Australian Journal of Basic and Applied Sciences, 5(12): 379-396, 2011 ISSN 1991-8178

Dynamic Voltage Restorer Application for Power Quality Improvement in Electrical Distribution System: An Overview
1 1

Rosli Omar, 2N.A. Rahim and 3Marizan Sulaiman

Faculty of Electrical, University Teknikal Malaysia Melaka, Karung Berkunci 1752, Pejabat Pos Durian Tunggal, 76109, Durian Tunggal Melaka. 2 Centre of Research for Power Electronics,Drives, Automation and Control, University of Malaya,50603 Kuala Lumpur, Malaysia. 3 Faculty of Electrical, University Teknikal Malaysia Melaka, Karung Berkunci 1752, Pejabat Pos Durian Tunggal, 76109, Durian Tunggal Melaka.
Abstract: Dynamic Voltage Restorer (DVR) is a custom power device that is used to improve voltage disturbances in electrical distribution system. The components of the DVR consist of voltage source inverter (VSI), injection transformers, passive filters and energy storage. The main function of the DVR is used to inject three phase voltage in series and in synchronism with the grid voltages in order to compensate voltage disturbances. The Development of (DVR) has been proposed by many researchers. This paper presents a review of the researches on the DVR application for power quality Improvement in electrical distribution network. The types of DVR control strategies and its configuration has been discussed and may assist the researchers in this area to develop and proposed their new idea in order to build the prototype and controller. Key words: Dynamic voltage restorer, controller, injection transformer, review, voltage source inverter. INTRODUCTION Recently applications of power electronic controller based on Custom Power Devices (CPD) are widely used in electrical distribution system for power quality improvement. CPD is a powerful tool based on semiconductor switches concept to protect sensitive loads if there is a disturbance from power line (Middlekauff, et al., 1998). Among the several novel CPD, the Dynamic Voltage Restorer (DVR) are now becoming more established in industry to mitigate the impact of voltage disturbances on sensitive loads. (A. Ghosh, et al., 2002; S.S. Choi, et al., 2000). Power quality in the distribution system can be improved by using a custom power device DVR for voltage disturbances such as voltage sags, swells, harmonics, unbalanced voltage and etc (Zhan, et al., 2003).The function of the DVR is a protection device to protect the precision manufacturing process and sophisticate sensitive electronic equipments from the voltage fluctuation and power outages. The DVR has been developed by Westinghouse for advance distribution. The DVR is able to inject a set of three single-phase voltages of an appropriate magnitude and duration in series with the supply voltage in synchronism through injection transformer to restore the power quality (J.G. Nielsen, et al., 2005;D.M. Vilathgamuwa, et al., 2004). The DVR is a series conditioner based on a pulse width modulated voltage source inverter, which is generating or absorbing real or reactive power independently. Voltage sags caused by unsymmetrical line-to-line, line to ground, double-line-to-ground and symmetrical three phase faults is affected to sensitive loads, the DVR injects the independent voltages to restore and maintained sensitive to its nominal value. The injection power of the DVR with zero or minimum power for compensation purposes can be achieved by choosing an appropriate amplitude and phase angle (Li, et al., 2007). 2.1 Dynamic Voltage Restorer (DVR): The conventional circuit configuration of the DVR is shown in Figure 1. Dynamic voltage restorer is a series connected device is used for mitigating voltage disturbances in the distribution system (Lee, et al., 2004). The DVRs can be used and are already in operation (W.E. Brumsickle, et al., 2001). DVR maintains the load voltage at a nominal magnitude and phase by compensating the voltage sag/swell, voltage unbalance and voltage harmonics presented at the point of common coupling (Mahesh, et al., 2008; Jowder, et al., 2009; Ramachandaramurthy, et al., 2004). These systems are able to compensate voltage sags by increasing the appropriate voltages in series with the supply voltage, and therefore avoid a loss of power. In 1994, L.Gyugyi (Patent No. 5329222) proposed an apparatus and a method for dynamic voltage restoration of utility distribution network. This method uses real power in order to inject the faulted supply voltages and is commonly known as the Dynamic Voltage Restorer (Gyugyi, et al., 1994). The DVR should capable to react as fast as possible to
Corresponding Author: Rosli Omar Faculty of Electrical, University Teknikal Malaysia Melaka, Karung, Berkunci 1752, Pejabat Pos Durian Tunggal, 76109, Durian Tunggal Melaka. E-mail: rosliomar@utem.edu.my

379

Aust. J. Basic & Appl. Sci., 5(12): 379-396, 2011

inject the missing voltage to the system due to sensitive loads are very sensitive to voltage variations (Chan, et al., 2006). The DVR is a series conditioner based on a pulse width modulated voltage source inverter, which is

Fig. 1: Conventional Circuit Configuration (Nielsen, et al., 2005). generating or absorbing real or reactive power independently. Voltage sags caused by unsymmetrical line-toline, line to ground, double-line-to-ground and symmetrical three phase faults is affected to sensitive loads, the DVR injects the independent voltages to restore and maintained sensitive to its nominal value. The compensation of harmonics and mitigates voltage transients has been discussed in (Li, et al., 2001). 2.2 The basic components of a DVR: DVR can be applied for medium voltage (Li, et al., 2007; Toodeji, et al., 2009; Meyer, et al., 2008) and in low voltage application (Muni et al., 2004). The DVR components has been discussed in (Zhan, et al., 2002;Chun, et al., 2003; Zhan, et al., 2003). The DVR system consists of two (2) important components namely a power circuit and a control unit. A comprehensive literature survey of DVR including power circuit, control unit and its application in electrical distribution system is discussed. Power circuit of DVR basically consists of a voltage source inverter, a seriesconnected injection transformer, an inverter output passive filter, and an energy storage device that is connected to the dc link (Boonchiam, et al., 2006; Ezoji, et al., 2009; Banaei, et al., 2006; Ghosh, et al., 2002; Nguyen, et al., 2004) as follows. Series Voltage Injection Transformers Energy Storage Passive Filters Voltage Source Inverter (VSI) By Pass Switch Power Circuit of a DVR is shown in Figure 2. In DVR the control circuit is used to derive the parameters (magnitude, frequency, phase shift, etc) of the control signal that has to be injected by the DVR. Based on the control signal, the injected voltage is generated by the switches in the power circuit (Zhan, et al., 2002; Kim, et al., 2005). 2.2.1 Series Voltage Injection Transformers: In a three-phase system, either three single-phase transformer units or one three phase transformer unit can be used for voltage injection purpose (Zhan, et al., 2000).The injection transformer comprises of two side voltages namely the high voltage side and low voltage side. Normally the high voltage side of the injection transformer is connected in series to the distribution system while power circuit of the DVR can be connected at the low voltage side. The basic function of the injection transformer is to increase the voltage supplied by the filtered VSI output to the desired level while isolating the DVR circuit from the distribution network. The transformer winding ratio is pre-determined according to the voltage required in the secondary side of the transformer (generally this is kept equal to the supply voltage to allow the DVR to compensate for full voltage sag (Zhan, et al., 2001). A higher transformer winding ratio will increase the primary side current, which will adversely affect the performance of the power electronic devices connected in the VSI. Three single phase or three-phase voltage injection transformers can be used for a three-phase DVR. In this case the high voltage of the injection transformer is connected to the distribution line and for single phase DVR one single-phase injection transformer can be connected (Zhan, et al., 2001). The single phase transformers can be used to inject the compensating voltages separately when three phase inverter is used. To evaluate the performance of the

380

Aust. J. Basic & Appl. Sci., 5(12): 379-396, 2011

DVR the rating of the injection transformer is an important factor that need to be considered due to the compensation ability of the DVR is totally depend on its ratingThe DVR performance is totally depend on the rating of the injection transformer , since it limits the maximum compensation ability of the DVR (Wang, et al., 2006; Banaei, et al., 2006). In (Loh, et al., 2004; Graovac, et al., 2001) ,discussed multilever inverter topology is used in DVR allowing the direct connection of the DVR to the distribution system without using injection transformer.

Fig. 2: Power Circuit of a DVR. (Chan, et al., 1998) The details explanations of the DVR power circuit components as mentioned earlier can be described as follows:

Fig. 3(a): The three single phase transformer connected in delta/open.

381

Aust. J. Basic & Appl. Sci., 5(12): 379-396, 2011

Fig. 3(b): The three single phase transformer connected in star/open. The three single phase transformers connection used in the three-phase DVR can be configured either in delta/open or star/open connection as shown in Figures 3(a) and (b). In case of unbalance fault in the high voltage side, the zero sequence current flowing almost zero,if the distribution transformer connection in -Y with the grounded neutral. As such connection, the DVR is only mitigate the positive and negative sequence components (Fitzer, et al., 2004). 2.2.2 Energy Storage: The DVR needs real power for compensation purposes during voltage disturbances in the distribution system. In this case the real power of the DVR must be supplied by energy storage when the voltage disturbances exit. The energy storage such as a battery is responsible to supply an energy source in DC form. Energy storage consists of two types form. One using stored energy to supply the delivered power and the other having no significant internal energy storage but instead energy is taken from the faulted grid supply during the sags (John Godsk Nielsen, et al., 2004). A shuntconverter or the rectifier is the main sources of the direct energy storage which is supplied to DVR. Flywheels, batteries, superconducting magnetic energy storage (SMES) and super capacitors can be used as energy storage devices. It is supplies the real power requirements of the system when DVR is used for compensation (Banaei, et al., 2006). The application of the energy storage in DVR is depending on the designed rating required and total cost is also must be considered (H. Awad, et al., 2003). Flywheels, batteries, superconducting magnetic energy storage (SMES) and super capacitors can be used as energy storage devices. It is supplies the real power requirements of the system when DVR is used for compensation lead acid batteries are popular among the others owing to its high response during charging and discharging. But the discharge rate is dependent on the chemical reaction rate of the battery so that the available energy inside the battery is determined by its discharge rate Storage systems with auxiliary supply is used to increase the system performance when the grid of DVR is weak(Ho, et al., 2008; Ramasamy, et al., 2007). Flywheel Energy Storage as a preferred energy storage device, the system utilizes a single AC/AC power converter for the grid interface as opposed to a more conventional AC/DC/AC converter, leading to higher power density and increased system realibility (Wang, et al., 2009; Zhu, et al., 2008; Perez, et al., 2006). However the suitable of the type of energy storage depend on the DVR designed in term rated power and the total cost factor. 2.2.3 LC Filter: Basically filter unit consists of inductor (L) and capacitor (C). The LC filter design procedure is discussed in (Dahono, et al., 1995). In DVR, filters are used to convert the inverted PWM waveform into a sinusoidal waveform. This can be achieved by eliminating the unwanted harmonic components generated by the VSI action. Higher orders harmonic components distort the compensated output voltage (Zhan, et al., 2000). The unnecessary switching harmonics generated by the VSI must be removed from the injected voltage waveform in order to maintain an acceptable Total Harmonics Distortion (THD) level. The switching frequencies of the VSI are usually up to several kHz for medium power level (Zhan, et al., 2001).

382

Aust. J. Basic & Appl. Sci., 5(12): 379-396, 2011

The passive filters can be placed either in the high voltage or in low voltage side winding of the series injection transformer (Agileswari, K., 2005). If the filter is installed at the low voltage side it has the advantage of being closer to the harmonic source thus high order harmonic currents are avoided to penetrate into the series injection transformer. Harmonics currents will circulate into the series injection transformer if the filtering scheme is placed at the high voltage (Newman, et al., 2005; Choi, et al., 2000). 2.2.4 Voltage Source Inverter (VSI): The function of an inverter system in DVR is used to convert the DC voltage supplied by the energy storage device into an AC voltage (Ravi kumar, et al., 2007). Voltage source inverter (VSI) of low voltage and high current with step up injection transformer is used for this purpose in the DVR compensation technique (Perera, et al., 2006). Generally Pulse-Width Modulated Voltage Source Inverter (PWMVSI) is used transformer is used. Thus a VSI with a low voltage rating is sufficient (Zhan, et al., 2001). There are two basic three phase inverter topologies, the popular two-level inverter as shown in Figure 3.1 and the multilever inverter as shown in Figure 3.2 (S.R. Ashcraft, et al., 1999), multilevel inverters have recently emerged as an attractive alternative to PWM schemes so that the losses associated with fast switching can be eliminated (S.R. Ashcraft, et al., 1999). The implementation of the PWM in the two level inverter is simpler and its cost is cheaper than a multilevel inverter.

Fig. 3.1: Two level switch mode inverter (Ashcraft, et al., 1999).

Fig. 3.2: Multilevel inverter (Loh et al., 2004; Ashcraft, et al., 1999).

383

Aust. J. Basic & Appl. Sci., 5(12): 379-396, 2011

2.2.5 By Pass Switch: Fault current causes by faults in the downstream will flow through the inverter circuit of the DVR. Therefore to avoid high currents flowing to the inverter, a protection device namely by-pass (crowbar circuit) switch is used, which is incorporated to by-pass the inverter circuit. Normally the by-pass switch will be in active mode and senses the current flowing in the distribution circuit and if the current flowing over than the inverter current rating limit, the circuit bypasses the DVR circuit components in order to protect the inverter from over currents. The bypass switch will become in inactive when the source current is in rated value or in normal condition. 3. Operation of the DVR: A typical DVR (Nielsen, et al., 2005) as shown in Figure 1 is used for voltage compensation in the distribution line. The operation of the DVR can be categorized into three operation mode as follows; Protection mode Standby mode and Injection mode In protection mode scheme, the bypass switch can be used as a protection device to protect DVR from the over current in the load side due to short circuit on the load or large inrush currents (Ramachandaramurthy, et al., 2004). The DVR can be protected by the action of the bypass switches by supplying another path for current as shown in Figure 3.3(a)

Fig. 3.3(a): The aspect of power switches. In standby mode (VDVR = 0), as shown in Figure 3.3(b) the injection transformers low voltage winding is shorted through the inverter. No switching of semiconductors occurs in this mode of operation because the individual inverter legs are triggered such as to establish a short-circuit path for the transformer connection. Therefore, only the comparatively low conduction losses of the semiconductors in this current loop contribute to the losses.The DVR will be most of the time in this mode. In (Jimichi, et al., 2008) discussed the operation of DVR during stanby mode,two upper IGBTs in each phase of the inverter remains turned off while the two lower IGBTs turned on. A short circuit across the secondary (inverter side) windings of the series transformer through LF is obtained eliminating the use of bypass switches. The DVR goes into injection mode (VDVR > 0) as soon as the sag is detected (Fitzer, et al., 2004). Three single-phase ac voltages are injected in series with required magnitude, phase and wave shape for compensation, (Nielsen, et al., 2004). The types of voltage sags, load conditions and power rating of DVR will determine the possibility of compensating voltage sag. The DVR should ensure the unchanged load voltage with minimum energy dissipation for injection due to the high cost of capacitors. The available voltage injection strategies are pre-sag, phase advance, voltage tolerance and in phase method (Ramachandaramurthy, et al., 2004).

384

Aust. J. Basic & Appl. Sci., 5(12): 379-396, 2011

Fig. 3.3(b): The View of Standby Mode. 3.1 The DVR Location in the Distribution System:

Fig. 3.4: Single-phase representation model of the DVR . Figure 3.4 represents a single phase model of the DVR. The DVR can be described as an ideal voltage source comprises of the reactive element XDVR in the injection transformer and line filter, and the value of the RDVR show the losses in the DVR. The impedance size of the DVR is related to the voltage and the power of the DVR. The DVRs can be placed either at the Medium voltage (MV) or Low voltage (LV) level. In this thesis only discusses the proposed design of the DVR in low voltage distribution system. In both systems the main purpose is to inject a synchronous voltages during faults. A main different between a LV connection and a MV connection is the flow of zero sequences currents and the generation of zero sequence voltages. In the four wire system the DVR must secure a low impendance for zero sequence currents and the zero sequence must either flow in the power inverter or in a delta winding of the injection transformer (Nielsen, et al., 2000). Figure 3.5 (a) and (b) show the typical location of the DVR in medium and low voltage level. Medium voltage comprises of a three wire while in Low Voltage four wire system is used.

385

Aust. J. Basic & Appl. Sci., 5(12): 379-396, 2011

Fig. 3.5: Two type of the DVR location, (a) Medium voltage three wire (b) Low voltage four wire.

Fig. 3.6: Location of the DVR at the low voltage distribution system (Nelson, et al., 2005). DVR application at low voltage distribution system as shown in Figure 3.5(b) has some advantages (Nielsen, et al., 2005) as follows; The DVR can be targeted more specifically at voltage sags sensitive loads

386

Aust. J. Basic & Appl. Sci., 5(12): 379-396, 2011

A majority of electric consumers have only access to the low voltage level and the DVR can both be placed by the customer or utility. The short-circuit level is significantly decreased by the distribution transformer and the DVR is easier to protect. Figure 3.6 represents the in intended location for the Low Voltage DVR four wires which is applied in the distribution system with 415 V line voltages. The basic of the Low voltage DVR is connected to the two level inverter with the main DVR parameters. 3.2 DVRs Topologies System in Distribution System: As mentioned earlier the function of a DVR is maintaining the voltage supply at the load to its nominal value. There are so many DVRs topologies proposed by the researchers. In (Nielsen, et al., 2005) discussed two types of DVR topologies system comprising of no energy storage and with energy storage. Normally during disturbances in a network, the DVR injects an appropriate voltage to recover the voltage at the load. In this situation the DVR need to have exchanges active and reactive power with the surrounding system. Figure 3.7 shows the system topologies for DVRs consists of two types topologies system, namely no energy storage and with energy storage.

Fig. 3.7: System Topologies For DVRs. 3.2.1 DVR Topologies with no Energy Storage: Topologies with no Energy storage can be divided into two systems configurations which are system 1 and system 2. The different between System 1 and System 2 in DVR topologies with no energy storage is that, in system 1 the energy source is from the incoming supply through a passive shunt converter connected to the supply side as shown in Figure 3.7(a) means that the energy is taken from the grid connected side through a passive shunt converter connected to the source side. While in system 2 (Woodley, et al., 2000) energy is taken from the grid connected side through a passive shunt converter connected to the load side as shown in Figure 3.7(b). DVR topologies with no energy storage use the fact that a significant part of the source voltage continuous maintain during the disturbances, and this source can be used to provide the boost energy required to maintain full power at its nominal voltage.

387

Aust. J. Basic & Appl. Sci., 5(12): 379-396, 2011

Fig. 3.7(a): DVR with no energy storage and supply-side connected converter.

Fig. 3.7(b): DVR with energy storage and load-side-connected shunt converter. 3.2.2 DVR Topologies With Energy Storage: The stored energy storage supplies the real power requirements of the system when DVR is used for compensation process when there is a disturbance in the distribution system. Flywheels, lead acid batteries, superconducting Magnetic Energy Storage (SMES) and supercapacitor can be used as energy storage devices. In voltage disturbances mitigation such as voltage sags the performance of the DVR can be improved by using energy storage even though storing electrical energy is expensive. System 3 as shown in Figure 3.8(a) is the topologies with energy storage where the variable DC-Link Voltage is used. The energy is stored in the DCLink Capacitor. The type of this topology is considered as a simple topology and it can be running with a variable dc-link voltage. The energy storage required to activate the DVR is proportional to the square of the rated dc-link voltage (Nielsen et al., 2005). In system 4 Constant DC-Link Voltage is applied to this topology, as shown in Figure 3.8(b). Energy storage such as SMES, batteries or supercapacitors can be used as a direct energy storage which is applied in DVR. The large energy storage is then transferred to the smaller rated dc-link storage using an inverter during the disturbances in the network.

388

Aust. J. Basic & Appl. Sci., 5(12): 379-396, 2011

Fig. 3.8(a): DVR with energy storage and with variable dc-link voltage.

Fig. 3.8(b): DVR with energy storage and with constant dc-link voltage. 3.3 Type of Control Strategies in DVR: In the literature survey (Chan, et al., 2006;Ezoji, et al., 2010; Marei, et al., 2007; Li, et al., 2007; Carl, et al., 2007) shows several techniques to implement and control philosophy of the DVR for power quality improvement in the distribution system. Most of the reported DVR systems are equipped with a control system that is configure to mitigate voltage sags/swells. Other DVR applications that include power flow control, reactive power compensation, as well as limited responses to power quality problems. The aim of the control scheme is to maintain constant voltage magnitude at the point where a sensitive load is connected under system disturbances. The control system only measures the r.m.s voltage at the load point, i.e., no reactive power measurements are required. The control of DVR is very important and it involves detection of voltage sags (start, end and depth of the voltage sag) by appropriate detection algorithms which work in real time. The voltage sags can last from a few milliseconds to a few cycles, with typical depths ranging from 0.9 p.u to 0.5 pu of a 1-pu nominal (Zhan, et al., 2001; Banaei, et al., 2006). Inverter is an important component of DVR. The performance of the DVR is directly affect to the control strategy of inverter. There have many studied been

389

Aust. J. Basic & Appl. Sci., 5(12): 379-396, 2011

done by the researchers about the inverter control strategy for the DVR implementation. The inverter control strategies used in DVR recently is shown in Figure.3.9.

Fig. 3.9: Inverter control strategy of DVR. The inverter control strategy comprises of two types of control as following: i. Linear Control and ii. Non Linear Control iii. Linear Control Linear control is considered as a common method of DVR control. Amongs the linear control been used in DVR are feed forward control, feedback control and composite control. Feed forward control is a simple method of DVR (Zhang, et al., 2000; Woodley, et al.,1999; Chi-Jen, et al., 2003; Han, et al., 2002). The feed forward control technique does not sense the load voltage and it calculates the injected voltage based on the difference between the pre-sag and during-sag voltages. The feedback control strategy measures the load and the difference between the voltage reference of the load and actual load voltage is injected voltage required (Huang, et al., 2002). The feedback control methods based on state space systems, which can be set up closed-loop poles in order to make faster time response is also discussed in (Wenyong, et al., 2007). Both the feed forward and the feedback control strategy may be implemented by scalar or vector control techniques. Double-loop feedback control method with outer ring voltage and inner current ring have been discussed in (Vilathgamuwa, et al., 2002; Xueson, et al., 2007; Nielsenj, et al., 2004; Hui, et al., 2004). Composite control strategy is a control method with grid voltage feed forward and load side voltage feedback, which has the strengths of feed-forward and feedback control strategy, so it can improve voltage compensation effect. An improved control method has been proposed in reference (Meng, et al., 2005). If the feedback control in the composite control is designed to double-loop, it can improve system stability, system performance and the adaptability of dynamic load. The combination with feed forward control can improve the system dynamic response rate, shortening the time of compensation significantly (Vilathgamuwa, et al., 2002). The control method with inductor current feedback and feed forward load current is designed without series transformers thus the size and cost of a DVR can be reduced is implemented in (Sngek, et al., 2004). i. Non Linear Control: Due to the usage of power semiconductor switches in the VSI, then the DVR is categorized as non-linear device. In case of when the system is unstable, the model developed does not explicitly control target so all the linear control methods cannot work properly due to their limitation.

390

Aust. J. Basic & Appl. Sci., 5(12): 379-396, 2011

(a): Artifical Neural network Control (ANN): One of the non-linear method control is Artificial neural network control (ANN) and it equipped with adaptive and self organization capacity. ANN control can monitor the non linear relationship based on input and output without the detail mathematical model. Normally ANN control can be classified into feed forward neural networks, feedback neural network, local approximation neural networks and fuzzy neural network based on structure. Control system using ANN control is implemented in (Jurado, et al., 2004). (b): Fuzzy Control: Fuzzy logic control of DVR for voltage injection is reported in (Bayindir, et al., 2007). Its design philosophy deviates from all the previous methods by accommodating expert knowledge in controller design. It is derived from fuzzy set theory introduced by (Zadeh, 1965). FL controllers are an attractive choice when precise mathematical formulations are not possible. In (Jurado, et al., 2004) discussed about the implementation of FL in DVR. The advantages of this controller is capability to reduced the error and transient overshoot of PWM. (c) Space Vector PWM (SVPWM) control: Space Vector PWM (SVPWM) control strategy used in AC motor variable speed drives by the Japanese scholars in the early 1980s. The main idea is to adopt a voltage inverter space vector of the switch to get quasicircular rotating magnetic field instead of the original SPWM, so better performance of the exchange is gained in low switching frequency conditions. A double-loop vector control has been proposed in reference (Awad, et al., 2004). To simplify the calculation, the theory PQR instantaneous power directly to the geostationary coordinate system to transform the three-phase voltage PQR coordinates of the three direct traffic has been proposed in reference (Lee, et al., 2004). Besides the types of these control, there is also available control for single phase sag detection methods used in DVR. Soft Phase Locked Loop (PLL) (Hangzhou, et al., 2008). Mathematical Morphology theory based low-pass filter (Zhou et al., 2008), Instantaneous Value Comparison Method (Bae, et al., 2007) are commonly used control for single phase voltage sag detection in the distribution system. 3.3 The Concept of Compensation Techniques in DVR: Figure 3.10 shows the concept of compensation techniques which is applied in DVR, can be divided into two categories as follows; i) The reactive power compensation ii) Active and reactive power compensation

Fig. 3.10: The Compensation Technique of A DVR (H. Awad, et al., 2003; Nielsen, et al., 2001) The methods for injection of missing voltage can be elaborated into pre sag compensation, in-phase compensation and phase advance or minimum energy compensation (Chung, et al., 2007; Ezoji, et al., 2009). The details of the of the pre-sag and in-phase compensation can be found in (Nielsen, et al., 2001) whereas minimum energy compensation is discussed widely in (Vilathgamuwa, et al., 2003).

391

Aust. J. Basic & Appl. Sci., 5(12): 379-396, 2011

3.3.1 Pre-Sag Compensation: In Pre-Sag compensation, it is important for both magnitude and the phase angle to be compensated. The different between the pre-sag and during the sag voltage are detected by the DVR and it injects the different voltage, Therefore, the amplitude and the phase of the voltage before the sag has to be exactly restored (Zhan, et al., 2002). Figure 3.11 illustrates the pre-sag compensation technique showing before and after the voltage sags.

. Fig. 3.11: Pre-sag compensation showing before and after the voltage sag. 3.3.2 In- Phase Compensation: In-Phase Compensation technique,the injection voltage is in phase with the source voltage (Margo, et al., 2007). When the source voltage is drop due to sagging problems in the network the injection voltage produced by the Voltage Source Inverter (VSI) will injects the missing voltage based on the drop voltage magnitude. This method can be shown in Figure 3.12.

Fig. 3.12: The diagram of In-Phase Compensation Technique. 3.3.3 Reactive Power Compensation: In the reactive power compensation only small energy storage is required in the other word this concept does not require any active power. The phasor diagram of the reactive power compensation is illustrated in Figure 3.13 (C.S. Chang, et al., 2004) in this compensation method the DVR providing reactive power compensation does not require any active power as it can be observed in the figure, the injected voltage is quardrature with the load current.

392

Aust. J. Basic & Appl. Sci., 5(12): 379-396, 2011

Fig. 3.13: Reactive Power Compensation Technique. Conclusion: A comprehensive study of a DVR as a powerful custom power device has been presented in this paper. The main function of a DVR is the protection of sensitive loads from voltage disturbances coming from network The types of voltage disturbances such as voltage sags or swells, transients, unbalanced voltage and harmonics. The existing topologies and its controllers applied in DVR have been elaborated with detail. This study also give useful knowledge for the researchers to develop a new design of DVR for voltage disturbances in electrical system. From the literature survey of DVR applications we can concluded that the trends of DVR through the years are still assumed as a good area . ACKNOWLEDGEMENT The authors wish to thank University of Malaya and Universiti Teknikal Malaysia Malacca for providing grant under grant PS002/2009B for this project. REFERENCES Ramasamy, A., V.K. Ramachandaramurthy, R.K. Iyer, Z.L. Liu, 2007. Control of dynamic voltage restorer using TMS320F2812, Electrical Power Quality and Utilisation Conference, pp: 1-6. Agileswari, K. Ramasamy, Rengan Krishnan Iyer, Dr. R.N. Mukerjee, Dr. Vigna K. Ramachandramurthy, 2005. Dynamic Voltage Restorer for voltage sag compensation, IEEE PEDS, pp: 1289-1293. Ghosh, A. and G. Ledwich, 2002. Compensation of Distribution System Voltage Using DVR, IEEE Trans onPower Delivery, 17(4): 1030-1036. Muni, B.P., S. Venkateshwarlu, H. V. Makthal, P. J. Hyderabad, 2004. Review of dynamic voltage restorer for power quality improvement, IEEE Industrial Electronics Society, 1: 749-754. Wang, B., G. Venkataramanan, and M. Illindala, 2006. Operation and control of a dynamic voltage restorer using transformer coupled H-bridge converters, IEEE Trans. Power Electron., 21(4): 1053-1061. Li, B.H., S.S. Choi and D.M.Vilathgamuwa, 2001. Design consideration of the line side filter used in the dynamic voltage restorer, IEE Proc. -Generation Transmission Distribution, 148(1). Bae, B.Y., D.K. Lee, D.Y. Lee, B.M. Han, 2007. Development of high-performance single-phase ineinteractive dynamic voltage restorer, Universities Power Engineering Conf., pp: 1-6. Zhan, C., V.K. Ramachandaramurthy, A. Arulampalam, C. Fitzzer, M. Barnes, N. Jenkins, 2002. Control of a battery supported dynamic voltage restorer, IEE proceedings on Transmission and Distribution, 149(5): 533-542.

393

Aust. J. Basic & Appl. Sci., 5(12): 379-396, 2011

Meyer, C., R.W. De Doncker, Y.W. Li, F. Blaabjerg, 2008. Optimized control strategy for a medium voltage DVR - Theoretical investigations and experimental results, Power Electronics, IEEE Transactions, 23: 2746-2754. Zhan, C., A. Arulampalam and N. Jenkins, 2003. Four-wire dynamic voltage restorer based on a threedimensional voltage space vector PWM algorithm, IEEE Trans. Power Electron., 18(4): 1093-1102. Zhan, C., M. Barnes, V.K. Ramachandarmurthy, N. Jenkins, 2000. Dynamic Voltage Restorer with a battery Energy Storage for Voltage Dip Mitigation, Eighth International Conference on Power Electronics and Variable Speed Drives, 2000, 18-19., pp: 360-365. Zhan, C., V.K. Ramachandaramurthy, A.Arulampalam, C.Fitzer, S.Kromlidis, M.Barnes, N.Jenkins, 2001. Dynamic voltage restorer based on Voltage space vector PWM control, IEEE transactions on Industry applications, 37(6): 1855-1863. Fitzer, C., M. Barnes, P. Green, 2004. Voltage Sag Detection Technique for a Dynamic Voltage Restorer, IEEE Trans. On Industry Application, 40(1). Hangzhou, C., 2008. Research on the SPLL based single phase voltage sag detection technique, Proceedings of the 7 International Conference on Instrumentation, Measurement, Circuits and Systems, pp: 6265. Chang, C.S., Zhemin Yu, 2004. Distributed Mitigation of Voltage Sag by Optimal Placement of Series Compensation Devices Based on Stochastic Assessment, IEEE transactions on Power Systems, 19(2): 788-795. Ho, C.N., H.S.H. Chung, K.T.K. Au, 2008. Design and implementation of a fast dynamic control scheme for capacitor supported dynamic voltage restorers, Power Electronics, IEEE Transactions, 23: 237-251. Graovac, D., V. Katic, A. Rufer, J. Knezevic, 2001. Unified power quality conditioner based on currentsource converter topology, European Conf. on Power Electr. and Applications, pp: 1-9. Mahimda Vilathgamuwa, D., H.M. Wijekoon, 2002. Control and analysis of a new dynamic voltage restorer circuit topology for mitigation long duration voltage sags, IEEE Transactions on Power Electronics, pp: 1105-1112. Vilathgamuwa, D.M., A.A.D.R. Perera, S.S. Choi, 2003. Voltage sag compensation with energy optimized dynamic voltage restorer, Power Delivery, IEEE Transactions, 18: 928-936. Jowder, F.A.L., 2009. Design and analysis of dynamic voltage restorer for deep voltage sag and harmonic compensation, Generation, Transmission & Distribution, 3: 547-560. Nielsenj, G., M. Newman and H. Nielsen, 2004. "Control and testing of a dynamic voltage restorer (DVR) at medium voltage level, " IEEE Trans on Power Electronics, 19(3): 806-813. Li, G.J., X.P. Zhang, S.S. Choi, T.T. Lie and Y.Z. Sum, 2007. Control strategy for dynamic voltage restorers to achieve minimum power injection without introducing sudden phase shiftIET Generation, Transmission and Distribution, 1(5): 847-853. Awad, H., F. Blaabjerg, 2004. Transient Performance Improvement of Static Series Compensator by Double Vector Control, Nineteenth Annual IEEE, Applied Power Electronics Conference and Exposition, 2004, APEC 2004, 1: 607-613. Awad, H., J. Svensson, M.H.J. Bollen, 2003. Static Series Compensator for Voltage Dips Mitigation,Power Tech Conference Proceddings,2003 IEEE Bolongna, pp: 23-28. Toodeji, H., S.H. Fathi, 2009. Cost reduction and control system improvement in electrical arc furnace using DVR, Industrial Electronics and Applications, IEEE Conference, pp: 211-215. Ezoji, H., A. Sheikholeslami, M.Tabasi and M.M. Saeednia, 2009. Simulation of Dynamic Voltage Restorer Using Hysteresis Voltage Control, European Journal of Scientific Research (EJSR), 27(1):152-166. Huang Han, Yang Chao, and Han Yingduo, 2002. "The simulation and experiment of dynamic voltage restorer control strategy, " Power System Technology, 26(1). Zhou, H., J. Zhou, Z.P.Qi, 2008. Fast voltage detection for a single-phase dynamic voltage restorer (DVR) using morphological low-pass filters , The Third International Conference on Electric Utility Deregulation and Restructuring and Power Technologies, pp: 2042-2046. Nielsen, J.G., F. Blaabjerg, N. Mohan, 2001. Control strategies for dynamic voltage restorer compensating voltage sags with phase jump", IEEE Applied Power Electronics Conference and Exposition, 2: 1267-1273. Nielsen, J.G., M. Newman, H. Nielsen, F. Blaabjerg, 2004. Control and testing of a dynamic voltage restorer (DVR) at medium voltage level , Power Electronics, IEEE Transactions, 19: 806-813. Nielsen, J.G., F. Blaabjerg. 2005. A detailed Comparison of system Topologies for Dynamic Voltage Restorer, IEEE Transactions on Industry Application, Vol. 41, Issue :5, Sept-Oct., pp: 1272-1280. John Godsk Nielsen, Michael Newman, Hans Nielsen, Frede Blaabjerg, 2004. Control and testing of a Dynamic Voltage Restorer at medium voltage level,IEEE transactions on Power Electronics, 19(3): 806-813. Zhu, J., X. Jiang, L. Huang, 2008. A novel dynamicvoltage restorer with flywheel energy storagesystem, Electrical Machines and Systems,International Conference, pp: 1995-1999. Perez, J., V. Cardenas, L. Moran, C. Nunez, 2006. Single phase AC-AC converter operating as a dynamic voltage restorer (DVR), IEEE Industrial Electronics Conference, pp: 1938-1943.

394

Aust. J. Basic & Appl. Sci., 5(12): 379-396, 2011

Jurado, F., M. Valverde, J. Carpi, 2003. Voltage Sag Correction by Dynamic Voltage Restorer Based on Fuzzy Logic Control, May, mai IEEE, pp: 421-424. Kasuni Perera, Daniel Salomon son and Arulampaiam, Atputharajah, Sanath Alahakoon, 2006. Automated Control Technique for A Single Phase Dynamic Voltage Restorer IEEE. Chan, K., A.Kara, D. Westermann, 1998. Integrated Gate Commutated Thyristor based Dynamic Voltage Restorer, International Conference on Power System technology Proceedings of POWERCON 98 Beijing China, 1: 635-638. Bayindir, K.., A. Teke, M. Tumay, 2007. A robust control of dynamic voltage restorer using fuzzy logic, Electrical Machines and Power Electronics, International Aegean Conf., pp: 55-60. Zadeh, L.A., 1965. "Fuzzy sets. Inform Contr., " pp: 338-353. Gyugyi, L., C.D. Schauder, C.W. Edwards, M.Sarkozi, 1994. Apparatus and method for dynamic voltage restoration of utility distribution networks,U.S. Patent, (5): 329-222. Banaei, M.R., S.H. Hosseini, S. Khanmohamadi and G.B. Gharehpetian, 2006. Verification of a new energy control strategy for dynamic voltage restorer by simulation, ELSEVIER Simulation Modeling Practice and Theory, 14: 113-125. Newman, M.J., D.G. Holmes, J.G. Nielsen, F. Blaabjerg, 2005. A dynamic voltage restorer (DVR) with selective harmonic compensation at medium voltage level, Industry Applications, IEEE Transactions, 41: 1744-1753. Vilathgamuwa, M., A.AD. Ranjithperera and S.S. Choi, 2002. "Performance improvement of the dynamic voltage restorer with closed-loop load voltage and current-mode control, " Power Electronics, 17(9): 824-834. Marei, M.I., E.F. El-Saadany and M.M. Salama, 2007. A New Approach to Control DVR Based on Symmetrical Components Estimation. IEEE on Transactions Power Delivery,22(4): 2017-2024. Woodley, N.H., L. Morgan, A. Sundaram, 1999. Experience with an Inverter-Based Dynamic Voltage Restorer, IEEE Transactions on Power Delivery, 14: 1181-1186. Chan, P.K.W., K.K.S. Leung, H.S.H. Chung, S.Y.R. Hui, 2006. Boundary controller for dynamic voltage restorers to achieve fast dynamic response, Applied Power Electronics Conference and Exposition, pp: 6. Boonchiam, P. and N. Mithulananthan, 2006. Dynamic Control Strategy in Medium Voltage DVR for Mitigating Voltage Sags/Swells, International Conference on Power System Technology, pp: 1-5. Nguyen, P.T.,T.K. Saha, 2004. Dynamic voltage restorer against balanced and unbalanced voltage sags: modelling and simulation, Power Engineering Society General Meeting, IEEE, (1): 639-644. Loh, P.C., D.M. Vilathgamuwa, S.K. Tang,H.L.Long, 2004. Multilevel dynamic voltage restorer.IEEE Power Electronic Letters, 2: 125-130. Dahono, P.A., A. Purwadi and Quamaruzzaman, 1995. An LC filter design method for single-phase PWM inverters, IEEE International Conf. on Power Electronics and Drive Systems, 2: 571-576. Margo, P., M.P. Heri, M. Ashari, T. Hiyama, 2007. Balanced voltage sag correction using dynamic voltage restorer based fuzzy polar controller, Proceedings of the Second International Conference on Innovative Computing, Information and Control. Lee, S.J., H. Kim, and S.K. Sul, 2004. "A novel control algorithm for static series compensators by use of PQR instantaneous power theory, " IEEE Trans on Power Electronics, 19(3): 814-827. Middlekauff, S.W., E.R. Collins Jr., 1998. System and Customer Impact Considerations for Series Custom Power Devices, IEEE Transactions on Power Delivery, 13(1): 278-282. Choi, S.S., B.H. Li, D.M. Vilathgamuwa, 2000. A Comparative Study of Inverter and Line Side Filtering Schemes in The Dynamic Voltage Restorer, IEEE Power Engineering Society Winter meeting, 2000, 4: 23-27, 2967-2972. Choi, S.S., B.H. Li, D.M. Vilathgamuwa, 2000. A comparative study of inverter- and line-side filtering schemes in the dynamic voltage restorer, IEEE Power Engineering Society Winter Meeting, 4: 2967-2972. Ravi Kumar, S.V., S. Siva Nagaraju, 2007. Simulation of D-Statcom and DVR in Power Systems ARPN Journal of Engineering and Applied Sciences, 2(3). Ashcraft, S.R., S.M. Halpin, 1996. DC-AC inverters for static condenser and dynamic voltage restorer applications, Proceedings of the Twenty-Eighth South-Eastern Symposium, 31 Mar-2 April, pp: 215-219. Sngek, S.S. Choi, and M. Vilathgamuwa, 2004. "Analysis of series compensation and DC-link voltage controls of a transformer less self-charging dynamic voltage restorer, " IEEE Trans on Power Delivery, 19(3): 1511-1518. Mahesh, S.S., M.K. Mishra, B.K. Kumar, V. Jayashankar, 2008. Rating and design issues of DVR injection transformer, Applied Power Electronics Conference and Exposition, pp: 449-455. Jimichi, T., H. Fujita, H. Akagi, 2008. Design and experimentation of a dynamic voltage restorer capable of significantly reducing an energy-storage element, Industry Applications, IEEE Transactions, 44: 817-825. Tan Meng, Wang Qiubao, and Yang Rengang. 2005. "Dynamic voltage restorer based on three singlephases, " Journal of ShengYang Agricultural University, 36(6): 679-682.

395

Aust. J. Basic & Appl. Sci., 5(12): 379-396, 2011

Ramachandaramurthy, V.K., A. Arulampalam, C. Fitzer, C. Zhan, M. Barnes and N. Jenkins, 2004 Supervisory control of dynamic voltage restorers IEE Proc.- Gener. Transm. Distrib., 151(4): 509-516. Li, Y.W., M. Vilathgamuwa, D.P. Chiang Loh, F. Blaabjerg, 2007. A dual-functional medium voltage level DVR to limit downstream fault currents, Power Electronics, IEEE Transactions, 22: 1330-1340. Zhang, Y.H., D.M. Viathgamuwa and S.S. Choi., 2000. "An experimental investigation of dynamic voltage restorer (DVR)," Proceedings of Power Engineering Society Winter Meeting, Singapore, Piscataway, NJ, USA, IEEE, 4: 2745-2750. Chung, Y.H., H.J. Kim, G.H. Kwon, T.B. Park, S.H. Kim, K.S. Kim and J.W. Choe, 2007, Dynamic voltage restorer with neural network controlled voltage disturbance detector and real-time digital voltage control, IEEE Power Engineering Society General Meeting, pp: 1-7. Yan Hui, Li Jun and Tang Guoqing, 2004. "Study of series power quality compensator with feedback control strategy for inverters," Proceeding of the 2004 IEEE International Conference on Electric Utility Deregulation, Restructuring and Power Technologies Hong Kong, pp: 752-757. Zhou Xuesong, Zhang Zhiyong and Ma Youjie, 2007. "Research on dynamic voltage restorer with double closed-loop control strategy, " Power Electronics, 41(6): 34-36.

396