(Approx.)
mm
5.9
6.9
8.1
9.7
11.4
12.9
14.3
16.0
18.4
20.4
mm
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.6
2.8
mm
12.5
13.5
14.7
16.3
18.
19.5
20.9
22.6
25.2
27.6
Size
Max DC
Resistance
@ 20C
Nominal
Inductance
mm
25
35
50
70
95
120
150
185
240
300
Ohm/km
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
mH/km
0.305
0.294
0.283
0.272
0.266
0.259
0.253
0.250
0.243
0.236
Capacitance
F/km
0.26
0.29
0.32
0.36
0.39
0.43
0.47
0.52
0.56
0.58
Uo/U (Um)=3.5/6(7.2)kV
7 6 5 4 3 2 1
Overall Diameter
(Approx.)
Weight of Cable
(Approx)
CUT
CUW
CUT
CUW
CUT
CUW
mm
2.1
2.1
2.2
2.3
2.5
2.6
2.7
2.8
3.0
3.2
mm
2.1
2.2
2.3
2.4
2.5
2.6
2.8
2.9
3.0
3.2
mm
39
41
44
48
52
56
59
63
69
75
mm
42
44
47
51
55
59
62
66
72
78
Kg/km
1925
2300
2775
3550
4500
5350
6350
7550
9500
11650
Kg/km
2075
2450
2950
3700
4600
5475
6550
7725
9675
11875
Conductor
Short Circuit
Current
for 1 second
kA
3.575
5.005
7.150
10.010
13.585
17.160
21.450
26.455
34.320
42.900
Current ratings
Buried Direct
In the ground
In buried ducts
In air
Voltage drop
Per phase
Amps
129
153
181
221
262
298
334
377
434
489
Amps
112
133
158
193
231
264
297
336
390
441
Amps
142
170
204
253
304
351
398
455
531
606
V/A.Km
0.799
0.590
0.448
0.325
0.248
0.206
0.175
0.150
0.125
0.108
Laying condition: Maximum conductor temperature 90C, Ambient temperature 30C. Underground temperature of soil 20C, Depth of laying - 0.8m.
Ground thermal resistivity 1.5 K.m/W, thermal resisitivity of earthenware ducts 1.2 K.m/W.
Note: Area of copper wire considered is 16 mm2 up to 120 mm2, 25 mm2 from 150 mm2 up to 300 mm2, 35 mm2 from 400 mm2 up to 630 mm2.
20
IEC 60502-2
1.
2.
3.
4.
Size
mm
25
35
50
70
95
120
150
185
240
300
Conductor
Conductor Screen
XLPE Insulation
Insulation Screen (Non-metallic)
Diameter of
Conductor
(Approx.)
Nominal
Insulation
Thickness
Diameter
Over
Insulation
(Approx.)
mm
5.9
6.9
8.1
9.7
11.4
12.9
14.3
16.0
18.4
20.4
mm
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
mm
14.3
15.3
16.5
18.1
19.8
21.3
22.7
24.4
26.8
28.8
Size
Max DC
Resistance
@ 20C
Nominal
Inductance
mm
25
35
50
70
95
120
150
185
240
300
Ohm/km
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
mH/km
0.331
0.318
0.305
0.292
0.285
0.276
0.269
0.263
0.255
0.248
F/km
0.21
0.23
0.25
0.29
0.31
0.34
0.37
0.40
0.44
0.48
7 6 5 4 3 2 1
Capacitance
Uo/U (Um)=6/10(12)kV
Overall Diameter
(Approx.)
Weight of Cable
(Approx)
CUT
CUW
CUT
CUW
CUT
CUW
mm
2.2
2.3
2.4
2.5
2.6
2.7
2.8
2.9
3.1
3.3
mm
2.2
2.3
2.4
2.5
2.7
2.8
2.9
3.0
3.2
3.3
mm
43
46
48
52
56
60
63
67
73
78
mm
46
48
51
55
59
63
65
70
76
81
Kg/km
2125
2575
3050
3825
4750
5675
6625
7875
9900
11975
Kg/km
2300
2750
3250
4000
5000
5850
6875
8150
10225
12200
Conductor
Short Circuit
Current
for 1 second
kA
3.575
5.005
7.150
10.010
13.585
17.160
21.450
26.455
34.320
42.900
Current ratings
Buried Direct
In the ground
In buried ducts
In air
Voltage drop
Per phase
Amps
129
153
181
221
262
298
334
377
434
489
Amps
112
133
158
193
231
264
297
336
390
441
Amps
142
170
204
253
304
351
398
455
531
606
V/A.Km
0.804
0.595
0.453
0.329
0.252
0.209
0.179
0.152
0.127
0.111
Laying condition: Maximum conductor temperature 90C, Ambient temperature 30C. Underground temperature of soil 20C, Depth of laying 0.8m.
Ground thermal resistivity 1.5 K.m/W, thermal resisitivity of earthenware ducts 1.2 K.m/W.
Note: Area of copper wire considered is 16 mm2 up to 120 mm2, 25 mm2 from 150 mm2 up to 300 mm2, 35 mm2 from 400 mm2 up to 630 mm2.
21
IEC 60502-2
1.
2.
3.
4.
Conductor
Conductor Screen
XLPE Insulation
Insulation Screen (Non-metallic)
size
Diameter of
Conductor
(Approx.)
Nominal
Insulation
Thickness
mm
25
35
50
70
95
120
150
185
240
300
mm
5.9
6.9
8.1
9.7
11.4
12.9
14.3
16.0
18.4
20.4
mm
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
Size
Max DC
Resistance
@ 20C
Nominal
Inductance
mm
25
35
50
70
95
120
150
185
240
300
Ohm/km
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
mH/km
0.359
0.344
0.329
0.314
0.306
0.296
0.288
0.280
0.271
0.260
Diameter
Over
Insulation
(Approx.)
mm
16.5
17.5
18.7
20.3
22.0
23.5
24.9
26.6
29.0
31.0
F/km
0.17
0.19
0.21
0.23
0.25
0.27
0.29
0.32
0.35
0.39
7 6 5 4 3 2 1
Capacitance
Uo/U (Um)=8.7/15(17.5)kV
Overall Diameter
(Approx.)
Weight of Cable
(Approx)
CUT
CUW
CUT
CUW
CUT
CUW
mm
2.4
2.5
2.6
2.7
2.8
2.9
3.0
3.1
3.3
3.4
mm
2.4
2.5
2.6
2.7
2.8
2.9
3.1
3.2
3.3
3.5
mm
47
51
53
58
61
65
66
72
78
83
mm
50
54
56
61
64
68
71
76
81
86
Kg/km
2550
2950
3450
4300
5275
6150
7125
8500
10550
12550
Kg/km
2700
3125
3600
4450
5425
6300
7400
8800
10775
12800
Conductor
Short Circuit
Current
for 1 second
kA
3.575
5.005
7.150
10.010
13.585
17.160
21.450
26.455
34.320
42.900
Current ratings
Buried Direct
In the ground
In buried ducts
In air
Voltage drop
Per phase
Amps
129
153
181
221
262
298
334
377
434
489
Amps
112
133
158
193
231
264
297
336
390
441
Amps
142
170
204
253
304
351
398
455
531
606
V/A.Km
0.809
0.600
0.457
0.333
0.255
0.213
0.182
0.155
0.130
0.113
Laying condition: Maximum conductor temperature 90C, Ambient temperature 30C. Underground temperature of soil 20C, Depth of laying - 0.8m.
Ground thermal resistivity 1.5 K.m/W, thermal resisitivity of earthenware ducts 1.2 K.m/W.
Note: Area of copper wire considered is 16 mm2 up to 120 mm2, 25 mm2 from 150 mm2 up to 300 mm2, 35 mm2 from 400 mm2 up to 630 mm2.
22
IEC 60502-2
1.
2.
3.
4.
Conductor
Conductor Screen
XLPE Insulation
Insulation Screen (Non-metallic)
Size
Diameter of
Conductor
(Approx.)
Nominal
Insulation
Thickness
mm
25
35
50
70
95
120
150
185
240
300
mm
5.9
6.9
8.1
9.7
11.4
12.9
14.3
16.0
18.4
20.4
mm
6.0
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
Diameter
Over
Insulation
(Approx.)
mm
19.5
19.5
20.7
22.3
24.0
25.5
26.9
28.6
31.0
33.0
Size
Max DC
Resistance
@ 20C
Nominal
Inductance
mm
Ohm/km
mH/km
F/km
25
35
50
70
95
120
150
185
240
300
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
0.394
0.365
0.349
0.332
0.323
0.312
0.303
0.295
0.285
0.270
0.14
0.16
0.18
0.20
0.21
0.23
0.25
0.27
0.30
0.33
Uo/U (Um)=12/20(24)kV
7 6 5 4 3 2 1
Overall Diameter
(Approx.)
Weight of Cable
(Approx)
CUT
CUW
CUT
CUW
CUT
CUW
mm
2.6
2.6
2.7
2.8
2.9
3.0
3.1
3.3
3.4
3.6
mm
2.6
2.7
2.8
2.9
3.0
3.1
3.2
3.3
3.5
3.6
mm
55
55
58
62
66
70
73
78
83
88
mm
59
59
62
65
69
73
76
80
86
90
Kg/km
3075
3900
4000
4725
5700
6700
7775
9100
11100
13150
Kg/km
3275
3550
4100
4900
6000
6900
8000
9325
11300
13350
Capacitance
Conductor
Short Circuit
Current
for 1 second
Current ratings
Buried Direct
In the ground
In buried ducts
In air
Voltage drop
Per phase
kA
Amps
Amps
Amps
V/A.Km
3.575
5.005
7.150
10.010
13.585
17.160
21.450
26.455
34.320
42.900
129
153
181
221
262
298
334
377
434
489
112
133
158
193
231
264
297
336
390
441
142
170
204
253
304
351
398
455
531
606
0.816
0.604
0.461
0.336
0.258
0.216
0.185
0.158
0.133
0.115
Laying condition: Maximum conductor temperature 90C, Ambient temperature 30C. Underground temperature of soil 20C, Depth of laying - 0.8m.
Ground thermal resistivity 1.5 K.m/W, thermal resisitivity of earthenware ducts 1.2 K.m/W.
Note: Area of copper wire considered is 16 mm2 up to 120 mm2, 25 mm2 from 150 mm2 up to 300 mm2, 35 mm2 from 400 mm2 up to 630 mm2.
23
IEC 60502-2
1.
2.
3.
4.
Size
mm
50
70
95
120
150
185
240
300
Conductor
Conductor Screen
XLPE Insulation
Insulation Screen (Non-metallic)
Diameter of
Conductor
(Approx.)
Nominal
Insulation
Thickness
Diameter
Over Insulation
(Approx.)
mm
8.1
9.7
11.4
12.9
14.3
16.0
18.4
20.4
mm
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
mm
25.7
27.3
29.0
30.5
31.9
33.6
36.0
38.0
Size
Max DC
Resistance
@ 20C
Nominal
Inductance
mm
Ohm/km
mH/km
F/km
50
0.387
0.399
0.14
70
0.268
0.380
0.16
95
0.193
0.369
0.17
120
0.153
0.355
150
0.124
185
Uo/U (Um)=18/30(36)kV
7 6 5 4 3 2 1
Overall Diameter
(Approx.)
Weight of Cable
(Approx)
CUT
CUW
CUT
CUW
CUT
CUW
mm
3.1
3.2
3.3
3.4
3.5
3.6
3.8
4.0
mm
3.1
3.2
3.4
3.5
3.6
3.7
3.9
4.0
mm
71
75
78
82
85
89
95
100
mm
73
77
81
85
88
92
98
102
Kg/km
5100
6100
7150
8100
9150
10500
12600
14900
Kg/km
5250
6200
7300
8300
9400
10750
12950
15050
Conductor
Short Circuit
Current
for 1 second
Current ratings
Buried Direct
In the ground
In buried ducts
In air
Voltage drop
Per phase
kA
Amps
Amps
Amps
V/A.Km
7.150
181
158
204
0.47
10.010
221
193
253
0.345
13.585
262
231
304
0.267
0.18
17.160
298
264
351
0.224
0.345
0.19
21.450
334
297
398
0.192
0.0991
0.334
0.21
26.455
377
336
455
0.166
240
0.0754
0.321
0.23
34.320
434
390
531
0.14
300
0.0601
0.308
0.25
42.900
489
441
606
0.122
Capacitance
Laying condition: Maximum conductor temperature 90C, Ambient temperature 30C. Underground temperature of soil 20C, Depth of laying - 0.8m.
Ground thermal resistivity 1.5 K.m/W, thermal resisitivity of earthenware ducts 1.2 K.m/W.
Note: Area of copper wire considered is 16 mm2 up to 120 mm2, 25 mm2 from 150 mm2 up to 300 mm2, 35 mm2 from 400 mm2 up to 630 mm2.
24
IEC 60502-2
1.
2.
3.
4.
5.
Size
mm
25
35
50
70
95
120
150
185
240
300
Conductor
Conductor Screen
XLPE Insulation
Insulation Screen (Non-metallic)
Insulation Screen (Metallic)
Diameter of
Conductor
(Approx.)
Nominal
Insulation
Thickness
Diameter
Over
Insulation
(Approx.)
mm
5.9
6.9
8.1
9.7
11.4
12.9
14.3
16.0
18.4
20.4
mm
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.6
2.8
mm
12.5
13.5
14.7
16.3
18.0
19.5
20.9
22.6
25.2
27.6
Size
Max DC
Resistance
@ 20C
Nominal
Inductance
mm
25
35
50
70
95
120
150
185
240
300
Ohm/km
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
mH/km
0.363
0.344
0.333
0.322
0.316
0.309
0.303
0.300
0.293
0.286
Capacitance
F/km
0.26
0.29
0.32
0.36
0.39
0.43
0.47
0.52
0.56
0.58
Uo/U (Um)=3.5/6(7.2) kV
765 4 3 2 1
6. PP Filler
7. Bedding
8. Steel Wire Armour
9. Outer Sheath
Nominal
Diameter of
steel wire
Nominal
Outer Sheath
Thickness
CUT/CUW
CUT
CUW
CUT
CUW
CUT
CUW
mm
2.0
2.0/2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5/3.15
3.15
mm
2.3
2.3
2.5
2.6
2.7
2.8
2.9
3.1
3.3
3.5
mm
2.3
2.4
2.5
2.6
2.8
2.9
3.0
3.1
3.4
3.6
mm
43
45
49
53
57
61
64
68
74
82
mm
46
50
52
56
60
64
67
71
78
85
Kg/km
3300
3750
4775
5725
6800
7850
8900
10375
12600
16050
Kg/km
3675
4475
5100
6000
7150
8150
9350
10750
13950
16475
Conductor
Short Circuit
Current
for 1 second
kA
3.575
5.005
7.150
10.010
13.585
17.160
21.450
26.455
34.320
42.900
Overall Diameter
(Approx.)
Weight of Cable
(Approx)
Current ratings
Buried Direct
In the ground
Amps
129
154
181
220
263
298
332
374
431
482
In buried ducts
In air
Voltage drop
Per phase
Amps
112
134
158
194
232
264
296
335
387
435
Amps
143
172
205
253
307
352
397
453
529
599
V/A.Km
0.81
0.60
0.458
0.334
0.257
0.215
0.185
0.159
0.124
0.118
Laying condition: Maximum conductor temperature 90C, Ambient temperature 30C. Underground temperature of soil 20C, Depth of laying - 0.8m.
Ground thermal resistivity 1.5 K.m/W, thermal resisitivity of earthenware ducts 1.2 K.m/W.
Note: Area of copper wire considered is 16 mm2 up to 120 mm2, 25 mm2 from 150 mm2 up to 300 mm2, 35 mm2 from 400 mm2 up to 630 mm2.
25
IEC 60502-2
1.
2.
3.
4.
5.
Size
mm
25
35
50
70
95
120
150
185
240
300
Conductor
Conductor Screen
XLPE Insulation
Insulation Screen (Non-metallic)
Insulation Screen (Metallic)
Diameter of
Conductor
(Approx.)
Nominal
Insulation
Thickness
Diameter
Over
Insulation
(Approx.)
mm
5.9
6.9
8.1
9.7
11.4
12.9
14.3
16.0
18.4
20.4
mm
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
mm
14.3
15.3
16.5
18.1
19.8
21.3
22.7
24.4
26.8
28.8
Size
Max DC
Resistance
@ 20C
Nominal
Inductance
mm
25
35
50
70
95
120
150
185
240
300
Ohm/km
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
mH/km
0.387
0.368
0.355
0.342
0.335
0.326
0.319
0.313
0.305
0.297
Capacitance
F/km
0.21
0.23
0.25
0.29
0.31
0.34
0.37
0.40
0.44
0.48
Uo/U (Um)=6/10(12)kV
765 4 3 2 1
6. PP Filler
7. Bedding
8. Steel Wire Armour
9. Outer Sheath
Nominal
Diameter of
steel wire
Nominal Outer
Sheath Thickness
Overall Diameter
(Approx.)
Weight of Cable
(Approx)
CUT/CUW
CUT
CUW
CUT
CUW
CUT
CUW
mm
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
3.15
3.15
mm
2.4
2.5
2.6
2.7
2.9
3.0
3.1
3.2
3.4
3.6
mm
2.5
2.6
2.7
2.8
2.9
3.0
3.1
3.3
3.5
3.6
mm
48
51
54
57
62
65
68
72
80
85
mm
52
54
57
61
65
68
72
76
83
88
Kg/km
4150
4625
5300
6200
7425
8475
9550
11000
14300
16625
Kg/km
4450
5000
5625
6575
7700
8750
9975
11425
14775
17050
Conductor
Short Circuit
Current
for 1 second
kA
3.575
5.005
7.150
10.010
13.585
17.160
21.450
26.455
34.320
42.900
Current ratings
Buried Direct
In the ground
Amps
129
154
181
220
263
298
332
374
431
482
In buried ducts
In air
Voltage drop
Per phase
Amps
112
134
158
194
232
264
296
335
387
435
Amps
143
172
205
253
307
352
397
453
529
599
V/A.Km
0.815
0.604
0.462
0.338
0.261
0.218
0.188
0.161
0.137
0.120
Laying condition: Maximum conductor temperature 90C, Ambient temperature 30C. Underground temperature of soil 20C, Depth of laying - 0.8m.
Ground thermal resistivity 1.5 K.m/W, thermal resisitivity of earthenware ducts 1.2 K.m/W.
Note: Area of copper wire considered is 16 mm2 up to 120 mm2, 25 mm2 from 150 mm2 up to 300 mm2, 35 mm2 from 400 mm2 up to 630 mm2.
26
IEC 60502-2
1.
2.
3.
4.
5.
Size
mm
25
35
50
70
95
120
150
185
240
300
Conductor
Conductor Screen
XLPE Insulation
Insulation Screen (Non-metallic)
Insulation Screen (Metallic)
Uo/U (Um)=8.7/15(17.5)kV
765 4 3 2 1
6. PP Filler
7. Bedding
8. Steel Wire Armour
9. Outer Sheath
Nominal
Outer Sheath
Thickness
Diameter of
Conductor
(Approx.)
Nominal
Insulation
Thickness
Diameter
Over
Insulation
(Approx.)
Nominal Diameter
of steel wire
CUT/CUW
CUT
CUW
CUT
CUW
CUT
CUW
mm
5.9
6.9
8.1
9.7
11.4
12.9
14.3
16.0
18.4
20.4
mm
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
mm
16.5
17.5
18.7
20.3
22.0
23.5
24.9
26.6
29.0
31.0
mm
2.5
2.5
2.5
2.5
2.5
2.5
2.5/3.15
3.15
3.15
3.15
mm
2.6
2.7
2.8
2.9
3.0
3.1
3.2
3.4
3.6
3.7
mm
2.6
2.7
2.8
3.0
3.1
3.2
3.3
3.5
3.7
3.8
mm
53
56
59
63
67
70
75
80
86
91
mm
56
59
62
66
70
74
78
83
89
94
Kg/km
4800
5300
5950
6925
8100
9175
10325
12900
15225
17525
Kg/km
5075
5575
6300
7300
8425
9525
11625
13300
15625
17975
Size
Max DC
Resistance
@ 20C
Nominal
Inductance
mm
25
35
50
70
95
120
150
185
240
300
Ohm/km
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
mH/km
0.413
0.394
0.379
0.364
0.356
0.346
0.338
0.330
0.321
0.312
Capacitance
F/km
0.17
0.19
0.21
0.23
0.25
0.27
0.29
0.32
0.35
0.39
Conductor
Short Circuit
Current
for 1 second
kA
3.575
5.005
7.150
10.010
13.585
17.160
21.450
26.455
34.320
42.900
Overall Diameter
(Approx.)
Weight of Cable
(Approx)
Current ratings
Buried Direct
In the ground
Amps
129
154
181
220
263
298
332
374
431
482
In buried ducts
In air
Voltage drop
Per phase
Amps
112
134
158
194
232
264
296
335
387
435
Amps
143
172
205
253
307
352
397
453
529
599
V/A.Km
0.820
0.609
0.466
0.342
0.265
0.222
0.191
0.165
0.140
0.123
Laying condition: Maximum conductor temperature 90C, Ambient temperature 30C. Underground temperature of soil 20C, Depth of laying - 0.8m.
Ground thermal resistivity 1.5 K.m/W, thermal resisitivity of earthenware ducts 1.2 K.m/W.
Note: Area of copper wire considered is 16 mm2 up to 120 mm2, 25 mm2 from 150 mm2 up to 300 mm2, 35 mm2 from 400 mm2 up to 630 mm2.
27
IEC 60502-2
1.
2.
3.
4.
5.
SIZE
mm
25
35
50
70
95
120
150
185
240
300
Conductor
Conductor Screen
XLPE Insulation
Insulation Screen (Non-metallic)
Insulation Screen (Metallic)
Diameter of
Conductor
(Approx.)
Nominal
Insulation
Thickness
Diameter
Over Insulation
(Approx.)
mm
5.9
6.9
8.1
9.7
11.4
12.9
14.3
16.0
18.4
20.4
mm
6.0
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
mm
19.5
19.5
20.7
22.3
24.0
25.5
26.9
28.6
31.0
33.0
Size
Max DC
Resistance
@ 20C
Nominal
Inductance
mm
25
35
50
70
95
120
150
185
240
300
Ohm/km
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
mH/km
0.444
0.415
0.399
0.382
0.373
0.362
0.353
0.345
0.335
0.320
Capacitance
F/km
0.14
0.16
0.18
0.20
0.21
0.23
0.25
0.27
0.30
0.33
Uo/U (Um)=12/20(24)kV
765 4 3 2 1
6. PP Filler
7. Bedding
8. Steel Wire Armour
9. Outer Sheath
Nominal
Diameter of steel
wire
Nominal Outer
Sheath Thickness
Overall Diameter
(Approx.)
Weight of Cable
(Approx)
CUT/CUW
CUT
CUW
CUT
CUW
CUT
CUW
mm
2.5
2.5
2.5
2.5
2.5
3.15
3.15
3.15
3.15
3.15
mm
2.8
2.8
3
3.1
3.2
3.3
3.4
3.6
3.7
3.9
mm
2.9
2.9
3.0
3.1
3.3
3.4
3.5
3.6
3.8
4.0
mm
61
61
64
68
73
77
81
85
91
95
mm
64
64
67
71
75
81
84
88
94
99
Kg/km
5675
5900
6600
7600
8850
10875
12100
13775
16050
18400
Kg/km
5975
6200
6925
7925
9100
11300
12600
14125
16525
18900
Conductor
Short Circuit
Current
for 1 second
kA
3.575
5.005
7.150
10.010
13.585
17.160
21.450
26.455
34.320
42.900
Current ratings
Buried Direct
In the ground
Amps
129
154
181
220
263
298
332
374
431
482
In buried ducts
In air
Voltage drop
Per phase
Amps
112
134
158
194
232
264
296
335
387
435
Amps
143
172
205
253
307
352
397
453
529
599
V/A.Km
0.825
0.613
0.47
0.346
0.268
0.225
0.194
0.167
0.142
0.124
Laying condition: Maximum conductor temperature 90C, Ambient temperature 30C. Underground temperature of soil 20C, Depth of laying - 0.8m.
Ground thermal resistivity 1.5 K.m/W, thermal resisitivity of earthenware ducts 1.2 K.m/W.
Note: Area of copper wire considered is 16 mm2 up to 120 mm2, 25 mm2 from 150 mm2 up to 300 mm2, 35 mm2 from 400 mm2 up to 630 mm2.
28
IEC 60502-2
1.
2.
3.
4.
5.
Size
mm
50
70
95
120
150
185
240
300
Conductor
Conductor Screen
XLPE Insulation
Insulation Screen (Non-metallic)
Insulation Screen (Metallic)
Diameter of
Conductor
(Approx.)
Nominal
Insulation
Thickness
Diameter
Over
Insulation
(Approx.)
mm
8.1
9.7
11.4
12.9
14.3
16.0
18.4
20.4
mm
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
mm
25.7
27.3
29.0
30.5
31.9
33.6
36.0
38.0
Size
Max DC
Resistance
@ 20C
Nominal
Inductance
mm
Ohm/km
mH/km
50
0.387
0.449
70
0.268
0.430
Uo/U (Um)=18/30(36) kV
765 4 3 2 1
6. PP Filler
7. Bedding
8. Steel Wire Armour
9. Outer Sheath
Nominal
Diameter of steel
Wire
Nominal Outer
Sheath Thickness
Overall Diameter
(Approx.)
Weight of Cable
(Approx)
CUT/CUW
CUT
CUW
CUT
CUW
CUT
CUW
mm
3.15
3.15
3.15
3.15
3.15
3.15
3.15
3.15
mm
3.4
3.5
3.6
3.7
3.8
4.0
4.1
4.3
mm
3.4
3.5
3.7
3.8
3.9
4.0
4.2
4.4
mm
78
82
86
90
93
97
103
108
mm
81
85
89
93
96
100
106
111
Kg/km
9400
10475
11775
13000
14250
15975
18375
20925
Kg/km
9725
10850
12150
13375
14750
16325
18850
21300
Current ratings
Conductor
Short Circuit
Current
for 1 second
Buried Direct
In the ground
In buried ducts
In air
Voltage drop
Per phase
F/km
kA
Amps
Amps
Amps
V/A.Km
0.14
7.150
181
158
205
0.480
0.16
10.010
220
194
253
0.355
Capacitance
95
0.193
0.419
0.17
13.585
263
232
307
0.277
120
0.153
0.405
0.18
17.160
298
264
352
0.233
150
0.124
0.395
0.19
21.450
332
296
397
0.202
185
0.0991
0.384
0.21
26.455
374
335
453
0.175
240
0.0754
0.371
0.23
34.320
431
387
529
0.149
300
0.0601
0.358
0.25
42.900
482
435
599
0.131
Laying condition: Maximum conductor temperature 90C, Ambient temperature 30C. Underground temperature of soil 20C, Depth of laying - 0.8m.
Ground thermal resistivity 1.5 K.m/W, thermal resisitivity of earthenware ducts 1.2 K.m/W.
Note: Area of copper wire considered is 16 mm2 up to 120 mm2, 25 mm2 from 150 mm2 up to 300 mm2, 35 mm2 from 400 mm2 up to 630 mm2.
29
IEC 60502-2
1.
2.
3.
4.
5.
Conductor
Conductor Screen
XLPE Insulation
Insulation Screen (Non-Metallic)
Insulation Screen (Metallic)
Diameter of
Conductor
(Approx.)
Nominal
Insulation
Thickness
Diameter
Over Insulation
(Approx.)
mm
25
35
50
70
95
120
150
185
240
300
mm
5.9
6.9
8.1
9.7
11.4
12.9
14.3
16.0
18.4
20.4
mm
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.6
2.8
mm
12.5
13.5
14.7
16.3
18.0
19.5
20.9
22.6
25.2
27.6
Size
Max DC
Resistance
@ 20C
Nominal
Inductance
mm
25
35
50
70
95
120
150
185
240
300
Ohm/km
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
mH/km
0.363
0.344
0.333
0.322
0.316
0.309
0.303
0.300
0.293
0.286
Size
Capacitance
F/km
0.26
0.29
0.32
0.36
0.39
0.43
0.47
0.52
0.56
0.58
8 76 5 4
Uo/U (Um)=3.5/6(7.2) kV
3 2 1
6. PP Filler
7. Bedding
8. Steel Tape Armour
9. Outer Sheath
Number &
Nominal
Thickness of
steel Tape
Nominal
Outer Sheath
Thickness
Overall Diameter
(Approx.)
CUT
CUW
CUT
CUW
CUT
CUW
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
mm
2.2
2.3
2.4
2.5
2.6
2.7
2.8
2.9
3.1
3.3
mm
2.2
2.3
2.4
2.5
2.6
2.8
2.9
3.0
3.2
3.4
mm
41
43
46
50
54
58
61
65
71
77
mm
44
46
49
53
57
61
64
68
74
80
Kg/km
2500
2900
3450
4275
5250
6175
7150
8475
10550
12875
Kg/km
2700
3150
3650
4500
5500
6400
7500
8775
10900
13175
Conductor
Short Circuit
Current
for 1 second
kA
3.575
5.005
7.150
10.010
13.585
17.160
21.450
26.455
34.320
42.900
Weight of Cable
(Approx)
Current ratings
Buried Direct
In the ground
In buried ducts
In air
Voltage drop
Per phase
Amps
129
154
181
220
263
298
332
374
431
482
Amps
112
134
158
194
232
264
296
335
387
435
Amps
143
172
205
253
307
352
397
453
529
599
V/A.Km
0.810
0.600
0.458
0.334
0.257
0.215
0.185
0.159
0.124
0.118
Laying condition: Maximum conductor temperature 90C, Ambient temperature 30C. Underground temperature of soil 20C, Depth of laying - 0.8m.
Ground thermal resistivity 1.5 K.m/W, thermal resisitivity of earthenware ducts 1.2 K.m/W.
Note: Area of copper wire considered is 16 mm2 up to 120 mm2, 25 mm2 from 150 mm2 up to 300 mm2, 35 mm2 from 400 mm2 up to 630 mm2.
30
IEC 60502-2
1.
2.
3.
4.
5.
Size
mm
25
35
50
70
95
120
150
185
240
300
Conductor
Conductor Screen
XLPE Insulation
Insulation Screen (Non-Metallic)
Insulation Screen (Metallic)
Nominal
Insulation
Thickness
Diameter
Over
Insulation
(Approx.)
Number &
Nominal
Thickness of
steel Tape
mm
5.9
6.9
8.1
9.7
11.4
12.9
14.3
16.0
18.4
20.4
mm
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
mm
14.3
15.3
16.5
18.1
19.8
21.3
22.7
24.4
26.8
28.8
mm
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
Size
Nominal
Inductance
mm
25
35
50
70
95
120
150
185
240
300
Ohm/km
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
mH/km
0.387
0.368
0.355
0.342
0.355
0.326
0.319
0.313
0.303
0.297
Capacitance
F/km
0.21
0.23
0.25
0.29
0.31
0.34
0.37
0.40
0.44
0.48
8 76 5 4
3 2 1
6. PP Filler
7. Bedding
8. Steel Tape Armour
9. Outer Sheath
Diameter of
Conductor
(Approx.)
Max DC
Resistance
@ 20C
Uo/U (Um)=6/10(12) kV
Conductor
Short Circuit
Current
for 1 second
kA
3.575
5.005
7.150
10.010
13.585
17.160
21.450
26.455
34.320
42.900
Nominal Outer
Sheath Thickness
Overall Diameter
(Approx.)
Weight of Cable
(Approx)
CUT
CUW
CUT
CUW
CUT
CUW
mm
2.3
2.4
2.5
2.6
2.7
2.9
3.0
3.1
3.3
3.4
mm
2.4
2.5
2.6
2.7
2.8
2.9
3.0
3.1
3.3
3.5
mm
45
48
50
54
58
62
65
69
76
80
mm
48
51
54
58
61
65
68
72
78
83
Kg/km
2825
3275
3825
4650
5675
6650
7650
9000
11200
13300
Kg/km
3100
3525
4050
4950
5900
6850
7975
9300
11450
13575
Current ratings
Buried Direct
In the ground
Amps
129
154
181
220
263
298
332
374
431
482
In buried ducts
In air
Amps
112
134
158
194
232
264
296
335
387
435
Amps
143
172
205
253
307
352
397
453
529
599
Voltage drop
Per phase
V/A.Km
0.815
0.604
0.462
0.338
0.265
0.218
0.188
0.161
0.137
0.120
Laying condition: Maximum conductor temperature 90C, Ambient temperature 30C. Underground temperature of soil 20C, Depth of laying - 0.8m.
Ground thermal resistivity 1.5 K.m/W, thermal resisitivity of earthenware ducts 1.2 K.m/W.
Note: Area of copper wire considered is 16 mm2 up to 120 mm2, 25 mm2 from 150 mm2 up to 300 mm2, 35 mm2 from 400 mm2 up to 630 mm2.
31
IEC 60502-2
1.
2.
3.
4.
Size
mm
25
35
50
70
95
120
150
185
240
300
Conductor
Conductor Screen
XLPE Insulation
Insulation Screen (Non-Metallic)
Nominal
Insulation
Thickness
Diameter
Over
Insulation
(Approx.)
Number &
Nominal
Thickness of
steel Tape
mm
5.9
6.9
8.1
9.7
11.4
12.9
14.3
16.0
18.4
20.4
mm
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
mm
16.5
17.5
18.7
20.3
22.0
23.5
24.9
26.6
29.0
31.0
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.8
Size
Nominal
Inductance
mm
25
35
50
70
95
120
150
185
240
300
Ohm/km
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
mH/km
0.413
0.394
0.379
0.364
0.356
0.346
0.338
0.330
0.321
0.312
Capacitance
F/km
0.17
0.19
0.21
0.23
0.25
0.27
0.29
0.32
0.35
0.39
8 76 5 4
3 2 1
6. PP Filler
7. Bedding
8. Steel Tape Armour
9. Outer Sheath
Diameter of
Conductor
(Approx.)
Max DC
Resistance
@ 20C
Uo/U (Um)=8.7/15(17.5) kV
Conductor
Short Circuit
Current
for 1 second
kA
3.575
5.005
7.150
10.010
13.585
17.160
21.450
26.455
34.320
42.900
Nominal Outer
Sheath Thickness
Overall Diameter
(Approx.)
Weight of Cable
(Approx)
CUT
CUW
CUT
CUW
CUT
CUW
mm
2.5
2.6
2.7
2.8
2.9
3.0
3.1
3.3
3.4
3.6
mm
2.5
2.6
2.7
2.8
3.0
3.1
3.2
3.3
3.5
3.7
mm
50
53
56
60
64
67
70
75
81
87
mm
53
56
59
63
67
70
74
78
84
90
Kg/km
3300
3750
4325
5200
6250
725
8250
9800
11900
14800
Kg/km
3500
4000
4525
5425
6550
7500
8650
1050
12100
15150
Current ratings
Buried Direct
In the ground
Amps
129
154
181
220
263
298
332
374
431
482
In buried ducts
In air
Voltage drop
Per phase
Amps
112
134
158
194
232
264
296
335
387
435
Amps
143
172
205
253
307
352
397
453
529
599
V/A.Km
0.820
0.609
0.46
0.342
0.265
0.222
0.191
0.165
0.140
0.123
Laying condition: Maximum conductor temperature 90C, Ambient temperature 30C. Underground temperature of soil 20C, Depth of laying - 0.8m.
Ground thermal resistivity 1.5 K.m/W, thermal resisitivity of earthenware ducts 1.2 K.m/W.
Note: Area of copper wire considered is 16 mm2 up to 120 mm2, 25 mm2 from 150 mm2 up to 300 mm2, 35 mm2 from 400 mm2 up to 630 mm2.
32
IEC 60502-2
1.
2.
3.
4.
5.
Size
mm
25
35
50
70
95
120
150
185
240
300
Conductor
Conductor Screen
XLPE Insulation
Insulation Screen (Non-Metallic)
Insulation Screen (Metallic)
Nominal
Insulation
Thickness
Diameter
Over
Insulation
(Approx.)
Number &
Nominal
Thickness of
steelTape
mm
5.9
6.9
8.1
9.7
11.4
12.9
14.3
16.0
18.4
20.4
mm
6.0
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
mm
19.5
19.5
20.7
22.3
24.0
25.5
26.9
28.6
31.0
33.0
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.8
Size
Nominal
Inductance
mm
25
35
50
70
95
120
150
185
240
300
Ohm/km
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
mH/km
0.444
0.415
0.399
0.382
0.373
0.362
0.353
0.345
0.335
0.320
Capacitance
F/km
0.14
0.16
0.18
0.20
0.21
0.23
0.25
0.27
0.30
0.33
8 76 5 4
3 2 1
6. PP Filler
7. Bedding
8. Steel Tape Armour
9. Outer Sheath
Diameter of
Conductor
(Approx.)
Max DC
Resistance
@ 20C
Uo/U (Um)=12/20(24) kV
Conductor
Short Circuit
Current
for 1 second
kA
3.575
5.005
7.150
10.010
13.585
17.160
21.450
26.455
34.320
42.900
Nominal Outer
Sheath Thickness
Overall Diameter
(Approx.)
Weight of Cable
(Approx)
CUT
CUW
CUT
CUW
CUT
CUW
mm
2.7
2.7
2.8
3
3.1
3.2
3.3
3.4
3.6
3.8
mm
2.8
2.8
2.9
3.0
3.1
3.2
3.4
3.5
3.7
3.9
mm
58
58
61
64
69
66
76
80
87
92
mm
61
61
64
67
72
75
79
83
90
95
Kg/km
4000
4225
4825
5800
6825
7900
9000
10400
13400
15600
Kg/km
4225
4500
5050
5925
7000
8100
9300
10700
13700
15900
Current ratings
Buried Direct
In the ground
Amps
129
154
181
220
263
298
332
374
431
482
In buried ducts
In air
Amps
112
134
158
194
232
264
296
335
387
435
Amps
143
172
205
253
307
352
397
453
529
599
Voltage drop
Per phase
V/A.Km
0.825
0.613
0.47
0.346
0.268
0.225
0.194
0.167
0.142
0.124
Laying condition: Maximum conductor temperature 90C, Ambient temperature 30C. Underground temperature of soil 20C, Depth of laying - 0.8m.
Ground thermal resistivity 1.5 K.m/W, thermal resisitivity of earthenware ducts 1.2 K.m/W.
Note: Area of copper wire considered is 16 mm2 up to 120 mm2, 25 mm2 from 150 mm2 up to 300 mm2, 35 mm2 from 400 mm2 up to 630 mm2.
33
IEC 60502-2
1.
2.
3.
4.
5.
Conductor
Conductor Screen
XLPE Insulation
Insulation Screen (Non-Metallic)
Insulation Screen (Metallic)
Diameter
Over
Insulation
(Approx.)
8 76 5 4
3 2 1
6. PP Filler
7. Bedding
8. Steel Tape Armour
9. Outer Sheath
Number &
Nominal
Thickness of
steel Tape
Diameter of
Conductor
(Approx.)
Nominal
Insulation
Thickness
mm
mm
mm
mm
50
8.1
8.0
25.7
2x0.5
70
9.7
8.0
27.3
Size
Uo/U (Um)=18/30(36) kV
Nominal Outer
Sheath Thickness
Overall Diameter
(Approx.)
Weight of Cable
(Approx)
CUT
CUW
CUT
CUW
CUT
CUW
mm
mm
mm
mm
Kg/km
Kg/km
3.2
3.3
73
76
6300
6500
2x0.5
3.3
3.4
77
80
7300
7550
95
11.4
8.0
29.0
2x0.5
3.5
3.5
81
84
8500
8650
120
12.9
8.0
30.5
2x0.5
3.6
3.7
86
89
10325
10600
150
14.3
8.0
31.9
2x0.5
3.7
3.8
89
92
11450
11850
185
16.0
8.0
33.6
2x0.8
3.9
3.9
93
96
13050
13325
240
18.4
8.0
36.0
2x0.8
4.0
4.1
99
102
15300
15600
300
20.4
8.0
38.0
2x0.8
4.2
4.2
104
106
17650
17900
Size
Max DC
Resistance
@ 20C
Nominal
Inductance
mm
Ohm/km
mH/km
F/km
50
0.387
0.449
70
0.268
0.430
95
0.193
120
150
Conductor
Short Circuit
Current
for 1 second
Current ratings
Buried Direct
In the ground
In buried ducts
In air
Voltage drop
Per phase
kA
Amps
Amps
Amps
V/A.Km
0.14
7.150
181
158
205
0.480
0.16
10.010
220
194
253
0.355
0.419
0.17
13.585
263
232
307
0.277
0.153
0.405
0.18
17.160
298
264
352
0.233
0.124
0.395
0.19
21.450
332
296
397
0.202
185
0.0991
0.384
0.21
26.455
374
335
453
0.175
240
0.0754
0.371
0.23
34.320
431
387
529
0.149
300
0.0601
0.358
0.25
42.900
482
435
599
0.131
Capacitance
Laying condition: Maximum conductor temperature 90C, Ambient temperature 30C. Underground temperature of soil 20C, Depth of laying - 0.8m.
Ground thermal resistivity 1.5 K.m/W, thermal resisitivity of earthenware ducts 1.2 K.m/W.
Note: Area of copper wire considered is 16 mm2 up to 120 mm2, 25 mm2 from 150 mm2 up to 300 mm2, 35 mm2 from 400 mm2 up to 630 mm2.
34
IEC 60502-2
1. Conductor
2. Conductor Screen
3. XLPE Insulation
Size
mm
25
35
50
70
95
120
150
185
240
300
400
500
630
Uo/U (Um)=3.5/6(7.2)kV
3 2
Diameter of
Conductor
(Approx.)
Nominal
Insulation
Thickness
Diameter
Over
Insulation
(Approx.)
mm
6.0
7.1
8.3
9.7
11.55
12.95
14.3
15.9
18.4
20.5
24.0
27.0
30.4
mm
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.6
2.8
3.0
3.2
3.2
mm
12.6
13.7
14.9
16.3
18.15
19.55
20.9
22.5
25.2
27.7
31.6
35.0
38.4
Overall Diameter
(Approx.)
Weight of Cable
(Approx)
CUT
CUW
CUT
CUW
CUT
CUW
mm
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.9
2.0
2.1
2.2
2.3
mm
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.9
1.9
2.0
2.2
2.3
2.4
mm
18
19
21
22
24
26
27
29
31
34
38
42
46
mm
20
21
22
24
26
27
29
30
33
36
40
44
48
Kg/km
375
425
500
600
700
800
925
1050
1300
1550
1925
2350
2900
Kg/km
550
550
675
750
850
925
1125
1275
1500
1750
2250
2675
3200
Flat
Touching
ducts
Trefoil
Flat
Touching
Flat
Spaced
kA
2.360
3.304
4.720
6.608
8.968
11.328
14.160
17.464
22.656
28.320
37.760
47.200
59.472
Trefoil
ducts
0.26
0.29
0.31
0.37
0.39
0.44
0.48
0.52
0.56
0.58
0.61
0.64
0.71
Flat
Spaced
F/km
0.760
0.745
0.726
0.694
0.679
0.660
0.645
0.630
0.611
0.596
0.573
0.564
0.548
In air
Amps
108
129
152
186
221
252
281
317
367
414
470
528
599
Amps
112
134
157
192
229
260
288
324
373
419
466
519
582
Amps
102
122
144
176
210
240
267
303
351
397
451
512
583
Amps
103
123
146
178
213
242
271
307
356
402
457
518
590
Amps
127
154
184
230
280
324
368
424
502
577
673
770
896
Amps
130
157
189
236
287
332
376
432
511
586
676
767
885
Amps
153
185
222
278
338
391
440
504
593
677
769
857
980
Buried
Direct
In
the
ground
mH/km
Flat
Trefoil
mH/km
0.444
0.426
0.412
0.388
0.378
0.364
0.354
0.343
0.332
0.324
0.313
0.306
0.296
In single -way
ducts
Trefoil
Ohm/km
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
Conductor
Short Circuit
Current
for 1 second
25
35
50
70
95
120
150
185
240
300
400
500
630
Inductance
Capacitance
mm
Max DC
Resistance
@ 20C
SIZE
Current ratings
V/A.Km
1.314
0.971
0.735
0.528
0.400
0.328
0.279
0.234
0.192
0.165
0.141
0.122
0.107
Laying condition: Maximum conductor temperature 90C, Ambient temperature 30C. Underground temperature of soil 20C, Depth of laying - 0.8m.
Ground thermal resistivity 1.5 K.m/W, thermal resisitivity of earthenware ducts 1.2 K.m/W.
Note: Area of copper wire considered is 16 mm2 up to 120 mm2, 25 mm2 from 150 mm2 up to 300 mm2, 35 mm2 from 400 mm2 up to 630 mm2.
35
IEC 60502-2
1. Conductor
2. Conductor Screen
3. XLPE Insulation
Size
mm
25
35
50
70
95
120
150
185
240
300
400
500
630
Uo/U (Um)=6/10(12)kV
3 2
Diameter of
Conductor
(Approx.)
Nominal
Insulation
Thickness
Diameter
Over
Insulation
(Approx.)
mm
6.0
7.1
8.3
9.7
11.55
12.95
14.3
15.9
18.4
20.5
24.0
27.0
30.4
mm
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
mm
14.4
15.5
16.7
18.1
19.95
21.35
22.7
24.3
26.8
28.9
32.4
35.4
38.8
Overall Diameter
(Approx.)
Weight of Cable
(Approx)
CUT
CUW
CUT
CUW
CUT
CUW
mm
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.9
2.0
2.0
2.1
2.2
2.3
mm
1.8
1.8
1.8
1.8
1.8
1.8
1.9
1.9
2.0
2.1
2.2
2.3
2.4
mm
20
21
23
24
26
28
29
31
33
35
39
42
46
mm
22
23
24
26
28
29
31
32
35
37
41
44
48
Kg/km
450
500
575
675
800
900
1000
1150
1400
1625
1975
2375
2875
Kg/km
625
650
700
800
900
1000
1200
1350
1600
1850
2300
2700
3250
Flat
Touching
Flat
Spaced
Amps
108
129
152
186
221
252
281
317
367
414
470
528
599
Amps
112
134
157
192
229
260
288
324
373
419
466
519
582
Amps
102
122
144
176
210
240
267
303
351
397
451
512
583
Amps
103
123
146
178
213
242
271
307
356
402
457
518
590
Amps
127
154
184
230
280
324
368
424
502
577
673
770
896
Amps
130
157
189
236
287
332
376
432
511
586
676
767
885
Amps
153
185
222
278
338
391
440
504
593
677
769
857
980
Trefoil
kA
2.360
0.304
4.720
6.608
8.968
11.328
14.160
17.464
22.656
28.320
37.760
47.200
59.472
Flat
Touching
ducts
0.21
0.23
0.25
0.29
0.31
0.34
0.37
0.40
0.45
0.49
0.55
0.60
0.68
Trefoil
ducts
F/km
0.770
0.751
0.731
0.700
0.681
0.666
0.650
0.635
0.615
0.599
0.580
0.565
0.549
In air
Flat
Spaced
Buried
Direct
In
the
ground
mH/km
Flat
Trefoil
mH/km
0.460
0.440
0.424
0.401
0.383
0.376
0.364
0.354
0.341
0.329
0.318
0.308
0.299
In single -way
ducts
Trefoil
Ohm/km
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
Conductor
Short Circuit
Current
for 1 second
25
35
50
70
95
120
150
185
240
300
400
500
630
Inductance
Capacitance
mm
Max DC
Resistance
@ 20C
SIZE
Current ratings
V/A.Km
1.318
0.973
0.737
0.530
0.401
0.331
0.280
0.236
0.194
0.166
0.142
0.123
0.108
Laying condition: Maximum conductor temperature 90C, Ambient temperature 30C. Underground temperature of soil 20C, Depth of laying - 0.8m.
Ground thermal resistivity 1.5 K.m/W, thermal resisitivity of earthenware ducts 1.2 K.m/W.
Note: Area of copper wire considered is 16 mm2 up to 120 mm2, 25 mm2 from 150 mm2 up to 300 mm2, 35 mm2 from 400 mm2 up to 630 mm2.
36
1. Conductor
2. Conductor Screen
3. XLPE Insulation
mm
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
mm
16.6
17.7
18.9
20.3
22.15
23.55
24.9
26.5
29.0
31.1
34.6
37.6
41.0
Weight of Cable
(Approx)
CUT
CUW
CUT
CUW
CUT
CUW
mm
1.8
1.8
1.8
1.8
1.8
1.9
1.9
2.0
2.0
2.1
2.2
2.3
2.4
mm
1.8
1.8
1.8
1.8
1.8
1.9
1.9
2.0
2.1
2.1
2.3
2.4
2.5
mm
22
24
25
27
28
30
31
33
36
38
42
45
49
mm
24
25
26
28
30
31
33
34
37
39
43
47
51
Kg/km
525
600
675
775
900
1025
1150
1300
1550
1775
2150
2550
3125
Kg/km
650
725
800
875
1000
1125
1325
1500
1750
1975
2450
2850
3450
Flat
Spaced
In air
kA
2.360
0.304
4.720
6.608
8.968
11.328
14.160
17.464
22.656
28.320
37.760
47.200
59.472
Amps
108
129
152
186
221
252
281
317
367
414
470
528
599
Amps
112
134
157
192
229
260
288
324
373
419
466
519
582
Amps
102
122
144
176
210
240
267
303
351
397
451
512
583
Amps
103
123
146
178
213
242
271
307
356
402
457
518
590
Amps
127
154
184
230
280
324
368
424
502
577
673
770
896
Amps
130
157
189
236
287
332
376
432
511
586
676
767
885
Amps
153
185
222
278
338
391
440
504
593
677
769
857
980
In single -way
ducts
Flat
Touching
Buried
Direct
In
the
ground
Current ratings
Trefoil
0.17
0.19
0.20
0.23
0.25
0.27
0.29
0.32
0.35
0.39
0.43
0.48
0.53
Overall Diameter
(Approx.)
Flat
Touching
ducts
F/km
0.780
0.758
0.738
0.706
0.690
0.672
0.656
0.641
0.621
0.605
0.585
0.570
0.554
Trefoil
ducts
Flat
mH/km
Flat
Spaced
mH/km
0.470
0.456
0.440
0.415
0.402
0.389
0.377
0.366
0.352
0.340
0.327
0.318
0.307
Capacitance
mm
6.0
7.1
8.3
9.7
11.55
12.95
14.3
15.9
18.4
20.5
24.0
27.0
30.4
Ohm/km
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
3 2
Trefoil
25
35
50
70
95
120
150
185
240
300
400
500
630
Diameter
Over
Insulation
(Approx.)
Inductance
Conductor
Short Circuit
Current
for 1 second
mm
Nominal
Insulation
Thickness
Trefoil
SIZE
mm
25
35
50
70
95
120
150
185
240
300
400
500
630
Uo/U (Um)=8.7/15(17.5)kV
Diameter of
Conductor
(Approx.)
Max DC
Resistance
@ 20C
Size
IEC 60502-2
V/A.Km
1.320
0.976
0.74
0.533
0.404
0.333
0.283
0.238
0.196
0.168
0.144
0.125
0.109
Laying condition: Maximum conductor temperature 90C, Ambient temperature 30C. Underground temperature of soil 20C, Depth of laying - 0.8m.
Ground thermal resistivity 1.5 K.m/W, thermal resisitivity of earthenware ducts 1.2 K.m/W.
Note: Area of copper wire considered is 16 mm2 up to 120 mm2, 25 mm2 from 150 mm2 up to 300 mm2, 35 mm2 from 400 mm2 up to 630 mm2.
37
IEC 60502-2
1. Conductor
2. Conductor Screen
3. XLPE Insulation
Size
mm
25
35
50
70
95
120
150
185
240
300
400
500
630
Uo/U (Um)=12/20(24)kV
3 2
Diameter of
Conductor
(Approx.)
Nominal
Insulation
Thickness
Diameter
Over
Insulation
(Approx.)
mm
6.0
7.1
8.3
9.7
11.55
12.95
14.3
15.9
18.4
20.5
24.0
27.0
30.4
mm
6.0
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
mm
19.6
19.7
20.9
22.3
24.15
25.55
26.9
28.6
31.0
33.1
36.6
39.6
43.0
Overall Diameter
(Approx.)
Weight of Cable
(Approx)
CUT
CUW
CUT
CUW
CUT
CUW
mm
1.8
1.8
1.8
1.8
1.9
1.9
2.0
2.0
2.1
2.2
2.3
2.4
2.5
mm
1.8
1.8
1.8
1.9
1.9
2.0
2.0
2.1
2.1
2.2
2.3
2.4
2.5
mm
26
26
27
29
31
32
34
35
38
40
44
47
51
mm
27
27
29
30
32
34
35
37
39
42
46
49
53
Kg/km
675
700
775
875
1025
1125
1250
1425
1675
1925
2300
2800
3325
Kg/km
775
800
875
1000
1125
1250
1450
1625
1875
2125
2600
3050
3600
Trefoil
Flat
Touching
Flat
Spaced
kA
2.360
0.304
4.720
6.608
8.968
11.328
14.160
17.464
22.656
28.320
37.760
47.200
59.472
Flat
Touching
ducts
0.14
0.16
0.18
0.20
0.21
0.23
0.25
0.27
0.30
0.33
0.37
0.40
0.45
Trefoil
ducts
F/km
0.792
0.763
0.744
0.712
0.696
0.677
0.662
0.646
0.626
0.610
0.590
0.575
0.558
In air
Flat
Spaced
Buried
Direct
In
the
ground
mH/km
Flat
Trefoil
mH/km
0.497
0.468
0.453
0.426
0.414
0.399
0.388
0.375
0.361
0.350
0.336
0.326
0.315
In single -way
ducts
Trefoil
Ohm/km
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
Conductor
Short Circuit
Current
for 1 second
25
35
50
70
95
120
150
185
240
300
400
500
630
Inductance
Capacitance
mm
Max DC
Resistance
@ 20C
SIZE
Current ratings
Amps
108
129
152
186
221
252
281
317
367
414
470
528
599
Amps
112
134
157
192
229
260
288
324
373
419
466
519
582
Amps
102
122
144
176
210
240
267
303
351
397
451
512
583
Amps
103
123
146
178
213
242
271
307
356
402
457
518
590
Amps
127
154
184
230
280
324
368
424
502
577
673
770
896
Amps
130
157
189
236
287
332
376
432
511
586
676
767
885
Amps
153
185
222
278
338
391
440
504
593
677
769
857
980
V/A.Km
1.324
0.976
0.743
0.535
0.407
0.335
0.285
0.24
0.197
0.17
0.146
0.126
0.111
Laying condition: Maximum conductor temperature 90C, Ambient temperature 30C. Underground temperature of soil 20C, Depth of laying - 0.8m.
Ground thermal resistivity 1.5 K.m/W, thermal resisitivity of earthenware ducts 1.2 K.m/W.
Note: Area of copper wire considered is 16 mm2 up to 120 mm2, 25 mm2 from 150 mm2 up to 300 mm2, 35 mm2 from 400 mm2 up to 630 mm2.
38
1. Conductor
2. Conductor Screen
3. XLPE Insulation
Size
mm
50
70
95
120
150
185
240
300
400
500
630
Diameter of
Conductor
(Approx.)
Nominal
Insulation
Thickness
Diameter
Over
Insulation
(Approx.)
mm
8.3
9.7
11.55
12.95
14.3
15.9
18.4
20.5
24.0
27.0
30.4
mm
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
mm
25.9
27.3
29.15
30.55
31.9
33.5
36.0
38.1
41.6
44.6
48.0
IEC 60502-2
Uo/U (Um)=18/30(36)kV
3 2
Overall Diameter
(Approx.)
Weight of Cable
(Approx)
CUT
CUW
CUT
CUW
CUT
CUW
mm
1.9
2.0
2
2.1
2.1
2.2
2.3
2.3
2.5
2.5
2.7
mm
2.0
2.0
2.1
2.1
2.2
2.2
2.3
2.4
2.5
2.6
2.7
mm
32
34
36
38
39
41
43
46
50
53
56
mm
34
35
38
39
40
42
45
47
51
54
58
Kg/km
1025
1150
1325
1450
1575
1750
2050
2300
2775
3200
3800
Kg/km
1150
1275
1450
1550
1800
1950
2225
2500
3050
3500
4050
In single -way
ducts
Max DC
Resistance
@ 20C
Trefoil
Flat
Capacitance
Conductor
Short Circuit
Current
for 1 second
Trefoil
Flat
Spaced
Trefoil
ducts
Flat
Touching
ducts
Trefoil
Flat
Touching
Flat
Spaced
In air
SIZE
Inductance
Buried
Direct
In
the
ground
Current ratings
mm
Ohm/km
mH/km
mH/km
F/km
kA
Amps
Amps
Amps
Amps
Amps
Amps
Amps
V/A.Km
50
0.641
0.487
0.761
0.14
4.720
152
157
144
146
184
189
222
0.749
70
0.443
0.459
0.728
0.16
6.608
186
192
176
178
230
236
278
0.541
95
0.320
0.446
0.712
0.17
8.968
221
229
210
213
280
287
338
0.413
120
0.253
0.430
0.693
0.18
11.328
252
260
240
242
324
332
391
0.341
150
0.206
0.417
0.677
0.19
14.160
281
288
267
271
368
376
440
0.291
185
0.164
0.404
0.661
0.21
17.464
317
324
303
307
424
432
504
0.245
240
0.125
0.388
0.641
0.23
22.656
367
373
351
356
502
511
593
0.203
300
0.100
0.375
0.624
0.25
28.320
414
419
397
402
577
586
677
0.175
400
0.0778
0.360
0.604
0.27
37.760
470
466
451
457
673
676
769
0.15
500
0.0605
0.349
0.589
0.30
47.200
528
519
512
518
770
767
857
0.131
630
0.0469
0.336
0.571
0.33
59.472
599
582
583
590
896
885
980
0.115
Laying condition: Maximum conductor temperature 90C, Ambient temperature 30C. Underground temperature of soil 20C, Depth of laying - 0.8m.
Ground thermal resistivity 1.5 K.m/W, thermal resisitivity of earthenware ducts 1.2 K.m/W.
Note: Area of copper wire considered is 16 mm2 up to 120 mm2, 25 mm2 from 150 mm2 up to 300 mm2, 35 mm2 from 400 mm2 up to 630 mm2.
39
IEC 60502-2
1.
2.
3.
4.
Conductor
Conductor Screen
XLPE Insulation
Insulation Screen (Non-metallic)
Size
Diameter of
Conductor
(Approx.)
Nominal
Insulation
Thickness
Diameter
Over
Insulation
(Approx.)
mm
25
35
50
70
95
120
150
185
240
300
400
500
630
mm
6.0
7.1
8.3
9.7
11.55
12.95
14.3
15.9
18.4
20.5
24.0
27.0
30.4
mm
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.6
2.8
3.0
3.2
3.2
mm
12.6
13.7
14.9
16.3
18.15
19.55
20.9
22.5
25.2
27.7
31.6
35.0
38.4
Uo/U (Um)=3.5/6(7.2)kV
7 6 5 4 3 2 1
Nominal
Diameter of
Aluminium
Wire
Nominal
Outer Sheath
Thickness
CUT/CUW
CUT
CUW
CUT
CUW
CUT
CUW
mm
1.6
1.6
1.6
1.6
1.6
1.6
2.0
2.0
2.0
2.0
2/2.5
2.5
2.5
mm
1.8
1.8
1.8
1.8
1.9
1.9
2.0
2.0
2.1
2.2
2.3
2.5
2.6
mm
1.8
1.8
1.8
1.8
1.9
1.9
2.0
2.1
2.2
2.2
2.4
2.5
2.6
mm
24
25
27
28
30
31
33
35
38
41
46
50
54
mm
26
27
28
29
31
33
35
37
40
42
48
52
56
Kg/km
750
825
900
975
1175
1300
1400
1650
2000
2325
2725
3475
4100
Kg/km
950
1025
1100
1225
1350
1500
1775
2000
2325
2625
3400
3900
4550
Overall Diameter
(Approx.)
Weight of Cable
(Approx)
Trefoil
Flat
Touching
Flat
Spaced
Amps
107
127
150
182
217
246
274
309
355
397
448
494
549
Amps
111
131
154
187
221
249
274
305
344
378
416
446
484
Amps
101
121
142
174
207
235
262
297
342
383
434
482
537
Amps
103
123
145
177
210
239
265
298
342
382
430
470
521
Amps
126
152
182
226
275
317
360
413
485
552
638
724
824
Amps
128
155
185
230
279
321
361
411
478
539
613
677
755
Amps
147
178
212
263
317
363
405
457
526
587
656
718
792
Flat
Touching
ducts
kA
2.360
3.304
4.720
6.608
8.968
11.328
14.160
17.464
22.656
28.320
37.760
47.200
59.472
Trefoil
ducts
0.26
0.29
0.31
0.37
0.39
0.44
0.48
0.52
0.56
0.58
0.61
0.64
0.71
In air
Flat
Spaced
F/km
0.785
0.760
0.735
0.708
0.692
0.637
0.658
0.642
0.623
0.608
0.589
0.576
0.558
Buried
Direct
In
the
ground
mH/km
In single -way
ducts
Trefoil
Trefoil
mH/km
0.473
0.461
0.444
0.418
0.406
0.392
0.380
0.369
0.356
0.346
0.334
0.327
0.315
Conductor
Short Circuit
Current
for 1 second
Ohm/km
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
Capacitance
25
35
50
70
95
120
150
185
240
300
400
500
630
Inductance
Flat
mm
Max DC
Resistance
@ 20C
Size
Current ratings
V/A.Km
1.323
0.979
0.743
0.535
0.407
0.336
0.286
0.241
0.198
0.17
0.146
0.127
0.112
Laying condition: Maximum conductor temperature 90C, Ambient temperature 30C. Underground temperature of soil 20C, Depth of laying - 0.8m.
Ground thermal resistivity 1.5 K.m/W, thermal resisitivity of earthenware ducts 1.2 K.m/W.
Note: Area of copper wire considered is 16 mm2 up to 120 mm2, 25 mm2 from 150 mm2 up to 300 mm2, 35 mm2 from 400 mm2 up to 630 mm2.
40
IEC 60502-2
1.
2.
3.
4.
Size
mm
25
35
50
70
95
120
150
185
240
300
400
500
630
Conductor
Conductor Screen
XLPE Insulation
Insulation Screen (Non-metallic)
Diameter of
Conductor
(Approx.)
Nominal
Insulation
Thickness
Diameter
Over
Insulation
(Approx.)
mm
6.0
7.1
8.3
9.7
11.55
12.95
14.3
15.9
18.4
20.5
24.0
27.0
30.4
mm
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
mm
14.4
15.5
16.7
18.1
19.95
21.35
22.7
24.3
26.8
28.9
32.4
35.4
38.8
7 6 5 4 3 2 1
Nominal
Outer Sheath
Thickness
CUT/CUW
CUT
CUW
CUT
CUW
CUT
CUW
mm
1.6
1.6
1.6
1.6
1.6
1.6/2
2.0
2.0
2.0
2.0
2/2.5
2.5
2.5
mm
1.8
1.8
1.8
1.9
1.9
2.0
2.1
2.1
2.2
2.2
2.4
2.5
2.6
mm
1.8
1.8
1.9
1.9
2.0
2.0
2.1
2.1
2.2
2.3
2.4
2.5
2.7
mm
26
27
29
30
32
34
36
37
40
42
47
51
55
mm
28
29
30
31
33
36
37
39
41
44
49
52
57
Kg/km
850
925
975
1100
1300
1400
1600
1800
2150
2400
2825
3500
4125
Kg/km
1050
1100
1225
1350
1475
1700
1925
2100
2450
2725
3450
3900
4600
Overall Diameter
(Approx.)
Weight of Cable
(Approx)
Trefoil
Flat
Touching
Flat
Spaced
Amps
107
127
150
182
217
246
274
309
355
397
448
494
549
Amps
111
131
154
187
221
249
274
305
344
378
416
446
484
Amps
101
121
142
174
207
235
262
297
342
383
434
482
537
Amps
103
123
145
177
210
239
265
298
342
382
430
470
521
Amps
126
152
182
226
275
317
360
413
485
552
638
724
824
Amps
128
155
185
230
279
321
361
411
478
539
613
677
755
Amps
147
178
212
263
317
363
405
457
526
587
656
718
792
Flat
Touching
ducts
kA
2.360
3.304
4.720
6.608
8.968
11.328
14.160
17.464
22.656
28.320
37.760
47.200
59.472
Trefoil
ducts
0.21
0.23
0.25
0.29
0.31
0.34
0.37
0.40
0.45
0.49
0.55
0.60
0.68
In air
Flat
Spaced
F/km
0.790
0.765
0.745
0.713
0.697
0.678
0.663
0.647
0.627
0.611
0.591
0.576
0.560
Buried
Direct
In
the
ground
mH/km
In single -way
ducts
Trefoil
Trefoil
mH/km
0.488
0.472
0.455
0.428
0.416
0.401
0.390
0.378
0.363
0.351
0.338
0.328
0.317
Conductor
Short Circuit
Current
for 1 second
Ohm/km
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
Capacitance
25
35
50
70
95
120
150
185
240
300
400
500
630
Inductance
Flat
mm
Max DC
Resistance
@ 20C
Size
Current ratings
V/A.Km
1.323
0.979
0.743
0.535
0.407
0.336
0.286
0.241
0.198
0.17
0.146
0.127
0.112
Laying condition: Maximum conductor temperature 90C, Ambient temperature 30C. Underground temperature of soil 20C, Depth of laying - 0.8m.
Ground thermal resistivity 1.5 K.m/W, thermal resisitivity of earthenware ducts 1.2 K.m/W.
Note: Area of copper wire considered is 16 mm2 up to 120 mm2, 25 mm2 from 150 mm2 up to 300 mm2, 35 mm2 from 400 mm2 up to 630 mm2.
41
IEC 60502-2
1.
2.
3.
4.
Size
mm
25
35
50
70
95
120
150
185
240
300
400
500
630
Conductor
Conductor Screen
XLPE Insulation
Insulation Screen (Non-metallic)
Diameter of
Conductor
(Approx.)
Nominal
Insulation
Thickness
Diameter
Over
Insulation
(Approx.)
mm
6.0
7.1
8.3
9.7
11.55
12.95
14.3
15.9
18.4
20.5
24.0
27.0
30.4
mm
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
mm
16.6
17.7
18.9
20.3
22.15
23.55
24.9
26.5
29.0
31.1
34.6
37.6
41.0
7 6 5 4 3 2 1
Nominal
Outer Sheath
Thickness
CUT/CUW
CUT
CUW
CUT
CUW
CUT
CUW
mm
1.6
1.6
1.6
1.6
2.0
2.0
2.0
2.0
2.0
2.5
2.5
2.5
2.5
mm
1.8
1.9
1.9
1.9
2.0
2.1
2.1
2.2
2.3
2.3
2.5
2.6
2.7
mm
1.9
1.9
1.9
2.0
2.1
2.1
2.2
2.2
2.3
2.4
2.5
2.6
2.7
mm
28
30
31
33
35
37
38
40
43
46
50
53
57
mm
30
31
32
34
37
38
40
41
44
48
51
55
59
Kg/km
925
1050
1100
1225
1475
1625
1775
2025
2300
2575
3225
3700
4375
Kg/km
1175
1275
1350
1500
1775
1875
2100
2325
2650
3075
3675
4175
4850
Overall Diameter
(Approx.)
Weight of Cable
(Approx)
Trefoil
Flat
Touching
Flat
Spaced
Amps
107
127
150
182
217
246
274
309
355
397
448
494
549
Amps
111
131
154
187
221
249
274
305
344
378
416
446
484
Amps
101
121
142
174
207
235
262
297
342
383
434
482
537
Amps
103
123
145
177
210
239
265
298
342
382
430
470
521
Amps
126
152
182
226
275
317
360
413
485
552
638
724
824
Amps
128
155
185
230
279
321
361
411
478
539
613
677
755
Amps
147
178
212
263
317
363
405
457
526
587
656
718
792
Flat
Touching
ducts
kA
2.360
3.304
4.720
6.608
8.968
11.328
14.160
17.464
22.656
28.320
37.760
47.200
59.472
Trefoil
ducts
0.17
0.19
0.21
0.23
0.25
0.27
0.29
0.32
0.35
0.39
0.43
0.48
0.53
In air
Flat
Spaced
F/km
0.796
0.771
0.751
0.719
0.703
0.684
0.668
0.652
0.632
0.616
0.596
0.582
0.656
Buried
Direct
In
the
ground
mH/km
In single -way
ducts
Trefoil
Trefoil
mH/km
0.505
0.484
0.468
0.441
0.428
0.413
0.401
0.388
0.373
0.361
0.346
0.337
0.325
Conductor
Short Circuit
Current
for 1 second
Ohm/km
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
Capacitance
25
35
50
70
95
120
150
185
240
300
400
500
630
Inductance
Flat
mm
Max DC
Resistance
@ 20C
Size
Current ratings
V/A.Km
1.326
0.982
0.746
0.538
0.409
0.338
0.288
0.242
0.200
0.172
0.147
0.128
0.113
Laying condition: Maximum conductor temperature 90C, Ambient temperature 30C. Underground temperature of soil 20C, Depth of laying - 0.8m.
Ground thermal resistivity 1.5 K.m/W, thermal resisitivity of earthenware ducts 1.2 K.m/W.
Note: Area of copper wire considered is 16 mm2 up to 120 mm2, 25 mm2 from 150 mm2 up to 300 mm2, 35 mm2 from 400 mm2 up to 630 mm2.
42
IEC 60502-2
1.
2.
3.
4.
Size
mm
25
35
50
70
95
120
150
185
240
300
400
500
630
Conductor
Conductor Screen
XLPE Insulation
Insulation Screen (Non-metallic)
Diameter of
Conductor
(Approx.)
Nominal
Insulation
Thickness
Diameter
Over
Insulation
(Approx.)
mm
6.0
7.1
8.3
9.7
11.55
12.95
14.3
15.9
18.4
20.5
24.0
27.0
30.4
mm
6.0
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
mm
19.6
19.7
20.9
22.3
24.15
25.55
26.9
28.5
31.0
33.1
36.6
39.6
43.0
7 6 5 4 3 2 1
Nominal
Outer Sheath
Thickness
CUT/CUW
CUT
CUW
CUT
CUW
CUT
CUW
mm
1.6
1.6
1.6
2.0
2.0
2.0
2.0
2.0
2.0/2.5
2.5
2.5
2.5
2.5
mm
1.9
1.9
2.0
2.0
2.1
2.1
2.2
2.2
2.3
2.4
2.5
2.6
2.8
mm
2.0
2.0
2.0
2.1
2.1
2.2
2.2
2.3
2.4
2.5
2.6
2.7
2.8
mm
32
32
32
35
37
39
40
42
45
48
52
56
59
mm
33
33
35
37
39
40
42
44
48
50
54
57
61
Kg/km
1150
1175
1250
1500
1650
1850
2000
2200
2475
2925
3425
4000
4650
Kg/km
1375
1400
1600
1700
1875
2100
2300
2525
3025
3325
3900
4450
5100
Overall Diameter
(Approx.)
Weight of Cable
(Approx)
Trefoil
Flat
Touching
Flat
Spaced
Amps
107
127
150
182
217
246
274
309
355
397
448
494
549
Amps
111
131
154
187
221
249
274
305
344
378
416
446
484
Amps
101
121
142
174
207
235
262
297
342
383
434
482
537
Amps
103
123
145
177
210
239
265
298
342
382
430
470
521
Amps
126
152
182
226
275
317
360
413
485
552
638
724
824
Amps
128
155
185
230
279
321
361
411
478
539
613
677
755
Amps
147
178
212
263
317
363
405
457
526
587
656
718
792
Flat
Touching
ducts
kA
2.360
3.304
4.720
6.608
8.968
11.328
14.160
17.464
22.656
28.320
37.760
47.200
59.472
Trefoil
ducts
0.14
0.16
0.18
0.20
0.21
0.23
0.25
0.27
0.30
0.33
0.37
0.40
0.45
In air
Flat
Spaced
F/km
0.805
0.776
0.456
0.724
0.708
0.689
0.673
0.657
0.637
0.621
0.601
0.586
0.569
Buried
Direct
In
the
ground
mH/km
In single -way
ducts
Trefoil
Trefoil
mH/km
0524
0.496
0.478
0.452
0.438
0.23
0.410
0.397
0.382
0.370
0.355
0.345
0.333
Conductor
Short Circuit
Current
for 1 second
Ohm/km
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
Capacitance
25
35
50
70
95
120
150
185
240
300
400
500
630
Inductance
Flat
mm
Max DC
Resistance
@ 20C
Size
Current ratings
V/A.Km
1.33
0.984
0.748
0.540
0.411
0.34
0.289
0.244
0.201
0.174
0.149
0.130
0.115
Laying condition: Maximum conductor temperature 90C, Ambient temperature 30C. Underground temperature of soil 20C, Depth of laying - 0.8m.
Ground thermal resistivity 1.5 K.m/W, thermal resisitivity of earthenware ducts 1.2 K.m/W.
Note: Area of copper wire considered is 16 mm2 up to 120 mm2, 25 mm2 from 150 mm2 up to 300 mm2, 35 mm2 from 400 mm2 up to 630 mm2.
43
IEC 60502-2
Conductor
Conductor Screen
XLPE Insulation
Insulation Screen (Non-metallic)
Nominal
Insulation
Thickness
Diameter
Over
Insulation
(Approx.)
mm
50
70
95
120
150
185
240
300
400
500
630
mm
8.3
9.7
11.55
12.95
14.3
15.9
18.4
20.5
24.0
27.0
30.4
mm
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
mm
25.9
27.3
29.15
30.55
31.9
33.5
36.0
38.1
41.6
44.6
48.0
Nominal
Diameter of
Aluminium Wire
Nominal
Outer Sheath
Thickness
Overall Diameter
(Approx.)
Weight of Cable
(Approx)
CUT/CUW
CUT
CUW
CUT
CUW
CUT
CUW
mm
2.0
2.0
2.0
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
mm
2.2
2.2
2.3
2.3
2.4
2.5
2.5
2.6
2.7
2.8
2.9
mm
2.2
2.3
2.3
2.4
2.5
2.5
2.6
2.7
2.8
2.9
3.0
mm
39
41
43
44
47
49
52
54
58
61
65
mm
41
42
44
46
49
50
53
55
60
63
67
Kg/km
1775
1900
2125
2225
2600
2850
3125
3475
4050
4600
5275
Kg/km
2000
2150
2350
2500
2950
3150
3550
3875
4550
5075
5775
In single -way
ducts
Flat
Trefoil
Flat
Spaced
Trefoil
ducts
Flat
Touching
ducts
Trefoil
Flat
Touching
Flat
Spaced
mm
Ohm/km
mH/km
mH/km
F/km
kA
Amps
Amps
Amps
Amps
Amps
Amps
Amps
50
0.641
0.509
0.772
0.14
4.720
150
154
142
145
182
185
212
0.754
70
0.443
0.481
0.740
0.16
6.608
182
187
174
177
226
230
263
0.545
Conductor
Short Circuit
Current
for 1 second
Trefoil
In air
Max DC
Resistance
@ 20C
Buried
Direct
In
the
ground
Current ratings
SIZE
Inductance
Capacitance
Size
Diameter of
Conductor
(Approx.)
7 6 5 4 3 2 1
1.
2.
3.
4.
V/A.Km
95
0.320
0.467
0.723
0.17
8.968
217
221
207
210
275
279
317
0.417
120
0.253
0.450
0.704
0.18
11.328
246
249
235
239
317
321
363
0.345
150
0.206
0.437
0.688
0.19
14.160
274
274
262
265
360
361
405
0.294
185
0.164
0.424
0.672
0.21
17.464
309
305
297
298
413
411
457
0.249
240
0.125
0.407
0.652
0.23
22.656
355
344
342
342
485
478
526
0.206
300
0.100
0.394
0.635
0.25
28.320
397
378
383
382
552
539
587
0.179
400
0.0778
0.377
0.614
0.27
37.760
448
416
434
430
638
613
656
0.153
500
0.0605
0.366
0.599
0.30
47.200
494
446
482
470
724
677
718
0.134
630
0.0469
0.353
0.582
0.33
59.472
549
484
537
521
824
755
792
0.118
Laying condition: Maximum conductor temperature 90C, Ambient temperature 30C. Underground temperature of soil 20C, Depth of laying - 0.8m.
Ground thermal resistivity 1.5 K.m/W, thermal resisitivity of earthenware ducts 1.2 K.m/W.
Note: Area of copper wire considered is 16 mm2 up to 120 mm2, 25 mm2 from 150 mm2 up to 300 mm2, 35 mm2 from 400 mm2 up to 630 mm2.
44
IEC 60502-2
1.
2.
3.
4.
Size
mm
25
35
50
70
95
120
150
185
240
300
Conductor
Conductor Screen
XLPE Insulation
Insulation Screen (Non-metallic)
Diameter of
Conductor
(Approx.)
Nominal
Insulation
Thickness
Diameter
Over Insulation
(Approx.)
mm
6.0
7.1
8.3
9.7
11.55
12.95
14.3
15.9
18.4
20.5
mm
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.6
2.8
mm
12.6
13.7
14.9
16.3
18.15
19.55
20.9
22.5
25.2
27.7
Uo/U (Um)=3.5/6(7.2)kV
7 6 5 4
3 2 1
Overall Diameter
(Approx.)
Weight of Cable
(Approx)
CUT
CUW
CUT
CUW
CUT
CUW
mm
2.1
2.1
2.2
2.3
2.5
2.6
2.7
2.8
3.0
3.2
mm
2.1
2.2
2.3
2.4
2.5
2.6
2.8
2.9
3.0
3.2
mm
39
41
44
45
27
55
58
62
68
75
mm
42
45
48
51
55
59
62
65
72
78
Kg/km
1425
1625
1875
2250
2725
3100
3550
4050
4975
6050
Kg/km
1600
1825
2100
2450
2900
3300
3800
4325
5225
6275
Current ratings
Conductor
Short Circuit
Current
for 1 second
Size
Max DC
Resistance
@ 20C
Nominal
Inductance
mm
Ohm/km
mH/km
F/km
kA
25
1.20
0.305
0.26
2.360
35
0.868
0.294
0.29
50
0.641
0.283
0.31
70
0.443
0.272
95
0.320
0.266
Capacitance
Buried Direct
In the ground
Voltage drop
Per phase
In buried ducts
In air
Amps
Amps
Amps
V/A.Km
100
87
110
1.288
3.304
119
103
132
0.946
4.720
140
122
158
0.711
0.36
6.608
171
150
196
0.506
0.39
8.968
203
179
236
0.379
0.309
120
0.253
0.259
0.43
11.328
232
205
273
150
0.206
0.253
0.47
14.160
260
231
309
0259
185
0.164
0.250
0.52
17.464
294
262
355
0.217
240
0.125
0.243
0.56
22.656
340
305
415
0.175
300
0.100
0.236
0.58
28.320
384
346
475
0.149
Laying condition: Maximum conductor temperature 90C, Ambient temperature 30C. Underground temperature of soil 20C, Depth of laying - 0.8m.
Ground thermal resistivity 1.5 K.m/W, thermal resisitivity of earthenware ducts 1.2 K.m/W.
Note: Area of copper wire considered is 16 mm2 up to 120 mm2, 25 mm2 from 150 mm2 up to 300 mm2, 35 mm2 from 400 mm2 up to 630 mm2.
45
IEC 60502-2
1. Conductor
2. Conductor Screen
3. XLPE Insulation
4. Insulation Screen (Non-metallic)
Size
mm
25
35
50
70
95
120
150
185
240
300
Nominal
Insulation
Thickness
Diameter
Over Insulation
(Approx.)
mm
6.0
7.1
8.3
9.7
11.55
12.95
14.3
15.9
18.4
20.5
mm
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
mm
14.4
15.5
16.7
18.1
19.95
21.35
22.7
24.3
26.8
28.9
Size
Nominal
Inductance
mm
25
35
50
70
95
120
150
185
240
300
Ohm/km
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
mH/km
0.331
0.318
0.308
0.292
0.285
0.276
0.269
0.263
0.255
0.248
Capacitance
F/km
0.21
0.23
0.25
0.29
0.31
0.34
0.37
0.40
0.44
0.48
3 2 1
Diameter of
Conductor
(Approx.)
Max DC
Resistance
@ 20C
7 6 5 4
Uo/U (Um)=6/10(12)kV
Conductor
Short Circuit
Current
for 1 second
kA
2.360
3.304
4.720
6.608
8.968
11.328
14.160
17.464
22.656
28.320
Overall Diameter
(Approx.)
Weight of Cable
(Approx)
CUT
CUW
CUT
CUW
CUT
CUW
mm
2.2
2.3
2.4
2.5
2.6
2.7
2.8
2.9
3.1
3.3
mm
2.2
2.3
2.4
2.5
2.7
2.8
2.9
3.0
3.2
3.3
mm
43
46
49
52
56
60
63
67
73
79
mm
46
49
52
55
60
63
66
70
76
81
Kg/km
1700
1950
2225
2575
3050
3500
3925
4450
5450
6375
Kg/km
1850
2150
2400
2750
3275
3675
4175
4750
5775
6600
Current ratings
Buried Direct
In the ground
In buried ducts
In air
Voltage drop
Per phase
Amps
87
103
122
150
179
205
231
262
305
346
Amps
110
132
158
196
236
273
309
355
415
475
V/A.Km
1.293
0.95
0.716
.0510
0.383
0.312
0.263
0.219
0.177
0.151
Amps
100
119
140
171
203
232
260
294
340
384
Laying condition: Maximum conductor temperature 90C, Ambient temperature 30C. Underground temperature of soil 20C, Depth of laying - 0.8m.
Ground thermal resistivity 1.5 K.m/W, thermal resisitivity of earthenware ducts 1.2 K.m/W.
Note: Area of copper wire considered is 16 mm2 up to 120 mm2, 25 mm2 from 150 mm2 up to 300 mm2, 35 mm2 from 400 mm2 up to 630 mm2.
46
IEC 60502-2
1.
2.
3.
4.
Conductor
Conductor Screen
XLPE Insulation
Insulation Screen (Non-metallic)
Size
Diameter of
Conductor
(Approx.)
Nominal
Insulation
Thickness
Diameter
Over
Insulation
(Approx.)
mm
25
35
50
70
95
120
150
185
240
300
mm
6.0
7.1
8.3
9.7
11.55
12.95
14.3
15.9
18.4
20.5
mm
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
mm
16.6
17.7
18.9
20.3
22.15
23.55
24.9
26.5
29.0
31.1
Size
Max DC
Resistance
@ 20C
Nominal
Inductance
mm
25
35
50
70
95
120
150
185
240
300
Ohm/km
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
mH/km
0.359
0.344
0.332
0.314
0.306
0.296
0.288
0.280
0.271
0.260
Capacitance
F/km
0.17
0.19
0.21
0.23
0.25
0.27
0.29
0.32
0.35
0.39
Uo/U (Um)=8.7/15(17.5)kV
7 6 5 4
3 2 1
Overall Diameter
(Approx.)
Weight of Cable
(Approx)
CUT
CUW
CUT
CUW
CUT
CUW
mm
2.4
2.5
2.6
2.7
2.8
2.9
3.0
3.1
3.3
3.4
mm
2.4
2.5
2.6
2.7
2.8
2.9
3.1
3.2
3.3
3.5
mm
49
52
55
58
63
66
69
73
79
84
mm
52
55
57
61
65
68
72
76
81
86
Kg/km
1950
2425
2700
3150
3675
4075
4525
5175
6125
6975
Kg/km
2025
2525
2800
3250
3875
4200
4725
5350
6275
7150
Conductor
Short Circuit
Current
for 1 second
kA
2.360
3.304
4.720
6.608
8.968
11.328
14.160
17.464
22.656
28.320
Current ratings
Buried Direct
In the ground
Amps
100
119
140
171
203
232
260
294
340
384
In buried ducts
In air
Voltage drop
Per phase
Amps
87
103
122
150
179
205
231
262
305
346
Amps
110
132
158
196
236
273
309
355
415
475
V/A.Km
1.299
0.955
0.72
0.514
0.386
0.316
0.266
0.222
0.18
0.153
Laying condition: Maximum conductor temperature 90C, Ambient temperature 30C. Underground temperature of soil 20C, Depth of laying - 0.8m.
Ground thermal resistivity 1.5 K.m/W, thermal resisitivity of earthenware ducts 1.2 K.m/W.
Note: Area of copper wire considered is 16 mm2 up to 120 mm2, 25 mm2 from 150 mm2 up to 300 mm2, 35 mm2 from 400 mm2 up to 630 mm2.
47
IEC 60502-2
1.
2.
3.
4.
Size
mm
25
35
50
70
95
120
150
185
240
300
Conductor
Conductor Screen
XLPE Insulation
Insulation Screen (Non-metallic)
Diameter of
Conductor
(Approx.)
Nominal
Insulation
Thickness
Diameter
Over Insulation
(Approx.)
mm
6.0
7.1
8.3
9.7
11.55
12.95
14.3
15.9
18.4
20.5
mm
6.0
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
mm
19.6
19.7
20.9
22.3
24.15
25.55
26.9
28.5
31.0
33.1
Size
Max DC
Resistance
@ 20C
Nominal
Inductance
mm
25
35
50
70
95
120
150
185
240
300
Ohm/km
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
mH/km
0.394
0.365
0.352
0.332
0.323
0.312
0.303
0.295
0.285
0.270
Capacitance
F/km
0.14
0.16
0.18
0.20
0.21
0.23
0.25
0.27
0.30
0.33
Uo/U (Um)=12/20(24)kV
7 6 5 4
3 2 1
Overall Diameter
(Approx.)
Weight of Cable
(Approx)
CUT
CUW
CUT
CUW
CUT
CUW
mm
2.6
2.6
2.7
2.8
2.9
3.0
3.1
3.3
3.4
3.6
mm
2.6
2.7
2.8
2.9
3.0
3.1
3.2
3.3
3.5
3.6
mm
55
56
58
62
66
70
74
78
83
88
mm
59
60
61
65
69
73
77
80
86
91
Kg/km
2650
2700
3050
3450
4000
4525
5075
5700
6650
7575
Kg/km
2850
2950
3225
3625
4175
4700
5325
5925
6925
7775
Conductor
Short Circuit
Current
for 1 second
kA
2.360
3.304
4.720
6.608
8.968
11.328
14.160
17.464
22.656
28.320
Current ratings
Buried Direct
In the ground
In buried ducts
In air
Amps
87
103
122
150
179
205
231
262
305
346
Amps
110
132
158
196
236
273
309
355
415
475
Amps
100
119
140
171
203
232
260
294
340
384
Voltage drop
Per phase
V/A.Km
0.305
0.959
0.724
0.517
0.389
0.319
0.269
0.225
0.183
0.155
Laying condition: Maximum conductor temperature 90C, Ambient temperature 30C. Underground temperature of soil 20C, Depth of laying - 0.8m.
Ground thermal resistivity 1.5 K.m/W, thermal resisitivity of earthenware ducts 1.2 K.m/W.
Note: Area of copper wire considered is 16 mm2 up to 120 mm2, 25 mm2 from 150 mm2 up to 300 mm2, 35 mm2 from 400 mm2 up to 630 mm2.
48
IEC 60502-2
1.
2.
3.
4.
Conductor
Conductor Screen
XLPE Insulation
Insulation Screen (Non-metallic)
Diameter
of
Conductor
(Approx.)
Nominal
Insulation
Thickness
mm
mm
mm
50
8.3
8.0
70
9.7
8.0
27.3
Size
Diameter
Over
Insulation
(Approx.)
Uo/U (Um)=18/30(36)kV
7 6 5 4
3 2 1
Overall Diameter
(Approx.)
Weight of Cable
(Approx)
CUT
CUW
CUT
CUW
CUT
CUW
mm
mm
mm
mm
mm
Kg/km
Kg/km
25.9
3.1
3.1
72
74
4300
4425
3.2
3.2
75
77
4825
4950
95
11.5
8.0
29.15
3.4
3.4
79
82
5475
5600
120
12.95
8.0
30.55
3.4
3.5
82
85
5925
6100
150
14.3
8.0
31.9
3.5
3.6
85
88
6450
6625
185
15.9
8.0
33.5
3.6
3.7
89
92
7100
7275
240
18.4
8.0
36.0
3.8
3.9
95
98
8275
8475
300
20.5
8.0
38.1
4.0
4.0
100
103
9275
9425
Size
Max DC
Resistance
@ 20C
Nominal
Inductance
Capacitance
Conductor
Short Circuit
Current
for 1 second
mm
50
70
95
120
150
185
240
300
Ohm/km
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
mH/km
0.404
0.380
0.369
0.355
0.345
0.334
0.321
0.308
F/km
0.14
0.16
0.17
0.18
0.19
0.21
0.23
0.25
kA
4.720
6.608
8.968
11.328
14.160
17.464
22.656
28.320
Current ratings
Buried Direct
In the ground
Amps
140
171
203
232
260
294
340
384
In buried ducts
In air
Voltage drop
Per phase
Amps
122
150
179
205
231
262
305
346
Amps
158
196
236
273
309
355
415
475
V/A.Km
0.734
0.526
0.398
0.327
0.277
0.232
0.19
0.162
Laying condition: Maximum conductor temperature 90C, Ambient temperature 30C. Underground temperature of soil 20C, Depth of laying - 0.8m.
Ground thermal resistivity 1.5 K.m/W, thermal resisitivity of earthenware ducts 1.2 K.m/W.
Note: Area of copper wire considered is 16 mm2 up to 120 mm2, 25 mm2 from 150 mm2 up to 300 mm2, 35 mm2 from 400 mm2 up to 630 mm2.
49
IEC 60502-2
1. Conductor
2. Conductor Screen
3. XLPE Insulation
4. Insulation Screen (Non-Metallic)
5. Insulation Screen (Metallic)
Size
Mm
25
35
50
70
95
120
150
185
240
300
Diameter of
Conductor
(Approx.)
Nominal
Insulation
Thickness
Diameter
Over Insulation
(Approx.)
mm
6.0
7.1
8.3
9.7
11.55
12.95
14.3
15.9
18.4
20.5
mm
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.6
2.8
mm
12.6
13.7
14.9
16.3
18.15
19.55
20.9
22.5
25.2
27.7
Size
Max DC
Resistance
@ 20C
Nominal
Inductance
mm
25
35
50
70
95
120
150
185
240
300
Ohm/km
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
mH/km
0.363
0.344
0.333
0.322
0.316
0.309
0.303
0.300
0.293
0.286
Capacitance
F/km
0.26
0.29
0.31
0.36
0.39
0.43
0.47
0.52
0.56
0.58
Uo/U (Um)=3.5/6(7.2) kV
765 4 3 2 1
6. PP Filler
7. Bedding
8. Steel Wire Armour
9. Outer Sheath
Nominal
Outer Sheath
Thickness
Overall Diameter
(Approx.)
Weight of Cable
(Approx)
CUT / CUT
CUT
CUW
CUT
CUW
CUT
CUW
mm
2.0
2.0
2.5
2.5
2.5
2.5
2.5
2.5
2.5/3.15
3.15
mm
2.3
2.3
2.5
2.6
2.7
2.8
2.9
3.1
3.3
3.5
mm
2.3
2.4
2.5
2.6
2.8
2.9
3.0
3.1
3.3
3.5
mm
42
45
49
53
57
60
63
67
74
82
mm
45
50
52
55
60
64
67
70
78
85
Kg/km
2850
3150
3950
4475
5150
5475
6200
6975
8150
10525
Kg/km
3025
3900
4275
4750
5450
6025
6675
7350
9500
10875
Conductor
Short Circuit
Current
for 1 second
kA
2.360
3.304
4.720
6.608
8.968
11.328
14.160
17.464
22.656
28.320
Current ratings
Buried Direct
In the ground
Amps
100
119
140
171
204
232
259
293
338
380
In buried ducts
In air
Amps
87
104
123
150
180
206
231
262
304
343
Amps
111
133
159
196
238
274
309
354
415
472
Voltage drop
Per phase
V/A.Km
1.299
0.955
0.721
0.515
0.388
0.318
0.269
0.226
0.185
0.158
Laying condition: Maximum conductor temperature 90C, Ambient temperature 30C. Underground temperature of soil 20C, Depth of laying - 0.8m.
Ground thermal resistivity 1.5 K.m/W, thermal resisitivity of earthenware ducts 1.2 K.m/W.
Note: Area of copper wire considered is 16 mm2 up to 120 mm2, 25 mm2 from 150 mm2 up to 300 mm2, 35 mm2 from 400 mm2 up to 630 mm2.
50
IEC 60502-2
1.
2.
3.
4.
5.
Uo/U (Um)=6/10(12)kV
765 4 3 2 1
Conductor
6. PP Filler
Conductor Screen
7. Bedding
XLPE Insulation
8. Steel Wire Armour
Insulation Screen (Non-Metallic) 9. Outer Sheath
Insulation Screen (Metallic)
Size
Diameter of
Conductor
(Approx.)
Nominal
Insulation
Thickness
Diameter
Over
Insulation
(Approx.)
mm
25
35
50
70
95
120
150
185
240
300
mm
6.0
7.1
8.3
9.7
11.55
12.95
14.3
15.9
18.4
20.5
mm
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
mm
14.5
15.5
16.7
18.1
19.95
21.35
22.7
24.3
26.8
28.9
Number &
Nominal
Thickness of
steel Wire
Overall Diameter
(Approx.)
Weight of Cable
(Approx)
CUT / CUT
CUT
CUW
CUT
CUW
CUT
CUW
mm
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
3.15
3.15
mm
2.4
2.5
2.6
2.7
2.9
3.0
3.1
3.2
3.4
3.6
mm
2.5
2.6
2.7
2.8
2.9
3.0
3.2
3.3
3.5
3.6
mm
48
50
54
57
61
65
68
72
80
85
mm
51
54
57
60
64
68
71
75
83
88
Kg/km
3700
4050
4475
4950
5700
6300
6850
7600
9875
11025
Kg/km
4050
4375
4775
5325
6025
6575
7275
8025
10325
11450
Conductor
Short Circuit
Current
for 1 second
Size
Max DC
Resistance
@ 20C
Nominal
Inductance
mm
Ohm/km
mH/km
F/km
kA
25
1.20
0.387
0.21
2.360
35
0.868
0.368
0.23
50
0.641
0.355
0.25
Capacitance
Nominal Outer
Sheath Thickness
Current ratings
In buried ducts
In air
Voltage drop
Per phase
Amps
Amps
Amps
V/A.Km
100
87
111
1.304
3.304
119
104
133
0.960
4.720
140
123
159
0.725
Buried Direct
In the ground
70
0.443
0.342
0.29
6.608
171
150
196
0.519
95
0.320
0.355
0.31
8.968
204
180
238
0.392
120
0.253
0.326
0.34
11.328
232
206
274
0.321
150
0.206
0.319
0.37
14.160
259
231
309
0.272
185
0.164
0.313
0.40
17.464
293
262
354
0.228
240
0.125
0.303
0.44
22.656
338
304
415
0.187
300
0.100
0.297
0.48
28.320
380
343
472
0.160
Laying condition: Maximum conductor temperature 90C, Ambient temperature 30C. Underground temperature of soil 20C, Depth of laying - 0.8m.
Ground thermal resistivity 1.5 K.m/W, thermal resisitivity of earthenware ducts 1.2 K.m/W.
Note: Area of copper wire considered is 16 mm2 up to 120 mm2, 25 mm2 from 150 mm2 up to 300 mm2, 35 mm2 from 400 mm2 up to 630 mm2.
51
IEC 60502-2
1.
2.
3.
4.
5.
Size
mm
25
35
50
70
95
120
150
185
240
300
Conductor
Conductor Screen
XLPE Insulation
Insulation Screen (Non-Metallic)
Insulation Screen (Metallic)
Diameter of
Conductor
(Approx.)
Nominal
Insulation
Thickness
Diameter
Over
Insulation
(Approx.)
mm
6.0
7.1
8.3
9.7
11.55
12.95
14.3
15.9
18.4
20.5
mm
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
mm
16.6
17.7
18.9
20.3
22.15
23.55
24.9
26.5
29.0
31.1
Number &
Nominal
Thickness of
steel Wire
765 4 3 2 1
6. PP Filler
7. Bedding
8. Steel Wire Armour
9. Outer Sheath
Nominal Outer
Sheath Thickness
Overall Diameter
(Approx.)
Weight of Cable
(Approx)
CUT / CUT
CUT
CUW
CUT
CUW
CUT
CUW
mm
2.5
2.5
2.5
2.5
2.5
2.5
2.5
3.15
3.15
3.15
mm
2.6
2.7
2.8
2.9
3.0
3.2
3.3
3.4
3.6
3.8
mm
2.6
2.7
2.8
2.9
3.1
3.2
3.4
3.5
3.7
3.8
mm
53
56
59
62
66
70
73
79
85
90
mm
56
59
62
65
70
73
78
82
88
93
Kg/km
4350
4700
5175
5675
6425
7000
7600
9450
10775
12000
Kg/km
4625
5000
5450
6050
6725
7350
8925
9900
11200
12400
Conductor
Short Circuit
Current
for 1 second
Size
Max DC
Resistance
@ 20C
Nominal
Inductance
mm
Ohm/km
mH/km
F/km
kA
25
1.20
0.413
0.17
2.360
35
0.868
0.394
0.19
50
0.641
0.382
0.21
70
0.443
0.364
0.23
Capacitance
Uo/U (Um)=8.7/15(17.5)kV
Current ratings
In buried ducts
In air
Voltage drop
Per phase
Amps
Amps
Amps
V/A.Km
100
87
111
1.309
3.304
119
104
133
0.965
4.720
140
123
159
0.73
6.608
171
150
196
0.523
Buried Direct
In the ground
95
0.320
0.356
0.25
8.968
204
180
238
0.396
120
0.253
.0346
0.27
11.328
232
206
274
0.325
150
0.206
0.338
0.29
14.160
259
231
309
0.276
185
0.164
0.330
0.32
17.464
293
262
354
0.232
240
0.125
0.321
0.35
22.656
338
304
415
0.19
300
0.100
0.312
0.39
28.320
380
343
472
0.163
Laying condition: Maximum conductor temperature 90C, Ambient temperature 30C. Underground temperature of soil 20C, Depth of laying - 0.8m.
Ground thermal resistivity 1.5 K.m/W, thermal resisitivity of earthenware ducts 1.2 K.m/W.
Note: Area of copper wire considered is 16 mm2 up to 120 mm2, 25 mm2 from 150 mm2 up to 300 mm2, 35 mm2 from 400 mm2 up to 630 mm2.
52
IEC 60502-2
1.
2.
3.
4.
5.
Conductor
Conductor Screen
XLPE Insulation
Insulation Screen (Non-Metallic)
Insulation Screen (Metallic)
Size
Diameter of
Conductor
(Approx.)
Nominal
Insulation
Thickness
Diameter
Over Insulation
(Approx.)
mm
25
35
50
70
95
120
150
185
240
300
mm
6.0
7.1
8.3
9.7
11.55
12.95
14.3
15.9
18.4
20.5
mm
6.0
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
mm
19.6
19.7
20.9
22.3
24.15
25.55
26.9
28.5
31.0
33.1
765 4 3 2 1
6. PP Filler
7. Bedding
8. Steel Wire Armour
9. Outer Sheath
Number &
Nominal
Thickness of
steel Wire
Nominal Outer
Sheath Thickness
Overall Diameter
(Approx.)
Weight of Cable
(Approx)
CUT / CUT
CUT
CUW
CUT
CUW
CUT
CUW
mm
2.5
2.5
2.5
2.5
2.5
3.15
3.15
3.15
3.15
3.15
mm
2.8
2.8
2.9
3.1
3.2
3.4
3.5
3.6
3.8
3.9
mm
2.9
2.9
3.0
3.1
3.3
3.4
3.5
3.6
3.8
4.0
mm
60
60
64
67
71
77
80
84
90
95
mm
63
64
67
70
74
80
83
87
93
98
Kg/km
5225
5325
5825
6350
7150
8700
9400
10300
11625
12825
Kg/km
5575
5650
6100
6675
7400
9100
9875
10700
12075
13325
Conductor
Short Circuit
Current
for 1 second
Size
Max DC
Resistance
@ 20C
Nominal
Inductance
mm
Ohm/km
mH/km
F/km
kA
25
1.20
0.444
0.14
2.360
35
0.868
0.415
0.16
50
0.641
0.399
70
0.443
95
Capacitance
Uo/U (Um)=12/20(24)kV
Current ratings
Buried Direct
In the ground
Voltage drop
Per phase
In buried ducts
In air
Amps
Amps
Amps
V/A.Km
100
87
111
1.314
3.304
119
104
133
0.968
0.18
4.720
140
123
159
0.733
0.382
0.20
6.608
171
150
196
0.527
0.320
0.373
0.21
8.968
204
180
238
0.399
120
0.253
0.362
0.23
11.328
232
206
274
0.328
150
0.206
0.353
0.25
14.160
259
231
309
0.279
185
0.164
0.345
0.27
17.464
293
262
354
0.234
240
0.125
0.335
0.30
22.656
338
304
415
0.192
300
0.100
0.320
0.33
28.320
380
343
472
0.165
LLaying condition: Maximum conductor temperature 90C, Ambient temperature 30C. Underground temperature of soil 20C, Depth of laying - 0.8m.
Ground thermal resistivity 1.5 K.m/W, thermal resisitivity of earthenware ducts 1.2 K.m/W.
Note: Area of copper wire considered is 16 mm2 up to 120 mm2, 25 mm2 from 150 mm2 up to 300 mm2, 35 mm2 from 400 mm2 up to 630 mm2.
53
IEC 60502-2
1.
2.
3.
4.
5.
Conductor
Conductor Screen
XLPE Insulation
Insulation Screen (Non-Metallic)
Insulation Screen (Metallic)
Size
Diameter of
Conductor
(Approx.)
Nominal
Insulation
Thickness
Diameter
Over
Insulation
(Approx.)
mm
50
70
95
120
150
185
240
300
mm
8.3
9.7
11.5
12.95
14.3
15.3
18.4
20.5
mm
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
mm
25.9
27.3
29.15
30.55
31.9
33.5
36.0
38.1
Size
mm
Max DC
Resistance
@ 20C
Nominal
Inductance
Ohm/km
mH/km
Capacitance
F/km
Uo/U (Um)=18/30(36)kV
765 4 3 2 1
6. PP Filler
7. Bedding
8. Steel wire Armour
9. Outer Sheath
Number &
Nominal
Thickness of
steel
Wire
Nominal Outer
Sheath Thickness
Overall Diameter
(Approx.)
Weight of Cable
(Approx)
CUT / CUT
CUT
CUW
CUT
CUW
CUT
CUW
mm
3.15
3.15
3.15
3.15
3.15
3.15
3.15
3.15
mm
3.4
3.5
3.6
3.8
3.9
4.0
4.2
4.3
mm
3.5
3.6
3.7
3.8
3.9
4.0
4.2
4.4
mm
78
81
85
89
92
96
102
107
mm
81
84
80
92
95
99
105
110
Kg/km
8550
9225
10150
10900
11550
12500
13925
15350
Kg/km
8900
9600
10450
11200
12050
12900
14400
15725
Conductor
Short Circuit
Current
for 1 second
kA
Current ratings
Buried Direct
In the ground
Amps
In buried ducts
In air
Amps
Amps
Voltage drop
Per phase
V/A.Km
50
0.641
0.454
0.14
4.720
140
123
159
0.743
70
0.443
0.430
0.16
6.608
171
150
196
0.536
95
0.320
0.419
0.17
8.968
204
180
238
0.408
120
0.253
0.405
0.18
11.328
232
206
274
0.336
150
0.206
0.395
0.19
14.160
259
231
309
0.286
185
0.164
0.384
0.21
17.464
293
262
354
0.242
240
0.125
0.371
0.23
22.656
338
304
415
0.20
300
0.100
0.358
0.25
28.320
380
343
472
0.171
Laying condition: Maximum conductor temperature 90C, Ambient temperature 30C. Underground temperature of soil 20C, Depth of laying - 0.8m.
Ground thermal resistivity 1.5 K.m/W, thermal resisitivity of earthenware ducts 1.2 K.m/W.
Note: Area of copper wire considered is 16 mm2 up to 120 mm2, 25 mm2 from 150 mm2 up to 300 mm2, 35 mm2 from 400 mm2 up to 630 mm2.
54
IEC 60502-2
1. Conductor
2. Conductor Screen
3. XLPE Insulation
Size
Nominal
Insulation
Thickness
Diameter
Over
Insulation
(Approx.)
mm
25
35
50
70
95
120
150
185
240
300
mm
6.0
7.1
8.3
9.7
11.55
12.95
14.3
15.9
18.4
20.5
mm
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.6
2.8
mm
12.6
13.7
14.9
16.3
18.15
19.55
20.9
22.5
25.2
27.7
Size
Nominal
Inductance
mm
25
35
50
70
95
120
150
185
240
300
Ohm/km
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
mH/km
0.363
0.344
0.333
0.322
0.316
0.309
0.303
0.300
0.293
0.286
8 7 65 4
2 1
Diameter of
Conductor
(Approx.)
Max DC
Resistance
@ 20C
Uo/U (Um)=3.5/6(7.2) kV
Capacitance
F/km
0.26
0.29
0.32
0.36
0.39
0.43
0.47
0.52
0.56
0.58
Number &
Nominal
Thickness of
steel Tape
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
Conductor
Short Circuit
Current
for 1 second
kA
2.360
3.304
4.720
6.608
8.968
11.328
14.160
17.464
22.656
28.320
Nominal
Outer Sheath
Thickness
Overall Diameter
(Approx.)
Weight of Cable
(Approx)
CUT
CUW
CUT
CUW
CUT
CUW
mm
2.2
2.3
2.4
2.5
2.6
2.7
2.8
2.9
3.1
3.3
mm
2.2
2.3
2.4
2.5
2.6
2.8
2.9
3.0
3.2
3.4
mm
41
43
46
50
54
57
60
64
71
78
mm
44
46
50
53
57
61
64
67
74
81
Kg/km
2000
2300
2625
3025
3550
4000
4450
5075
6100
7275
Kg/km
2250
2575
2825
3275
3750
4225
4800
5375
6450
7575
Current ratings
Buried Direct
In the ground
Amps
100
119
140
171
204
232
259
293
338
380
In buried ducts
In air
Amps
87
104
123
150
180
206
231
262
304
343
Amps
111
133
159
196
238
274
309
354
415
472
Voltage drop
Per phase
V/A.Km
1.299
0.955
0.721
0.515
0.388
0.318
0.269
0.226
0.185
0.158
Laying condition: Maximum conductor temperature 90C, Ambient temperature 30C. Underground temperature of soil 20C, Depth of laying - 0.8m.
Ground thermal resistivity 1.5 K.m/W, thermal resisitivity of earthenware ducts 1.2 K.m/W.
Note: Area of copper wire considered is 16 mm2 up to 120 mm2, 25 mm2 from 150 mm2 up to 300 mm2, 35 mm2 from 400 mm2 up to 630 mm2.
55
IEC 60502-2
1. Conductor
2. Conductor Screen
3. XLPE Insulation
Uo/U (Um)=6/10(12) kV
8 7 65 4
2 1
7. Bedding
8. Steel Tape Armour
9. Outer Sheath
Diameter of
Conductor
(Approx.)
Nominal
Insulation
Thickness
Diameter
Over
Insulation
(Approx.)
Number &
Nominal
Thickness of
steel Tape
Nominal
Outer Sheath
Thickness
Overall Diameter
(Approx.)
CUT
CUW
CUT
CUW
CUT
CUW
Mm
25
35
50
70
95
120
150
185
240
300
mm
6.0
7.1
8.3
9.7
11.55
12.95
14.3
15.9
18.4
20.5
mm
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
mm
14.4
15.5
16.7
18.1
19.95
21.35
22.7
24.3
26.8
28.9
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
mm
2.3
2.4
2.5
2.6
2.7
2.9
3.0
3.1
3.3
3.4
mm
2.4
2.5
2.6
2.7
2.8
2.9
3.0
3.1
3.3
3.5
mm
45
47
51
54
58
62
65
69
76
81
mm
48
51
54
57
61
65
68
72
79
84
Kg/km
2400
2675
3000
3400
3975
4475
4950
5600
6750
7675
Kg/km
2625
2900
3225
3650
4200
4675
5275
5900
7000
8000
Size
Max DC
Resistance
@ 20C
Nominal
Inductance
mm
25
35
50
70
95
120
150
185
240
300
Ohm/km
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
mH/km
0.387
0.368
0.355
0.342
0.355
0.326
0.319
0.313
0.303
0.297
Size
Capacitance
F/km
0.21
0.23
0.25
0.29
0.31
0.34
0.37
0.40
0.44
0.48
Conductor
Short Circuit
Current
for 1 second
kA
2.360
3.304
4.720
6.608
8.968
11.328
14.160
17.464
22.656
28.320
Weight of Cable
(Approx)
Current ratings
Buried Direct
In the ground
Amps
100
119
140
171
204
232
259
293
338
380
In buried ducts
In air
Voltage drop
Per phase
Amps
87
104
123
150
180
206
231
262
304
343
Amps
111
133
159
196
238
274
309
354
415
472
V/A.Km
1.304
0.960
0.725
0.519
0.392
0.321
0.272
0.228
0.187
0.160
Laying condition: Maximum conductor temperature 90C, Ambient temperature 30C. Underground temperature of soil 20C, Depth of laying - 0.8m.
Ground thermal resistivity 1.5 K.m/W, thermal resisitivity of earthenware ducts 1.2 K.m/W.
Note: Area of copper wire considered is 16 mm2 up to 120 mm2, 25 mm2 from 150 mm2 up to 300 mm2, 35 mm2 from 400 mm2 up to 630 mm2.
56
IEC 60502-2
1. Conductor
2. Conductor Screen
3. XLPE Insulation
Size
Nominal
Insulation
Thickness
Diameter
Over Insulation
(Approx.)
mm
25
35
50
70
95
120
150
185
240
300
mm
6.0
7.1
8.3
9.7
11.55
12.95
14.3
15.9
18.4
20.5
mm
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
mm
16.6
17.7
18.9
20.3
22.15
23.55
24.9
26.5
29.0
31.1
Size
Nominal
Inductance
mm
25
35
50
70
95
120
150
185
240
300
Ohm/km
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
mH/km
0.413
0.394
0.382
0.364
0.356
.0346
0.338
0.330
0.321
0.312
8 7 65 4
2 1
Diameter of
Conductor
(Approx.)
Max DC
Resistance
@ 20C
Uo/U (Um)=8.7/15(17.5) kV
Capacitance
F/km
0.17
0.19
0.21
0.23
0.25
0.27
0.29
0.32
0.35
0.39
Nominal
Outer Sheath
Thickness
7. Bedding
8. Steel Tape Armour
9. Outer Sheath
Number &
Nominal
Thickness of
steel Tape
CUT
CUW
CUT
CUW
CUT
CUW
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.8
mm
2.5
2.6
2.7
2.8
2.9
3.0
3.1
3.3
3.4
3.6
mm
2.5
2.6
2.7
2.8
3.0
3.1
3.2
3.3
3.5
3.7
mm
50
53
56
59
63
67
70
75
81
88
mm
54
56
59
63
67
70
74
78
84
90
Kg/km
2875
3150
3500
3950
4550
5050
5550
6375
7425
9225
Kg/km
3075
3400
3750
4175
4775
5275
5850
6650
7725
9575
Conductor
Short Circuit
Current
for 1 second
kA
2.360
3.304
4.720
6.608
8.968
11.328
14.160
17.464
22.656
28.320
Overall Diameter
(Approx.)
Weight of Cable
(Approx)
Current ratings
Buried Direct
In the ground
Amps
100
119
140
171
204
232
259
293
338
380
In buried ducts
In air
Amps
87
104
123
150
180
206
231
262
304
343
Amps
111
133
159
196
238
274
309
354
415
472
Voltage drop
Per phase
V/A.Km
1.309
0.965
0.73
0.523
0.396
0.325
0.276
0.232
0.19
0.163
Laying condition: Maximum conductor temperature 90C, Ambient temperature 30C. Underground temperature of soil 20C, Depth of laying - 0.8m.
Ground thermal resistivity 1.5 K.m/W, thermal resisitivity of earthenware ducts 1.2 K.m/W.
Note: Area of copper wire considered is 16 mm2 up to 120 mm2, 25 mm2 from 150 mm2 up to 300 mm2, 35 mm2 from 400 mm2 up to 630 mm2.
57
IEC 60502-2
1. Conductor
2. Conductor Screen
3. XLPE Insulation
Diameter of
Conductor
(Approx.)
Nominal
Insulation
Thickness
Diameter
Over
Insulation
(Approx.)
mm
25
35
50
70
95
120
150
185
240
300
mm
6.0
7.1
8.3
9.7
11.55
12.95
14.3
15.9
18.4
20.5
mm
6.0
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
mm
19.6
19.7
20.9
22.3
24.15
25.55
26.9
28.5
31.0
33.1
Size
Nominal
Inductance
mm
25
35
50
70
95
120
150
185
240
300
Ohm/km
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
mH/km
0.444
0.415
0.399
0.382
0.373
0.362
0.353
0.345
0.335
0.320
8 7 65 4
2 1
Size
Max DC
Resistance
@ 20C
Uo/U (Um)=12/20(24) kV
Number &
Nominal
Thickness of
steel Tape
Capacitance
F/km
0.14
0.16
0.18
0.20
0.21
0.23
0.25
0.27
0.30
0.33
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
Conductor
Short Circuit
Current
for 1 second
kA
2.360
3.304
4.720
6.608
8.968
11.328
14.160
17.464
22.656
28.320
7. Bedding
8. Steel Tape Armour
9. Outer Sheath
Nominal Outer
Sheath Thickness
Overall Diameter
(Approx.)
Weight of Cable
(Approx)
CUT
CUW
CUT
CUW
CUT
CUW
mm
2.7
2.7
2.8
2.9
3.1
3.2
3.3
3.4
3.6
3.8
mm
2.8
2.8
2.9
3.0
3.1
3.2
3.4
3.5
3.7
3.9
mm
57
58
61
64
68
73
76
80
87
92
mm
61
61
63
67
72
76
79
83
90
95
Kg/km
350
3625
4000
4475
5125
5775
6300
7000
8925
9950
Kg/km
3750
3850
4225
4675
5325
5950
6600
7300
9250
10350
Current ratings
Buried Direct
In the ground
Amps
100
119
140
171
204
232
259
293
338
380
In buried ducts
In air
Amps
87
104
123
150
180
206
231
262
304
343
Amps
111
133
159
196
238
274
309
354
415
472
Voltage drop
Per phase
V/A.Km
1.314
0.968
0.733
0.527
0.399
0.328
0.279
0.234
0.192
0.165
Laying condition: Maximum conductor temperature 90C, Ambient temperature 30C. Underground temperature of soil 20C, Depth of laying - 0.8m.
Ground thermal resistivity 1.5 K.m/W, thermal resisitivity of earthenware ducts 1.2 K.m/W.
Note: Area of copper wire considered is 16 mm2 up to 120 mm2, 25 mm2 from 150 mm2 up to 300 mm2, 35 mm2 from 400 mm2 up to 630 mm2.
58
IEC 60502-2
1. Conductor
2. Conductor Screen
3. XLPE Insulation
Size
mm
50
70
95
120
150
185
240
300
Uo/U (Um)=18/30(36) kV
8 7 65 4 3
2 1
Diameter of
Conductor
(Approx.)
Nominal
Insulation
Thickness
Diameter
Over
Insulation
(Approx.)
Number &
Nominal
Thickness of
Aluminium Tape
mm
8.3
9.7
11.55
12.95
14.3
15.9
18.4
20.5
mm
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
mm
25.9
27.3
29.15
30.55
31.9
33.5
36.0
38.1
2x0.5
2x0.5
2x0.5
2x0.8
2x0.8
2x0.8
2x0.8
2x0.8
Size
Max DC
Resistance
@ 20C
Nominal
Inductance
mm
Ohm/km
mH/km
F/km
50
0.641
0.454
70
0.443
0.430
95
0.320
120
150
Conductor
Short Circuit
Current
for 1 second
Nominal Outer
Sheath Thickness
7. Bedding
8. Steel Tape Armour
9. Outer Sheath
Overall Diameter
(Approx.)
Weight of Cable
(Approx)
CUT
CUW
CUT
CUW
CUT
CUW
mm
3.2
3.3
3.5
3.6
3.7
3.9
4.0
4.2
mm
3.3
3.4
3.5
3.7
3.8
3.9
4.1
4.2
mm
74
77
82
86
89
93
100
104
mm
77
80
84
89
92
96
102
107
Kg/km
5500
6050
6775
8150
8775
9600
10900
12050
Kg/km
5725
6275
6950
8400
9075
9825
11125
12275
Current ratings
Buried Direct
In the ground
In buried ducts
In air
Voltage drop
Per phase
kA
Amps
Amps
Amps
V/A.Km
0.14
4.720
140
123
159
0.743
0.16
6.608
171
150
196
0.536
0.419
0.17
8.968
204
180
238
0.408
0.253
0.405
0.18
11.328
232
206
274
0.336
0.206
0.395
0.19
14.160
259
231
309
0.286
185
0.164
0.384
0.21
17.464
293
262
304
0.242
240
0.125
0.371
0.23
22.656
338
304
415
0.20
300
0.100
0.358
0.25
28.320
380
343
472
0.171
Capacitance
Laying condition: Maximum conductor temperature 90C, Ambient temperature 30C. Underground temperature of soil 20C, Depth of laying - 0.8m.
Ground thermal resistivity 1.5 K.m/W, thermal resisitivity of earthenware ducts 1.2 K.m/W.
Note: Area of copper wire considered is 16 mm2 up to 120 mm2, 25 mm2 from 150 mm2 up to 300 mm2, 35 mm2 from 400 mm2 up to 630 mm2.
59
Current Carrying Capacity for Aluminium Wire Armoured Cables with Single Point Bonding
CU/XLPE/AWA/PVC 3.5/6kV to 18/30kV
IEC
Current Carrying Capacity (2)
Size
Direct Buried
In Air
mm2
Amps
Amps
25
138
162
35
165
197
50
195
236
70
236
294
95
282
358
120
322
415
150
359
472
185
406
541
240
469
640
300
527
734
400
604
858
500
667
973
630
747
1114
Current Carrying Capacity for Aluminium Wire Armoured Cables with Single Point Bonding
AL/XLPE/AWA/PVC 3.5/6kV to 18/30kV
IEC
Current Carrying Capacity (2)
60
Size
Direct Buried
In Air
mm2
Amps
Amps
25
108
126
35
128
152
50
151
183
70
183
227
95
219
277
120
249
322
150
280
366
185
316
422
240
367
498
300
414
573
400
476
675
500
535
778
630
609
904
Derating Factors
90 C
25
35
40
45
50
55
60
1.08
1.04
0.96
0.91
0.87
0.82
0.76
0.71
90 C
Temperature (C)
10
15
25
30
35
40
45
50
1.07
1.04
0.96
0.93
0.89
0.85
0.80
0.76
185 mm
Three-Core Cables
> 185 mm
0.5
1.04
1.06
1.04
0.6
1.02
1.04
1.03
0.98
0.97
0.98
1.25
0.96
0.95
0.96
1.5
0.95
0.93
0.95
1.75
0.94
0.91
0.94
0.93
0.90
0.93
2.5
0.91
0.88
0.91
0.90
0.86
0.90
61
Derating Factors
Table 4: Correction Factors for Depth of Laying for Cables in Ducts
Single Core Cables
Depth of Laying (m)
185 mm
Three-Core Cables
> 185 mm
0.5
1.04
1.05
1.03
0.6
1.02
1.03
1.02
0.98
0.97
0.99
1.25
0.96
0.95
0.97
1.5
0.95
0.93
0.96
1.75
0.94
0.92
0.95
0.93
0.91
0.94
2.5
0.91
0.89
0.93
0.90
0.88
0.92
Table 5: Correction Factors for Soil Thermal Resistivities other than 1.5 k.m/W for Direct Buried
Single-Core Cable
Nominal area of
Conductor
62
mm
0.7
0.8
0.9
2.5
16
1.29
1.24
1.19
1.15
0.89
0.82
0.75
25
1.30
1.25
1.20
1.16
0.89
0.81
0.75
35
1.30
1.25
1.21
1.16
0.89
0.81
0.75
50
1.32
1.26
1.21
1.16
0.89
0.81
0.74
70
1.33
1.27
1.22
1.17
0.89
0.81
0.74
95
1.34
1.28
1.22
1.18
0.89
0.80
0.74
120
1.34
1.28
1.22
1.18
0.88
0.80
0.74
150
1.35
1.28
1.23
1.18
0.88
0.80
0.74
185
1.35
1.29
1.23
1.18
0.88
0.80
0.74
240
1.36
1.29
1.23
1.18
0.88
0.80
0.73
300
1.36
1.30
1.24
1.19
0.88
0.80
0.73
400
1.37
1.30
1.24
1.19
0.88
0.79
0.73
Derating Factors
Table 6: Correction Factors for Thermal Reisistivities other than 1.5 K.m/W for Single-Core
Cables in Buried Ducts
Nominal Area of
Conductor
mm
0.7
0.8
0.9
2.5
16
1.20
1.17
1.14
1.11
0.92
0.85
0.79
25
1.21
1.17
1.14
1.12
0.91
0.85
0.79
35
1.21
1.18
1.15
1.12
0.91
0.84
0.79
50
1.21
1.18
1.15
1.12
0.91
0.84
0.78
70
1.22
1.19
1.15
1.12
0.91
0.84
0.78
95
1.23
1.19
1.16
1.13
0.91
0.84
0.78
120
1.23
1.20
1.16
1.13
0.91
0.84
0.78
150
1.24
1.20
1.16
1.13
0.91
0.83
0.78
185
1.24
1.20
1.17
1.13
0.91
0.83
0.78
240
1.25
1.21
1.17
1.14
0.90
0.83
0.77
300
1.25
1.21
1.17
1.14
0.90
0.83
0.77
400
1.25
1.21
1.17
1.14
0.90
0.83
0.77
Table 7: Correction Factors for Thermal Reisistivities other than 1.5 K.m/W for Three Core
Cables Direct Buried
Nominal Area of
Conductor
mm
0.7
0.8
0.9
2.5
16
1.23
1.19
1.16
1.13
0.91
0.84
0.78
25
1.24
1.20
1.16
1.13
0.91
0.84
0.78
35
1.25
1.21
1.17
1.13
0.91
0.83
0.78
50
1.25
1.21
1.17
1.14
0.91
0.83
0.77
70
1.26
1.21
1.18
1.14
0.90
0.83
0.77
95
1.26
1.22
1.18
1.14
0.90
0.83
0.77
120
1.26
1.22
1.18
1.14
0.90
0.836
0.77
150
1.27
1.22
1.18
1.15
0.90
0.83
0.77
185
1.27
1.23
1.18
1.15
0.90
0.83
0.77
240
1.28
1.23
1.19
1.15
0.90
0.83
0.77
300
1.28
1.23
1.19
1.15
0.90
0.82
0.77
400
1.28
1.23
1.19
1.15
0.90
0.82
0.76
63
Derating Factors
Table 8: Correction Factors for Soil Thermal Resistivities other than 1.5Km/W for Three Core
Cables in Ducts
Nominal Area of
Conductor
mm
0.7
0.8
0.9
2.5
16
1.12
1.11
1.09
1.08
0.94
0.89
0.84
25
1.14
1.12
1.08
0.94
0.89
0.84
35
1.14
1.12
1.10
1.08
0.94
0.88
0.84
50
1.14
1.12
1.10
1.08
0.94
0.88
0.84
70
1.15
1.13
1.11
1.09
0.94
0.88
0.83
95
1.15
1.13
1.11
1.09
0.94
0.88
0.83
120
1.15
1.13
1.11
1.09
0.93
0.88
0.83
150
1.16
1.13
1.11
1.09
0.93
0.88
0.83
185
1.16
1.14
1.11
1.09
0.93
0.87
0.83
240
1.16
1.14
1.12
1.10
0.93
0.87
0.82
300
1.17
1.14
1.12
1.10
0.93
0.87
0.82
400
1.17
1.14
1.12
1.10
0.92
0.86
0.81
1.10
Table 9 : Correction Factors for Groups of Three Core Cables in Horizontal Formation
Laid in the Ground
Spacing Between Cable Centres
64
Touching
200
400
600
800
0.80
0.86
0.90
0.92
0.94
0.69
0.77
0.82
0.86
0.89
0.62
0.72
0.79
0.83
0.87
0.57
0.68
0.76
0.81
0.85
0.54
0.65
0.74
0.80
0.84
0.51
0.63
0.72
0.78
0.83
0.49
0.61
0.71
0.78
0.47
0.60
0.70
0.77
10
0.46
0.59
0.69
11
0.45
0.57
0.69
12
0.43
0.56
0.68
Derating Factors
Table 10: Correction Factors for Groups of Three Phase Circuits of Single Core Cables Laid Direct
in the Ground
Spacing Between Cable Centers
Number of Cables in Group
Touching
200
400
600
800
0.73
0.83
0.88
0.90
0.92
0.60
0.73
0.79
0.83
0.86
0.54
0.68
0.75
0.80
0.84
0.49
0.63
0.72
0.78
0.82
0.46
0.61
0.70
0.76
0.81
0.43
0.58
0.68
0.75
0.80
0.41
0.57
0.67
0.74
0.39
0.55
0.66
0.73
10
0.37
0.54
0.65
11
0.36
0.53
0.64
12
0.35
0.52
0.64
Table 11: Correction Factors for Groups of Three Core Cables in Single way Ducts in Horizontal
Formation.
Spacing Between Cable Centers
Number of Cables in Group
Touching
200
400
600
800
0.85
0.88
0.92
0.94
0.95
0.75
0.80
0.85
0.88
0.91
0.69
0.75
0.82
0.86
0.89
0.65
0.72
0.79
0.84
0.87
0.62
0.69
0.77
0.83
0.87
0.59
0.67
0.76
0.82
0.86
0.57
0.65
0.75
0.81
0.55
0.64
0.74
0.80
10
0.54
0.63
0.73
11
0.52
0.62
0.73
12
0.51
0.61
0.72
65
Derating Factors
Table 12: Correction Factors for Groups for Three Phase Circuits of Single Core Cables in Single
Way Ducts
200
400
600
800
0.78
0.85
0.89
0.91
0.93
0.66
0.75
0.81
0.85
0.88
0.59
0.70
0.77
0.82
0.86
0.55
0.66
0.74
0.80
0.84
0.51
0.64
0.72
.78
0.83
0.48
0.61
0.71
0.77
0.82
0.46
0.60
0.70
0.76
0.44
0.58
0.69
0.76
10
0.43
0.57
0.68
11
0.42
0.56
0.67
12
0.40
0.55
0.67
Table 13: Max. Short Circuit Current For Copper Conductors at 1 Sec.
Construction
XLPE Cable
Cond.
Max Temp
Normal
Operation
Short Circuit
Conductor
90
250
Max Temp
80
70
65
60
50
40
30
20
170
176
181
149
154
157
159
165
Table 14: Max. Short Circuit Current For Aluminium Conductors at 1 Sec.
Construction
XLPE Cable
Cond.
Max Temp
Normal
Operation
Short Circuit
Conductor
90
250
Max Temp
80
70
65
60
50
40
30
20
116
120
98
102
104
105
109
113
Isc for time (t) can be obtained from the following formula:
Isc (t) = Isc (1)
t
Where: Isc (1) = short circuit current at 1 sec.
66
Table 15: Reduction Factors for groups of more than one multi-core cable in air
To be applied to the current-carrying capacity for one multi-core cable in free air
67
Table 16: Reduction Factors for groups of more than one circuit of single-core cable (Note 2)
To be applied to the current-carrying capacity for one circuit of single-core cable in free air
68
69
70
Permissible short circuit current for Various cross section of round wire screens
71
72
15) Layer of sand 10 cm approx. under and over the cable shall be furnished. Then a layer of brick
or tile shall be placed for warning, mechanical protection, load distribution.
16) When pulling the cable inside conduit/pipe the inner diameter of the pipe shall be min. 1.5 times
the cable diameter.
17) It is preferable to use pipe with funnel shape, cable should not rest at the sharp edges of the
pipe, special care should be taken such that stones and other objects are not dragged with the
cable inside the pipe.
18) Pipe should be cleaned before pulling operation.
19) Special lubricant can be used to minimize the cable friction with the pipe wall.
20) When cables of different voltages are laid together it is preferable that the higher voltage to be
laid down, then the lower voltage and then the lower voltage. High voltage cables should be
separated by a covering slab from the other cables.
21) For direct buried installations, rollers at a distance of around 1 2 meters are to be used based
on cable weight, in any case cable should not touch the ground. It is recommended to use
motorized rollers at the distance of 20 M to 30 M with proper monitoring. These are beside
the normal cable rollers specially near bending points so that the cable pulling force shall be
distributed evenly over the complete length of the cable. This kind of pulling is recommended
when there are many bends in the cable route.
22) For cable pulling, cable stocking can be used for Steel Wire armoured cables while for nonarmoured cables Steel Tape armoured cables pulling head is preferred. Special care shall be
taken to seal the cable head avoiding water penetration during pulling.
23) It is not advisable to use cable pulling stocking when the ambient temperature is around 450C or
more and under direct sunlight as the outer jacket might soften and get damaged.
24) It is recommended to use pulling head when the cable is pulled inside pipes or conduits as
slipping of stocking might occur inside the pie or conduit.
25) While pulling, continuous monitoring of the tensile force should be maintained.
26) At the bend, cable shall be guided by rollers. Direct touch with trench wall shall be completely
avoided.
27) Immediately after cutting, the cable ends must be suitably sealed so that there is no ingress of
moisture.
28) It is recommended to inspect the cable after laying to ensure that the cable has not been
damaged.
29) Cable after laying should not be straightened but left with slight meandering to allow longitudinal
expansion and contraction during thermal cycling.
30) When the ground water table is high it is advisable to use special cable construction with
longitudinal and radial watertight characteristics.
73
74
Minimum Radius
During Laying
Single Core:
(a) Unarmoured
(b) Armoured (PVC)
(c) Armoured (PE)
20 X D
15 X D
20 X D
15 X D
12 X D
15 X D
Three Core:
(d) Unarmoured
(e) Armoured (PVC)
(f) Armoured (PE)
15 X D
12 X D
15 X D
12 X D
10 X D
12 X D
Type of Cable
Un-armoured
Cables*
Armoured cables
Formula
P=.A
P=
.A
Factor
= 50 N/mm
(Copper Conductor)
= 30 N/mm
(Aluminium Conductor)
= 50 N/mm
(Copper Conductor)
= 30 N/mm
(Aluminium Conductor)
P = k . d
k = 9 N/mm
*When pulling 3 single core cables simultaneously with a common pulling stocking, the same maximum pulling force applies, whereas the pulling force
3 laid-up single core cables is 3 times that of a single core and for 3 non-laid-up single core cables is 2 times that of a single core.
Where:
P
A
d
k
=
=
=
=
=
Pull in Newtons
Total cross sectional area in mm of all conductors (but not screen or concentric conductor)
Outside diameter of the cable in mm
Permissible tensile stress of conductor in N/mm
Empirically derived factor in N/mm
Table 19: Permissible Radial Load Values
Permissible radial loads for pulling through plastic pipes
Non-Armoured Cables
10000 N/m
Cables with Single Armour
15000 N/m
Maximum permissible loads on rollers fitted on bends
Non-Armoured Cables
1500 N/m
Cables with Single Armour
2500 N/m
When using roller chain (5 rollers / m)
Non-Armoured Cables
7500 N/m
Cables with Single Armour
12500 N/m
When only 3 rollers / m are fitted
Non-Armoured Cables
4500 N/m
Cables with Single Armour
7500 N/m
75